12800
Death within 1-3 minutes.
* ppm = parts per million
** OSHA Occupational Safety & Health Association
The following symptoms may be related to CARBON MONOXIDE POISONING and should be
discussed with ALL members of the household:
–
Mild exposure: Headaches, running nose, sore eyes, often described as “flu-like”
symptoms.
–
Medium exposure: Dizziness, drowsiness, vomiting.
–
Extreme exposure: Unconsciousness, brain damage, death.
!
Warning!
Carbon monoxide poisoning
Many cases of reported CARBON MONOXIDE POISONING indicate that while victims are
aware they are not well, they become so disoriented they are unable to save themselves by
either exiting the building or calling for assistance.
8.2.2
Test/Silence (CO detector)
Notice!
At CO levels above 300 ppm, you cannot silence the detector.
To silence the detector:
–
Press the Test/Silence button (test button).
The red LED continues to flash. If detectable CO is still present, the detector will sound again
within 4 minutes. You can only silence the detector once during an actual CO incident.
8.2.3
Monitoring (CO detector)
The detector automatically monitors its status and updates every 50 seconds.
–
Press the test button to see the detector status.
–
If the detector is indicating a Sensor Fault, press the test button to silence the detector
for 24 hours. You can only silence the detector once for a fault.
The table below shows the status response to monitoring:
Monitoring summary
Status result
Red
LED(alarm)
Amber LED
(fault)
Green LED
(power)
Sounder
Action
Standby
No visual or audible indication if unit is OK
Unit OK
(Button test)
OFF
OFF
ON
Low to high
sound
Low Battery
OFF
1 flash
OFF
1 sound
Replace
batteries or
replace
Содержание RADION Life Safety