47
Action programming
47.1 Introduction
On the
Action programming
pages, the keys of the
keypads and the control inputs can be configured. The
process of configuring a key or control input consists of
two steps:
1 Assigning a behavior (see section 47.2).
2 Assigning an action (see section 47.3).
47.2 Behavior
47.2.1 Introduction
The behavior specifies how the control input deals with
incoming signals or how the key reacts when it is
pressed. The following behaviors are available:
•
Momentary on break or make (see section 47.2.2).
•
Single shot on break or make (see section 47.2.3).
•
Toggle on break or make (see section 47.2.4).
47.2.2 Momentary behaviors
47.2.2.1 Momentary
If the behavior is momentary, the action coupled to the
control input or key is active during the time the
external contact is closed.
47.2.2.2 Momentary with immediate abort
If the behavior is momentary with immediate abort, the
action coupled to the control input or key is active
during the time the external contact is closed. For an
example, see figure 47.2. When the external contact is
opened, the action is immediately aborted.
47.2.2.3 Momentary with phase completion and abort
on repress
If the behavior is momentary with phase completion
and abort on repress, the action coupled to the control
input or key is active during the time the external
contact is closed. For an example, see figure 47.3. When
the external contact is opened, the action is stopped
after the completion of the current phase
When the external contact is closed again while the
action is still running, the action is immediately aborted.
For an example, see figure 47.4.
figure 47.1: Momentary behavior
make
break
action
figure 47.2: Momentary with immediate abort
figure 47.3: Momentary with phase completion and
abort on repress (1)
figure 47.4: Momentary with phase completion and
abort on repress (2)
make
break
action
start/stop
start
call
abort
make
break
action
start/stop
start
call
stop
make
break
action
start/stop
start
call
stop
abort
Содержание Praesideo 3.5
Страница 1: ...Praesideo 3 5 Installation and User Instructions Digital Public Address and Emergency Sound System en ...
Страница 131: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 4 Amplifiers en 131 Part 4 Amplifiers ...
Страница 201: ...Bosch Security Systems 2011 02 2011 02 Installation and User Instructions 5 Call Stations en 201 Part 5 Call Stations ...
Страница 309: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 8 Software en 309 Part 8 Software ...
Страница 411: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 10 Events en 411 Part 10 Events ...
Страница 487: ...Bosch Security Systems 2011 02 Praesideo 3 5 Installation and User Instructions 12 Appendices en 487 Part 12 Appendices ...
Страница 497: ......
Страница 498: ... Bosch Security Systems B V Data subject to change without notice 2011 02 ...