About this product | Automax 100 | Extension module TS-AC E2-M3-1X
31/94
Bosch Rexroth AG | 05.2021 | DOK-SUPPL*-TS-AC E2-M3-ITRS-EN-P
Local diagnostics and status indicators
Local diagnostics and status indicators
Local diagnostics and status indicators
Des.
Color
Meaning
Status
Description
D
Red/
yellow/
green
Local bus communication diagnosis
Power down
Off
Participants in (power) reset.
Not connected
Red, flashing Participant working but there is no connection to upstream participant.
Reset
Red ON
Application reset
Participant working but there is still a connection to upstream participant,
application in reset.
Ready
Yellow ON
Participant working, there is a connection to upstream participant, participant
has not recognized valid cycle after power on.
Connected
Yellow,
flashing
Valid data cycles recognized but participant not (yet) part of current
configuration.
Device application
not active
Green/yellow
alternating
Valid data cycles are recognized.
Output data set to valid by master application, but input data not set to valid
by slave application.
Active
Green,
flashing
Participant working, communication within the station is OK.
Input data not read by master application. (For example, connection to the
controller has not yet been established.)
Run
Green ON
Valid data cycles are recognized. All data is valid.
UI
Green
U
Input
On
Feed-in of digital input modules available.
Off
Feed-in of digital input modules not available.
00 … 03,
10 … 13,
20 ... 23,
30 ... 33
Yellow
Status of inputs
On
Input is set.
Off
Input is not set.
5.2.7
Analog input module (-5KE1)
Module „S20-AI-4-I“ is used for receipt of analog current signals.
The information on the following pages is an excerpt from the data sheet.
Information on the data sheet can be found in chapter „
“ as of page [
].
Features
4 analog differential input channels for connection of current signals
Connection of sensors in 2, 3 and 4-wire circuit
Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, ±20 mA
Simultaneous sampling of all channels
High crosstalk attenuation between channels by separated signal paths
Diagnostics and status indicators
Содержание rexroth Automax 100
Страница 101: ......