Commercial Series TriTech Motion Detector

ISC-CDL1-W15G, ISC-CDL1-W15G-CHI, ISC-CDL1-W15H, ISC-CDL1-W15K

 

 

en

Reference Guide

 

Содержание ISC-CDL1-W15G

Страница 1: ...Commercial Series TriTech Motion Detector ISC CDL1 W15G ISC CDL1 W15G CHI ISC CDL1 W15H ISC CDL1 W15K en Reference Guide ...

Страница 2: ......

Страница 3: ...3 7 3 4 Adjustable microwave sensitivity 24 7 4 Self test 24 8 Troubleshooting 25 8 1 Motion detector does not appear to respond to motion 25 8 2 Motion detector is in continuous alarm 25 8 3 Motion detector appears normal but does not send alarms to the control panel 25 8 4 Motion detector does not appear to detect motion in the space directly under it 25 8 5 Motion detector does not appear to de...

Страница 4: ... At least once per year vary the range and coverage To ensure continual daily operation instruct the end user to walk through the far end of the coverage pattern This ensures an alarm output prior to arming the system 1 4 en Safety Commercial Series TriTech Motion Detector 2015 06 02 F 01U 314 294 Reference Guide Bosch Security Systems Inc ...

Страница 5: ...ntellectual property of Bosch Security Systems Inc and is protected by copyright All rights reserved Trademarks All hardware and software product names used in this document are likely to be registered trademarks and must be treated accordingly Bosch Security Systems Inc product manufacturing dates Use the serial number located on the product label and refer to the Bosch Security Systems Inc websi...

Страница 6: ...t Callout Description Callout Description 1 Removable terminal block 5 Look down adjustment 2 Removable bubble level 6 Resistor jumpers 3 Wall Tamper 7 Configuration switches 4 Self locking cam lock 8 Microwave adjustment 3 6 en Detector overview Commercial Series TriTech Motion Detector 2015 06 02 F 01U 314 294 Reference Guide Bosch Security Systems Inc ...

Страница 7: ...on detector away from Glass exposed to the outdoors Objects that might change temperature rapidly such as heat sources air conditioning outlets or surfaces heated by sunlight Objects that small animals such as birds and mice might climb on stairs shelves ledges furniture and appear in the upper zones of the PIR which are more sensitive Small animals in close proximity in the field of view of the m...

Страница 8: ...ows The PIR sensor does not detect through glass Near doors and windows or other openings where cold or warm air can flow onto the detector Do install Where an intruder is most likely to cross through the coverage pattern Within recommended mounting height range measured from the floor On solid vibration free surface 8 en Installation considerations Commercial Series TriTech Motion Detector 2015 0...

Страница 9: ... animals such as rodents up to 4 5 kg 10 lbs when mounted according to the installation considerations listed in this document Commercial Series TriTech Motion Detector Installation considerations en 9 Bosch Security Systems Inc Reference Guide 2015 06 02 F 01U 314 294 ...

Страница 10: ...position Hold the base and slide the unit body down then lift the cover to remove it from the base Figure 5 1 Unlocking the base and removing the body Place the motion detector onto the base When you remove the motion detector body from the base the cam automatically returns to the locked position When you place the motion detector body onto the base the cam must remain in locked position Do not m...

Страница 11: ...formance when mounted vertically The motion detector base includes a removable bubble level which helps you align the unit Before drilling the mounting holes in the surface use the bubble level to align the motion detector Refer to Bubble level page 14 Mount directly to the surface When surface mounting select the mounting holes shown in the following figure Drill the holes or tap them out with a ...

Страница 12: ...ket allows you to insert the wiring through the black tube section in the center of the bracket mounting plate and through the back of the motion detector base The B338 bracket designed for ceiling mounting allows a vertical pivot range of 7º to 16º and a horizontal pivot of 45º The bracket allows you to insert the wiring through the ceiling cavity and into the motion detector base When using a mo...

Страница 13: ...ed by UL Brackets are not EN50131 compliant Notice Do not use the bracket to tip the motion detector vertically unless you intend to compensate for a non vertical surface It may cause false alarms or reduced catch performance Wire knockouts Use the following figure to determine the knockouts to use for the desired installation 5 3 Commercial Series TriTech Motion Detector Installation en 13 Bosch ...

Страница 14: ...en the walls and behind the terminal block other features such as EOL resistor jumper pins cannot interfere with or puncture the wires Bubble level The motion detector s coverage pattern performs optimally when mounted vertically The motion detector base includes a removable bubble level which helps you align the unit Before drilling the mounting holes in the surface use the bubble level to align ...

Страница 15: ...l the base is level and mark the remaining surface mounting hole locations 5 Remove the bubble level from the round cavity and place it back to its original position Notice Do not leave the bubble level in the circular holder You cannot properly place the motion detector body onto the mounting base with the bubble level in the circular holder Do not use a bracket to tip the detector in any directi...

Страница 16: ...rce Alarm terminals Normally closed solid state voltage free dry contact relay The contacts are closed shorted during the warm up period and during normal operation when no alarm is detected or if only one technology PIR or Microwave is active The alarm contacts change to open status under the following conditions Insufficient input power Motion alarm condition both PIR and microwave activity Noti...

Страница 17: ...shown in the alarm control panel documentation Notice Built in resistor values cannot meet every control panel resistor value requirement If the connected control panel resistor values and loop structure do not match the combinations allowed by the built in resistors make sure to remove the jumpers and use only external resistors NC NC T T 1 2 2 2 k 1 0 k 2 2 k 33 k 1 0 k Figure 6 2 EOL resistors ...

Страница 18: ...elp of this resistor The loop continuity breaks and indicates a tamper condition if any of the following occurs the tamper switch opens the motion detector body is removed from the base or the wire is cut The available resistance values are 1 kΩ 2 2 kΩ and 33 kΩ Notice When using single EOL loops this resistor represents the EOL resistor Refer to the control panel documentation to verify whether i...

Страница 19: ...built in resistors for the same output Do not use both Single EOL loop Alarm and Tamper 1 2 2 2 k 1 0 k 2 2 k 33 k 1 0 k 2 NC T T NC NC NC T T 1 2 2 2 k 1 0 k 2 2 k 33 k 1 0 k 1 2 2 2 k 1 0 k 2 2 k 33 k 1 0 k 1 2 3 Figure 6 5 Single EOL Loop Callout ᅳ Description 1 ᅳ 1 kΩ 2 ᅳ 2 2 kΩ 3 ᅳ 33 kΩ 6 3 6 3 1 Commercial Series TriTech Motion Detector Wiring en 19 Bosch Security Systems Inc Reference Guid...

Страница 20: ... 33 k 1 0 k 1 2 2 2 k 1 0 k 2 2 k 33 k 1 0 k 1 2 3 4 Figure 6 6 Double EOL Loop Callout ᅳ Description 1 ᅳ 1 kΩ Alarm 1 kΩ Tamper 2 ᅳ 1 kΩ Alarm 2 2 kΩ Tamper 3 ᅳ 2 2 kΩ Alarm 1 kΩ Tamper 4 ᅳ 2 2 kΩ Alarm 2 2 kΩ Tamper 6 3 2 20 en Wiring Commercial Series TriTech Motion Detector 2015 06 02 F 01U 314 294 Reference Guide Bosch Security Systems Inc ...

Страница 21: ...ft to disable the look down zone Turn right to enable the look down zone ON 1 2 Figure 7 1 Setting the optional look down zone Walk test LED The walk test LED indicates the motion detector condition depending on status 2 min During the warm up period after providing power to the device the LED flashes continuously until the device is ready for use During walk test the LED indicates simultaneous PI...

Страница 22: ... walk test LED automatically changes brightness In dark environments the LED intensity lessens in bright environments the LED intensity increases Walk test Before you begin the walk test review the walk test LED indicator statuses Refer to Walk test LED page 21 At the beginning of the test with no motion in the protection area the LED should be OFF If you observe LED activity without movement chec...

Страница 23: ...ion detector body onto the base 4 Wait at least 2 minutes 5 Repeat walk test procedures and range increase until the PIR and microwave detection range is as desired 6 If on the last walk test you observe LED activity while walking outside the coverage area decrease the microwave range and repeat the walk test Notice Do not adjust the microwave range higher than required Doing so might cause the mo...

Страница 24: ...eter as instructed to reduce the potential for false alarms or for very large rooms The following figure shows how to adjust the setting using the potentiometer Turn counterclockwise to reduce sensitivity ON 1 2 Figure 7 4 Microwave potentiometer adjustment Self test The motion detector performs a routine self test every 7 hours testing both the PIR and microwave circuit If either technology fails...

Страница 25: ... control panel Potential causes Incorrect alarm loop resistance configuration Incorrect alarm loop wiring Motion detector does not appear to detect motion in the space directly under it Potential causes The look down zone is disabled Motion detector does not appear to detect motion near the edge of the coverage area Potential causes Microwave range too short PIR sensitivity too low Mounting height...

Страница 26: ...nit Motion detector LED flashes four times in a row repeatedly Potential causes The motion detector failed during the routine self test Motion detector LED flashes five times in a row repeatedly Potential causes The supply voltage is too low 8 7 8 8 8 9 26 en Troubleshooting Commercial Series TriTech Motion Detector 2015 06 02 F 01U 314 294 Reference Guide Bosch Security Systems Inc ...

Страница 27: ... 30 C to 55 C 22 F to 130 F UL 0 C to 49 C 32 F to 120 F AFNOR CNPP 10 C to 55 C Mechanical Color White Dimensions 120 mm x 70 mm x 55 mm 4 7 in x 2 75 in x 2 2 in Wire size Ø 0 40 mm to 1 29 mm 26 AWG to 16 AWG UL 22 AWG to 16 AWG Material High impact ABS plastic Coverage pattern The protected coverage area is where the microwave and PIR patterns overlap For the following figure Dark green PIR de...

Страница 28: ...2 m 0 m 2 m 4 m 6 m 7 5 m 0 ft 25 ft 20 ft 13 ft 7 ft 0 ft 7 ft 13 ft 20 ft 25 ft 2 3 m 7 5 ft 2 75 m 9 ft 12 m 39 ft 14 m 46 ft 90 Figure 9 1 Coverage pattern 28 en Specifications Commercial Series TriTech Motion Detector 2015 06 02 F 01U 314 294 Reference Guide Bosch Security Systems Inc ...

Страница 29: ......

Страница 30: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2015 Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany ...