30
|
Operating Temperatures and Pressures
LM Series Heat Pump
LM Series Heat Pump
8 733 905 315 (2013/9)
Subject to change without prior notice
OPERATING TEMPERATURES AND
PRESSURES
Operating Temperatures and Pressures
COOLING
HEATING
Model
Entering
Water
Temp. F
Wat
er
Flow
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Rise °F
Air
Temp
Drop °F
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Water
Temp
Drop
Air
Temp
Rise °F
LM024
Part
Load
30°
4
75-91
264-322
5-6
15-17
8
79-96
270-331
3-4
16-18
40°
4
88-107
277-339
6-7
17-20
8
115-140
175-214
8-9
19-23
92-112
284-348
4-5
18-21
50°
4
129-157
218-267
14-17
18-20
98-122
291-356
7-8
20-23
8
124-151
204-250
8-9
19-22
110-130
298-364
5-6
21-24
60°
4
134-163
249-305
13-16
17-20
112-136
304-372
8-10
22-26
8
128-156
233-287
8-9
18-21
117-143
312-381
6-7
23-28
70°
4
138-168
281-341
13-16
17-19
124-152
318-389
9-11
24-29
8
133-161
263-323
7-9
18-21
131-159
325-398
6-8
26-31
80°
4
143-174
317-388
13-16
16-19
136-166
331-405
11-13
27-32
8
137-167
297-366
7-9
17-20
143-174
339-415
7-9
28-33
90°
4
147-179
357-437
13-16
16-18
149-181
345-422
12-14
29-35
8
141-172
335-411
7-9
17-20
156-190
352-432
8-10
31-37
100°
4
151-185
402-492
13-15
15-18
8
146-177
378-459
7-9
16-19
LM024
Full
Load
30°
4
76-92
242-297
3-4
13-14
8
80-97
249-304
2-3
13-15
40°
4
125-151
180-221
14-18
19-22
89-108
255-312
4-5
15-17
8
120-146
169-207
8-10
20-23
93-113
261-320
3-3
16-18
50°
4
134-163
211-258
14-18
18-21
106-118
267-327
5-6
17-19
8
129-157
198-242
8-10
19-23
110-126
274-335
3-4
18-21
60°
4
139-169
241-295
14-17
18-21
113-138
280-342
6-7
19-22
8
134-163
227-278
8-10
19-22
119-145
287-351
4-5
20-23
70°
4
144-175
272-333
14-17
17-20
126-155
292-358
7-8
21-24
8
138-168
255-313
8-10
18-21
133-162
300-367
5-6
22-26
80°
4
148-181
307-375
14-17
17-19
138-168
305-373
8-9
23-27
8
143-174
288-353
8-10
18-21
145-177
312-382
5-6
24-29
90°
4
153-186
346-423
14-17
16-19
151-184
317-388
8-10
25-29
8
147-179
325-398
8-9
17-20
158-193
325-398
6-7
26-31
100°
4
158-191
389-477
13-16
16-18
8
152-185
366-448
8-9
17-20
This chart shows approximate temperatures and pressures for a unit in good repair. The values shown are meant as
a guide only and should not be used to estimate system charge. This chart assumes rated air flow and 80º d.b./67º
w.b. entering air temperature in cooling, 70º d.b. entering air temperature in heating. Heating data at entering fluid
temperatures below 50º assumes the use of antifreeze. As a result of continuing research and development,
specifications are subject to change without notice.
Содержание LM Series
Страница 39: ...Wiring Diagrams 39 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 26 ...
Страница 41: ...Wiring Diagrams 41 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 28 ...
Страница 43: ...Wiring Diagrams 43 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 30 ...
Страница 45: ...Wiring Diagrams 45 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 ...
Страница 47: ...Wiring Diagrams 47 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 31 ...
Страница 49: ...Wiring Diagrams 49 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 33 ...
Страница 53: ...WIRING HARNESS DRAWINGS 53 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 Figure 37 Single Phase ...
Страница 55: ...Dimensional Drawings 55 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 DIMENSIONAL DRAWINGS Figure 39 ...
Страница 59: ...Notes 59 LM Series Heat Pump 8 733 905 315 2013 9 Revised 09 13 NOTES ...