background image

MDCI Series – All DC Inverter Outdoor Units (Three phase) 

6 720 862 442 (2016/04)

OPEARTING CONDITIONS  |  5

   

 NOTE

 

On completion of installing the air conditioning unit, ensure the 
electrical power supply is on to the unit for the minimum of 12hrs 
prior to operation.  Failure to do so, may result in product failure.  
Should the units electrical power supply be interrupted for a period 
of more than 24hrs, then the above process will have to be   repeated.

 

Pay attention not to block the air inlet and outlet. Blockages may 
decrease the efficiency of the unit or shut the unit down via it‘s 
protection devices.

3.  OPEARTING CONDITIONS

See the table below for safe and effective use of the system.  Maximum and 
minimum temperatures are displayed.

Table 3-1

Temperature

Mode

Outdoor temperature Room temperature

Cooling operation

-15°C~46°C

21°C~32°C

Heating operating

-15°C~24°C

0°C~28°C

   

 NOTE

1.  If air conditioning unit is used outside the above conditions, it may 

cause the unit to function abnormally.

2.  The units can produce condense water when the humidity is high.

3.  Optimum performance will be achieved within these operating 

temperatures.

4.  The A-weighted sound pressure level is below 70 dB.

4.  OPERATION AND PERFORMANCE

4.1  Protection Equipment

The protection devices will stop the unit from running when an error is 
detected.

This protection device will stop the unit automatically. When a protection 
device is activated, the running indicator flashes. The protection device may 
have been activated as a result of the following circumstances.

The protection devices may be activated in following conditions:

 

Cooling Operation

 

The air inlet or air outlet on the outdoor unit is blocked.

 

Strong winds are continuously blowing on the air outlet.

 

Heating Operation

 

The indoor unit filters are blocked

 

The air outlet on the indoor unit is blocked

   

 NOTE

Do not attempt to re-activate the electrical power supply to the unit via 
the protection device until the problem has been solved.

4.2  Electrical power to the unit is interrupted

 

Should the electrical power supply be interrupted, all operation of the 
unit will stop.  Isolate the main electrical supply to the unit until the 
electrical power supply has returned and stabilised.

 

When the electrical power supply is re-established, the controller will 
flash and will begin to initialise.

 

Communication problem. 

 

Should the communication between units be lost, switch off the 
electrical power supply to all indoor/outdoor units.  Firstly re-instate 
the power to the indoor units, then re-instate the power to the 
outdoor unit.

4.3  Heating capacity

 

If the outdoor ambient temperature decreases, then the output of 
heat discharged from the indoor units will also decrease.

 

In cold temperatures the unit will default to heating mode only.

   

 NOTE

1.  Should the electrical power supply be interrupted, the indoor units 

will run for 20-30 seconds after to reject all of the heat built up.

4.4  Five-minute protection feature

 

A protection feature prevents the air conditioning unit from being 
activated for approximately 5 minuites when it restarts immediately 
after operation.

4.5  Cooling and heating operation

 

The indoor units must run in the same mode to stop conflicting errors. 
All units must be selected in the same mode.

 

When two different modes are selected the heating mode will take 
priority. However if a priority mode has been set up, then this will take 
priority. You can set a priority of ‚first unit turned on in the morning 
is the master‘, ‚heating priority‘, ‚cooling priority‘ or ‚a single unit as 
priority‘.

 

If the Air conditioning unit has a running mode selected, then the 
air conditioner can not run on modes other than the pre-set one. 
Standby or No Priority will show on the display.

4.6  Features of heating operation

 

The fans inside the indoor units may stop periodically to avoid 
discharging the incorrect temperature of air into the room.  The 
fans will start again once the unit has the sufficient temperature to 
discharge.  This will also be apparent for the first 3-5 minutes from 
when the unit is first turned on.

Содержание MDCI20-3

Страница 1: ...ur air conditioning unit please read this manual carefully and keep it for future reference 6 720 862 442 2016 04 User manual CLIMATE 5000 VRF MDCISeries AllDCInverterOutdoorUnits Threephase MDCI20 3 MDCI22 3 MDCI26 3 ...

Страница 2: ... Refrigerant pipework connector 4 Connection pipework Fig 1 NOTE All the pictures in this manual are for explanation purposes only They may be slightly different from the air conditioning unit you have purchased dependent on model Indoor unit Outdoor unit ...

Страница 3: ...tect the heat exchanger When the unit is running fans will be operating Keep hands away from fan blades to prevent injury Ensure cleaning products do not come into contact with any of the units electrical components Caution should also be taken when using any other flammable or corrosive products close to the unit Never put any objects into the air inlet or outlet Objects touching the fan at high ...

Страница 4: ...ESCRIPTION OF UNIT The air conditioning system consists of an outdoor unit indoor units connective pipework and a way of controlling the system remote controller see Fig 1 Force Cooling Control Force cooling control Button sw1 Display control button sw2 MAIN BOARD OUTDOOR UNIT sw1 sw2 Force Cooling Control Fig 2 1 Force cooling control of the outdoor unit is to be pressed when test running The uni...

Страница 5: ... via the protection device until the problem has been solved 4 2 Electrical power to the unit is interrupted Shouldtheelectricalpowersupplybeinterrupted alloperationofthe unit will stop Isolate the main electrical supply to the unit until the electrical power supply has returned and stabilised When the electrical power supply is re established the controller will flash and will begin to initialise...

Страница 6: ... do not match Irrecoverable HF 8 Reserved Recoverable E1 9 Communication fault between the outdoor and indoor units Recoverable E2 10 T3 T4 temperature sensor fault Recoverable E4 11 Voltage protection fault or a lack of Phase B Phase N Recoverable E5 12 DC fan motor fault Recoverable E6 13 Discharge temperature sensor fault Recoverable E7 14 A fan in the A region run for more than 5 minutes in he...

Страница 7: ... until the unit has stopped When the drain pump optional accessories is in operation a noise will be heard When the system stops after heating the system will encounter a noise whilst the refrigerant settles down Expansion valves shut down and refrigerant gets trapped in the system Symptom 4 2 Indoor unit outdoor unit A continuous low hissing sound is heard when the system is in operation This is ...

Страница 8: ...rrect refrigerant pressure Vacuum and recharge refrigerant Maintenance or change compressor Install manostat A qualified person should investigate Low cooling effect Outdoor unit and indoor unit heat exchangers are dirty The air filter is dirty Inlet outlet of indoor outdoor units is blocked Doors and windows are open Direct sunshine on outdoor unit Too much heat resource Outdoor temp is too high ...

Страница 9: ...ler need changing The power supply is off The TEMP indicator does not come on Check whether the MODE indicated on the display is FAN ONLY The temperature cannot be set during FAN mode The indication on the display disappears after of time Check whether the timer operation has come to an end and TIMER OFF is not indicated on the display The air conditioning unit operation will stop at it s set time...

Страница 10: ...6 720 862 442 2016 04 MDCI Series All DC Inverter Outdoor Units Three phase NOTES 10 ...

Страница 11: ...MDCI Series All DC Inverter Outdoor Units Three phase 6 720 862 442 2016 04 NOTES 11 ...

Страница 12: ......

Отзывы: