15 / 50
ctrlX CORE
Standards used
Bosch Rexroth AG
R911405645, Edition 05
Voltage dips at current supply interfaces
PS1 < 1 ms, evaluation criterion A
Electrical isolation
24 V supply (U
L
/U
L
GND) to the functional earth
24 V supply (U
P
/U
P
GND) to the functional earth
DC 707 V
24 V supply voltage (U
L
/U
L
GND and U
P
/U
P
GND)
to XF10, XF50, XF51 und XF23, XF24 at ctrlX
CORE
PLUS
X3
DC 1200 V
U
L
/U
L
GND to U
P
/U
P
GND
DC 1200 V
NOTICE
Electronic damage due to polarity reversal or due to a nominal current that is
too low
The power supply unit has to be able to deliver the quadruple nominal current
of the internal and external fuses to ensure that the fuse reliably triggers in
case of error.
8
Standards
8.1
Standards used
Table 5: Angewandte Normen – Standards used – Normes appliquées
Norm
Standard
Norme
Bedeutung
Meaning
Signification
Ausgabe
Edition
Édition
DIN EN 60204-1
Sicherheit von Maschinen
Elektrische Ausrüstung von Maschinen
–
Safety of machinery
Electrical equipment of machines
–
Sécurité des machines
Equipement électrique des machines
2019
DIN EN 61131-2
Speicherprogrammierbare Steuerungen
Teil 2: Betriebsmittelanforderungen und Prüfungen
–
Programmable controllers
Part 2: Equipment requirements and tests
–
Automates programmables
Partie 2: Spécifications et essais des équipements
2008
St
andar