Unit Configuration
|
7
Heat Pump Controller
8733819577 (2019/02)
Heat Pump Controller
Subject to change without prior notice
UNIT CONFIGURATION
Settings
The Bosch EasyStart app is used to configure available features of the HPC as follows:
Table 2 HPC Settings
Alarm Mode
The HPC has a fault alarm that can be configured
(via the Bosch EasyStart app) as constant or
pulsed. Constant configuration will energize and
latch the alarm output. The pulse alarm setting will
allow the alarm relay to pulse the alarm in sync
with the status LED indicator.
HPC Settings
Default Settings
Freeze Protection Strategy
15°F–26°F
26°F
Cooling CFM per TON
300–450
400 CFM/Ton
Heating CFM per TON
300–450
375 CFM/Ton
Fan Only CFM reduction
50–100%
80%
Dehumidification CFM reduction
15–40%
15%
Heat Recover Package
Enabled or Disabled
Disabled
Heat Recovery Setpoint
110°F–140°F
120°F
Heat Recovery Sample Rate
2–6 Samples/Hr
3 Samples/Hr
Electric Heat Size
None, 5kW, 10kW, 15kW, 20kW
None
Low Loop Water Protection
Enabled or Disabled
Disabled
Low Loop Control Setpoint
20°F–50°F
34°F
Loop Pump Compressor Delay
30–240 seconds
30s
Mode of Compressor Operation
Comfort or Economy
Comfort
Down-Staging
Latched or Unlatched
Unlatched
Number of Lockouts
2–4 Strikes
3 Strikes
Lockout Reset
(Y1) signal or (R)
(Y1)
Units of Temperature
°F or °C
°F
Alarm Type
Constant or Pulse
Pulse
Date
MM/DD/YYYY
Time
HH:MM
High Efficiency Mode
Enable or Disabled
Disabled
Compressor Runtime Reset
Write Only
Model Number
(from the Unit Data Plate)
SM036-1VTC-FRTADC-
CMGXXXXXD7HXXX4XXXXSNA
Serial Number
(from the Unit Data Plate)
1234-567-891011-1213141516
Refer to the “Updating the Firmware and
Configuring Unit Settings” section on page #26
for details on accessing these settings.
NOTICE
: Keep the HRP configuration setting
set to disabled if there is no domestic water
supply available.