Praesideo 3.5
| Installation and User Instructions | 9 | System Configuration
en
| 400
•
Class-A switchover
•
Group A fault
•
Group A or B line fault
•
Group B fault
•
Incompatible hardware version
•
Pilot tone calibration failure
•
Unit missing
Loudspeaker faults are excluded from the list of zone
related faults that will activate the zone fault indicator,
so loudspeaker end-of-line supervision must be used
instead or additionaly to comply to EN54-16. This is
because in Praesideo loudspeaker faults are not assigned
to a specific amplifier output or zone, but only to the
loudspeaker itself, wherever it is.
It is also possible to configure this
Zone status
function on
an LBB4432/00 keypad, but then the second LED will
turn on for the active priority call, which is yellow. For a
zone fault the first LED will flash, which is green. In
most cases these colors are not acceptable, so better use
an LBB4434/00 with dedicated indicators. Also, on an
LBB4432/00 keypad these indicators cannot be
combined with the
Zone selection
key, which has its own
bi-color indicator. On a custom panel, using the
LBB4434/00 keypad kits, the indicators and switch of a
Zone selection
key and the
Zone status
indicators can be
grouped together to give a clear overview of the
selection.
•
Priority
- The action is activated if the priority is
equal to or higher than this specified priority.
•
Available outputs
- Shows the available zones,
zone groups and control outputs. Use the dropdown
list to choose the type of outputs that are shown.
•
Add/Remove buttons
- Using the
>
and
<
buttons, selected outputs can be added to or
removed from
Assigned outputs
.
•
Assigned outputs
- Shows the outputs that have
been assigned to the key.
47.3.33 Zone priority status
The
Zone priority status
action is intended for
LBB4434/00 Call Station Keypad Kits. The key/input
itself is not used by this action; only the indicator/output
attached to the key is activated. The
Zone priority status
action activates the indicator/output belonging to the
key if there is a call made to the zone with a priority
equal to the defined priority. The purpose of this
function is to be able to build a custom display with
zone indicators that will show in which zones a call with
a specific priority is busy. In this way the indicators can
show whether a certain emergency or alert message is
running in a zone by setting the defined priority to the
priority of that message.
See figure 47.39 for an overview of the
Action
programming
page for a
Zone priority status
key.
Configuring a
Zone priority status
key is similar to
configuring a
Zone status
key (see section 47.3.32).
figure 47.38: Zone status key
figure 47.39: Zone priority status key
Содержание Praesideo 3.5
Страница 1: ...Praesideo 3 5 Installation and User Instructions Digital Public Address and Emergency Sound System en ...
Страница 131: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 4 Amplifiers en 131 Part 4 Amplifiers ...
Страница 201: ...Bosch Security Systems 2011 02 2011 02 Installation and User Instructions 5 Call Stations en 201 Part 5 Call Stations ...
Страница 309: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 8 Software en 309 Part 8 Software ...
Страница 411: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 10 Events en 411 Part 10 Events ...
Страница 487: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 12 Appendices en 487 Part 12 Appendices ...
Страница 497: ......
Страница 498: ... Bosch Security Systems B V Data subject to change without notice 2011 02 ...