Troubleshooting
Greentherm T9900 SE/i – 6 720 813 635 (2019/03)
64
B1 Internal Adjust
▶ Touch symbols
or
until display shows
B1 Internal
Adjust
.
Fig. 62
B1 Internal Adjust - P1 Active
▶ Touch the symbol
to enter
B1 Internal Adjust
.
1)
B1 Internal Adjust
will start automatically.
▶ Wait approximately 60 seconds until a green check mark
appears in the display, which indicates that the
B1 Internal
Adjust
is completed. Do not interfere with the appliance
during this period.
Fig. 63
B1 Internal adjust is completed
L2 Gas Adjust
▶ Touch the symbol
to enter
L2 Gas Adjust
.
L2 Gas Adjust
value is shown (ionization).
▶ Change
L2 Gas Adjust
parameter until
ION
value is
according to table 26.
▶ Increase
L2 Gas Adjust
parameter to increase
ION
value
and vice-versa.
Fig. 64
L2 Gas Adjust - ION value
▶ Touch the symbol
to save value.
▶ Touch the symbol
to return to the main menu.
Minimum power adjust
is completed.
Table 26 L2 ION values
Gas and Air adjustment is complete
.
8.12.3 Restore factory values
To restore factory values for combustion settings,
▶ Proceed with the following steps.
To enter
P1 and P2
menu,
▶ Access to
AU Technical Settings
menu.
▶ Touch symbols
or
to select
CA
menu.
Display shows
CA Combustion Adjust
.
▶ Touch the symbol
to enter
CA
menu.
▶ Touch symbols
or
to select
MA - Manual Adjust
menu.
▶ Touch the symbol
to enter
P1
or
P2
menu.
Reset Parameters P1
After enter
MA - Manual Adjust
,
▶ Access to menu
P1
.
1)
B1 Internal Adjust
will calculate automatically the amount
of air in low fire (P2). This method uses P1 values to start
calculation.
L2 Gas Adjust
1)
1) For information on unit’s configuration (gas type: NG/LPG
and capacity: 160 000BTU/199 000BTU), see rating plate
(
199 000 BTU
160 000 BTU
Natural Gas
ION (L2 Gas Adjust)
125 - 160
100 - 130
LP Gas
ION (L2 Gas Adjust)
150 - 180
100 - 135
672081681
5
-39
.
1V
ION
17
128
L2 Gas
Adjust