9.1 Fault 

Descriptions 

1 System 

Fault 

 

A system fault only displays when any of 
the following faults occur. After entering 
Fault Analysis Mode, press and hold the [1] 
key to determine which of the following 
faults occurred.  

 

Low Battery Fault

 – A low battery fault 

registers when the system detects a low 
capacity back-up battery. The system 
automatically performs a battery test every 
four hours and every time you arm the 
system. 

 

Date and Time

 – The date and time fault 

registers every time the system is powered 
down. This type of fault does not cause the 
FAULT indicator to display on the codepad 
unless your installer programmed the 
automatic arming time. Refer to 

Section 10. 

Date and Time

 on page 13 to program the 

date and time. 

 

RF Receiver Fail

 – The RF receiver fault 

registers once the system detects that the 
wireless receiver unit is disconnected. 

 

Horn Speaker Fail

 – This fault registers 

when the system detects that the horn 
speaker is disconnected. This fault clears 
once the horn speaker is reconnected. Your 
installer must program the system for this 
feature to operate. 

 

Telephone Line Fail

 – A telephone line 

fault registers when the system detects that 
the telephone line is disconnected from the 
control panel. Your installer must program 
the system for this feature to operate. 

 

EEPROM Fail

 – An EEPROM fail registers 

when the system detects an internal 
checksum error. Contact your installer as 
soon as this fault displays. 

 

AUX Power Supply Fail

 – This fault 

occurs when either of the two 1 A AUX 
power supplies fails. Contact your installer 
as soon as this fault displays. 

RF Low Battery 

 

This fault occurs when any of the RF 
wireless devices report a low battery 
condition to the control panel. While in 
Fault Analysis Mode, press and hold the [2] 
key until two beeps sound. This displays the 
zone reporting the RF Low Battery fault. 

 

 

Zone Tamper Fail  

 

This fault occurs when any zone becomes 
an open circuit. Press and hold the [3] key 
until two beeps sound. This displays the 
zone reporting the tamper fail fault. 

Sensor Watch Fault 

 

A sensor watch fault registers because one 
or more detection devices failed to detect 
any movement during the disarmed state 
for the time period programmed by your 
installer. The fault clears once the zone in 
question detects movement and resets. 

Press and hold the [4] key until two beeps 
sound. This displays the zone reporting the 
sensor watch fault. 

RF Sensor Watch 

 

An RF sensor watch fault registers because 
one or more RF detection devices fails to 
communicate to the RF radio receiver for 
the time period programmed by your 
installer. The fault clears once the RF 
device in question successfully transmits to 
the RF radio receiver. 

Press and hold the [5] key until two beeps 
sound. This displays the RF detection 
device reporting the RF sensor watch fault. 

6 Communication 

Fail 

 

A communication fail registers when the 
control panel fails to communicate with the 
receiving party (such as a monitoring 
company, mobile phone, or pocket pager). 
The communication fault clears once the 
control panel successfully reports to the 
receiving party. 

To determine which receiver failed to 
communicate, press and hold the [6] key. 

10.   Date and Time 

Programming the date and time is only required 
when you need functions such as automatic test 
reports, automatic arming, and history events to 
operate correctly. 

How to Program the Date and Time 

1.

 

Enter your four character Master Code, followed 
by [6] and the [#] key (for example, [25806#]). 
Three beeps sound, and the STAY and AWAY 
indicators flash. 

2.

 

Enter the day, month, year, hour, and minute 
(DD, MM, YY, HH, MM format) (for example, 
DD = day of the month, MM = month of the 
year, YY = current year, HH = hour of the day, 
MM = minute of the day). 
To program the hour of the day, use the 24:00 
hour format. 

Содержание ICP-CC488

Страница 1: ...EN User s Guide ICP CC488 Control Panel ICP CC488 ...

Страница 2: ... telecom customers Immediately disconnect this equipment should it become physically damaged and arrange for its disposal or repair The transmit level from this device is set at a fixed level and because of this there may be circumstances where the performance is less than optimal Before reporting such occurrences as faults please check the line with a standard telepermitted telephone and do not r...

Страница 3: ...ce 14 13 2 Telco Disarm Sequence 14 14 Testing 15 14 1 Horn Speaker Test 15 14 2 Bell Test 15 14 3 Strobe Test 15 14 4 Walk Test Mode 15 14 5 Test Report 15 15 Event Memory 15 16 Day Alarm 15 17 Codepad Buzzer Tone Change 15 18 Remote Arming by Telephone 16 19 Partitioning 16 19 1 Master Partitioned Codepad Indicators 16 19 1 1 Zone Indicators 16 19 1 2 Area On Off Indicators 16 19 1 3 Area Displa...

Страница 4: ...able 9 How to Arm the System in AWAY Mode 8 Table 10 How to Arm the System in STAY Mode 1 8 Table 11 Fault Indicators 12 Table 12 Telco Arm Disarm Dialing Digits 15 Table 13 Domestic Dialing Telephone Digits 17 Table 14 Zone Status Display Descriptions 18 Table 15 System Status 18 Table 16 Glossary of Terms 20 ...

Страница 5: ...s and options are detailed however suitability is left up to the individual Every system can be tailored to meet all requirements quickly and easily 2 Specifications Table 1 Specifications Temperature Range 0 o C to 45 o C 32o F to 113o F Humidity 10 to 95 Power Source TF008 Plug Pack 240 V 18 VAC 1 3 A Stand By Current 65 mA Current Draw in Alarm Condition 115 mA Current Draw in Alarm Condition w...

Страница 6: ...one is manually isolated or selected to be isolated 3 2 AWAY Indicator The AWAY indicator displays that the system is armed in AWAY Mode The AWAY indicator flashes in unison with the STAY indicator when programming various options throughout the Operators Manual Refer to Section 3 10 2 Arming in AWAY Mode for information on the different methods of arming the system in AWAY Mode Table 3 AWAY Indic...

Страница 7: ...wledged 3 9 Audible Indications Table 7 defines the audible indicators given out by the codepad buzzer Table 7 Audible Indicators Audible Indicator Definition One short beep A button was pressed on the codepad or Exit Time ended when armed in STAY Mode 1 or STAY Mode 2 Two short beeps The system accepted your code Three short beeps The requested function was executed One long beep Indicates the en...

Страница 8: ...are two different methods for arming the system in STAY Mode 1 Method one is standard and always operates Method two is optional and may be disabled by your installer if you do not want to use single button arming Entry Guard Timer for STAY Mode 1 When arming the system in STAY Mode 1 an optional entry timer called Entry Guard Timer for STAY Mode 1 is available Use this entry timer to delay the si...

Страница 9: ...ally isolated in STAY Mode 2 repeat Step 2 as many times as required 3 Press the button to exit this mode when you finish selecting all zones to be automatically isolated in STAY Mode 2 Two beeps sound and the STAY and AWAY indicators turn off 4 Disarming the System When you enter the premises after the system is armed in AWAY mode or if you armed the system in STAY Mode 1 or STAY Mode 2 you must ...

Страница 10: ... and the STAY and AWAY indicators flash 2 Enter the user code number 1 to 16 followed by the button for example 2 User 2 16 User 16 Two beeps sound and the selected user number displays on the codepad indicators 3 Press the button to delete the selected User Code Two beeps are heard and the STAY and AWAY indicators turn off To delete other User Codes repeat this procedure as many times as required...

Страница 11: ...r of incorrect code attempts equals the number programmed by your installer the system activates an alarm condition If reporting back to a security monitoring station the system sends an Access Denied report To shutdown and lockout a codepad for a period of time 0 sec to 150 sec ask your installer to program this function 8 Isolating Zones Use isolating zones to manually disable one or more zones ...

Страница 12: ...ault and stops the codepad from beeping once every min How to Determine the Type of System Fault To determine which system fault occurred enter Fault Analysis Mode by following the steps below 1 Hold down the 5 key until two beeps sound The FAULT indicator remains steady and the STAY and AWAY indicators flash in unison A zone indicator displays the type of fault that occurred for example Zone 1 Sy...

Страница 13: ...is Mode press and hold the 2 key until two beeps sound This displays the zone reporting the RF Low Battery fault 3 Zone Tamper Fail This fault occurs when any zone becomes an open circuit Press and hold the 3 key until two beeps sound This displays the zone reporting the tamper fail fault 4 Sensor Watch Fault A sensor watch fault registers because one or more detection devices failed to detect any...

Страница 14: ...elecommunications provider has the call forward option available The examples given in this feature are only applicable to Australia Call Forward Immediate On You can redirect calls to anywhere in Australia including mobile phones pagers and answering services When Call Forward is turned on your telephone does not ring Call Forward No Answer When your telephone is not answered within 20 sec this f...

Страница 15: ...rt This feature only applies if your system reports using the telephone By holding down the 9 key until two beeps sound the system sends a Test Report 15 Event Memory Use this function to replay the last 40 events that the system recorded The event memory history replays all alarms and the arming disarming of the system in AWAY Mode STAY Mode 1 and STAY Mode 2 However the system cannot differentia...

Страница 16: ... can be operated from one Master Partitioned codepad or from separate Area Addressable codepads 19 1 Master Partitioned Codepad Indicators The indicators on a Master Partitioned codepad are configured into four groups such as Zone Indicators Area On Off Display Area Display and Status Indicators Figure 8 ICP CP500PW Master Partitioned Codepad 19 1 1 Zone Indicators Zone indicators 1 to 8 show the ...

Страница 17: ...ween siren tones the control panel hangs up after 2 min and calls the next telephone number Pressing the key for 1 sec to 3 sec during the pause acknowledges the call No further calls are made for that event If the call was successfully acknowledged a tone of decreasing pitch sounds Table 13 Domestic Dialing Telephone Digits Digit Required Number to Program Digit Required Number to Program 0 0 8 8...

Страница 18: ...on 0 Zone Normal Indicates that the corresponding zone is in the sealed state 1 Alarm Indicates that the corresponding zone is unsealed and in alarm condition 2 Zone Bypassed Indicates that a system operator manually isolated the corresponding zone Refer to Section 8 Isolating Zones 11 for information on how to manually isolate a zone s prior to arming the system 3 Zone Trouble Indicates that a zo...

Страница 19: ...01U089456 02 Figure 9 Basic Pager Display 1 Subscriber ID number 2 Zone status 3 System status 4 0 Zone Normal 1 Alarm 2 Manually Isolated 3 Auto Isolated 5 8 Disarmed 9 Armed 6 0 Normal 1 Panic Duress 2 Fire Alarm 3 Medical Alarm 7 0 AC Normal 1 AC Failure 8 0 System Normal 1 System Fault ...

Страница 20: ...ile the system is disarmed detector A unit installed as a satellite component in a security system designed to detect an intruder within a protected area Some common forms of detection devices are passive infrared smoke photo electric beams reed switches and vibration sensors disarmed A system status that does not accept alarms except for 24 Hour zones dynamic battery testing A method used to moni...

Страница 21: ...hat automatically isolates certain zones when the security system is armed in this mode Only the installer can program these zones STAY Mode 2 A condition that automatically isolates certain zones when the security system is armed in this mode The Master Code holder can program these zones telco arming sequence A feature that automatically diverts a telephone number to another telephone when a sec...

Страница 22: ...llation Notes EN 22 Bosch Security Systems Inc 12 08 F01U089456 02 23 Installation Notes Installation Company Technician s Name Technician s Telephone Number Installation Date Warranty Expiration Panel Software Version Service Notes ...

Страница 23: ...lows you to describe each zone and mark whether the zone was programmed to be automatically isolated in STAY Mode 1 or was programmed for day alarm operation Isolated In STAY Mode 1 Day Alarm Enabled Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone 16 ...

Страница 24: ...e 13 User Code 6 User Code 14 User Code 7 User Code 15 User Code 8 User Code 16 Entry Exit Times Entry Timer 1 Exit Time Entry Timer 2 Entry Guard Time Arming Options Single Button Arming YES NO Forced Arming YES NO Single Button Disarming YES NO Remote Arming by Telephone YES NO Automatic Arming Time AM PM Automatic Disarming Time AM PM Output Descriptions Output 1 Output 3 Output 2 Output 4 Isol...

Страница 25: ... Radio User code 10 ID Number 14 Radio User code 14 ID Number 11 Radio User code 11 ID Number 15 Radio User code 15 ID Number 12 Radio User code 12 ID Number 16 Radio User code 16 ID Number 9 Digit RF Device ID Numbers Place the RF Device ID Sticker in the appropriate location below Zone Number Zone Number 1 RF Device 1 ID Number 9 RF Device 9 ID Number 2 RF Device 2 ID Number 10 RF Device 10 ID N...

Страница 26: ... Acknowledging Domestic Calls 17 Disable 18 Programming Domestic Telephone Numbers 18 Duress Alarm 11 EEPROM Fault 13 Entry Delay Entry Time 21 Entry Guard Timer 8 9 Event Memory Recall 16 External Equipment 21 Fault Analysis 12 Fault Descriptions 13 AUX Power Supply Fail 13 Communciation Fail 14 Date and Time 13 EEPROM Fault 13 Horn Speaker 13 Low Battery 13 RF Low Battery 13 RF Receiver Fail 13 ...

Страница 27: ...nsor Watch 14 Sealed 21 Sensor Watch 14 22 Silent Alarm 22 Specifications 5 STAY Indicator 6 STAY Mode 1 8 22 Entry Guard Timer 8 STAY Mode 2 8 22 Entry Guard Timer 9 Programming Zones 9 Strobe Test 15 System Disarmed 6 Tamper Alarm 11 Tamper Fail 13 Telco Arm Sequence 14 22 Telco Disarm Sequence 15 22 Telephone Line Fail 13 Test Report 16 Testing Bell Test 15 Horn Speaker Test 15 Strobe Test 15 T...

Страница 28: ... 2008 Bosch Security Systems Inc F01U089456 02 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 USA www boschsecurity com ...

Отзывы: