Bosch GC 7000 WP Скачать руководство пользователя страница 14

Whilst it is always our intention to fully assist, it is essential to recognise that all information given by the company in response to an enquiry of any nature is provided in good faith and based 

upon the information provided with the enquiry. We recommend that advice should always be checked with your installer or contract partner. Consequently, the company cannot be held 

responsible for any liability relating to the use or repetition of such information or part thereof. In addition, whilst making every reasonable effort to monitor the performance and quality of 

our supply, installation and service network, we do not accept responsibility for the workmanship or operation of any third party company that the company may have promoted either in 

conversation, e-mail, or other communication. Similarly, the views and opinions expressed in communication with individuals within the company may not reflect that of the business as a whole.

 

You can find this, and all issued technical bulletins on the Worcester website at: 

worcester-bosch.co.uk/tb 

or 

worcester-bosch.ie/tb

 

13

 

Worcester, Bosch Group, Cotswold Way, Warndon, Worcester WR4 9SW Technical Services: 0330 123 3366 [email protected]

 

Bosch Flue and Ventilation Quick Reference Guide 2022

 

 

 

 

Open flue terminations

 

 

5U (uncorrected chimney height) calculations for assessing flue height and aggregated groups of flue terminals 

 

 

Where a group of individual flues terminate close to each other and within 5U they must be aggregated, and the 

value used for the flue height calculation.

 

 

Flue termination height above structures (distance X) for appliances up to 333 kW 

(Refer to Figure 15)

 

 

 

For terminals fitted to a pitched roof the end-piece termination (as shown in 

Figure 15

) should be at least 1.5m from the roof 

surface when measured horizontally and at least distance ‘

X

’ above the roof line (See table above for correct ‘

X

’ value 

calculations). 

 

For terminals fitted to a flat roof (where there is no general access) the end-piece termination (Base of the grill or terminal 

position) should be located at least distance ‘

X

’ (See table above) above the roof line at the point where it exits the roof (See 

Figure 14

). 

 

Where the terminal is located within 2.5m of an adjacent structure the terminal should be at least distance ‘

X

’ above the structure 

(See table above for distance ‘

X

’ and reference 

Figure 15

). 

 

 

 

 

 

Terminations for Ridged and flat roof configurations

 

 

Please note: 

Flue diameters specified 170mm or less require a terminal that is designed to minimize the ingress of rain or birds. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reference 

Description 

Unit 

50 

kW 

65 

kW 

85 

kW 

100 

kW 

125 

kW 

145 

kW 

5U (5 x Uncorrected chimney 

height)

 

For determining if low level flue terminations 

must be treated as a group

 

mm 

1221 

1465 

1695 

1869 

2110 

2337 

IGEM Calculation used 

Description 

Unit 

50 

kW 

65 

kW 

85 

kW 

100 

kW 

125 

kW 

145 

kW 

Distance X – (

IGEM-UP-10, Fig. 8) 

(Distance X = 1.5225 x (net heat input kW) + 493.43)

 

Distance for Flue 

terminals located on a 

roof. 

mm 

566 

592 

619 

641 

674 

707 

 

Figure 15

 

Содержание GC 7000 WP

Страница 1: ...GC 7000 WP Flue and Ventilation Quick Reference Guide 2022 ...

Страница 2: ...g boilers only Please note Groups of boilers exceeding 70 kW net are covered by IGEM UP 10 Edition 4 and BS6644 2011 Total rated net input must not exceed 70 kW Natural ventilation for open flued appliances installed within a room BOILER TYPE NET HEAT INPUT VENTILATION ROUTE ROOM 1 ROOM 2 ROOM 3 GC 7000 WP 50 kW 47 5 kW Ventilation for room containing appliance 203 cm N A N A Ventilation through 1...

Страница 3: ...e of 15ºC Open flued gas appliance installed within a plant room SYSTEM TYPE GRILLE LOCATION WITH 600MM CLEARANCE FROM ANY OBSTRUCTION HEATING OR HWS 50 SUMMER USAGE HEATING OR HWS 75 SUMMER USAGE HEATING OR HWS 100 SUMMER USAGE High level free area cm per kW net heat input cm 2 3 4 Low level free area cm per kW net heat input cm 4 5 6 Open flued gas appliance installed within an enclosure natural...

Страница 4: ...eviewsandopinionsexpressedincommunicationwithindividualswithinthecompanymaynotreflectthatofthebusinessasawhole You can find this and all issued technical bulletins on the Worcester website at worcester bosch co uk tb or worcester bosch ie tb 3 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Positioning of ventilation withi...

Страница 5: ...all issued technical bulletins on the Worcester website at worcester bosch co uk tb or worcester bosch ie tb 4 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 An example of ventilation distribution fora plant room that has louvered doors and additional high level ventil...

Страница 6: ...co uk tb or worcester bosch ie tb 5 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 Air supply and ventilation within a commercial installation continued quick referencing guide to meet IGEM UP 10 Edition 4 and BS6644 2011 Mechanical ventilation for appliances without d...

Страница 7: ...o uk tb or worcester bosch ie tb 6 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 Flue termination The information in this section is based on fluing not exceeding 333 kW aggregated for anything over 333 kW please refer to vertical open flue termination See page 11 Ple...

Страница 8: ...300mm above below or either side of an opening door air vent or opening window 10 600mm diagonally to an opening door air vent or opening window 11 300mm to an internal or external corner 12 2 000mm below a Velux window 600mm above or to either side of the Velux window 13 400mm from a pitched roof or in regions with heavy snow fall 500mm 14 500mm clearance to any vertical structure on a roof 600mm...

Страница 9: ...y may have promoted either in conversation e mail orothercommunication Similarly theviewsandopinionsexpressedincommunicationwithindividualswithinthecompanymaynotreflectthatofthebusinessasawhole You can find this and all issued technical bulletins on the Worcester website at worcester bosch co uk tb or worcester bosch ie tb 8 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Se...

Страница 10: ...website at worcester bosch co uk tb or worcester bosch ie tb 9 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 Horizontal flue terminal distances from openings within a wall When multiple horizontal room sealed flues terminate on the same wall a clearance zone will need...

Страница 11: ...Worcester WR4 9SW Technical Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 Plume Management Kit termination clearances The plume terminal outlet must follow the conditions outlined in Figure 9 When directing the plume discharge outlet please refer to the tables below for minimum distance from an opening This is to prevent products of comb...

Страница 12: ... required figures within IGEM UP 10 Edition 4 Figure 11B page 45 distance Y from figure 5 above is used to assess this risk Figure 12 page 46 formula to calculate distance G 19 32 x Net head input kW 647 59 5U the distance for GC 7000 WP appliances can be found on page 12 of this document Section 1 Type C room sealed appliances with net heat exceeding 70kW and not exceeding 333kW low level flue di...

Страница 13: ...either in conversation e mail orothercommunication Similarly theviewsandopinionsexpressedincommunicationwithindividualswithinthecompanymaynotreflectthatofthebusinessasawhole You can find this and all issued technical bulletins on the Worcester website at worcester bosch co uk tb or worcester bosch ie tb 12 Worcester Bosch Group Cotswold Way Warndon Worcester WR4 9SW Technical Services 0330 123 336...

Страница 14: ... group of individual flues terminate close to each other and within 5U they must be aggregated and the value used for the flue height calculation Flue termination height above structures distance X for appliances up to 333 kW Refer to Figure 15 For terminals fitted to a pitched roof the end piece termination as shown in Figure 15 should be at least 1 5m from the roof surface when measured horizont...

Страница 15: ...cal Services 0330 123 3366 technical advice uk bosch com Bosch Flue and Ventilation Quick Reference Guide 2022 Open flue terminations above 333kW net input When a flue configuration is rated over 333 kW net heat input then according to the Clean air act local authorities must be informed to gain approval of the Chimney height This is to ensure that flue discharges do not cause nuisance to others o...

Страница 16: ...85 6 x GC 7000 WP 65kW 385 8 0 858 4 29 1 x GC 7000 WP 85kW 82 0 339 1 69 2 x GC 7000 WP 85kW 164 0 514 2 57 3 x GC 7000 WP 85kW 246 0 655 3 28 4 x GC 7000 WP 85kW 328 0 779 3 89 5 x GC 7000 WP 85kW 410 0 890 4 45 6 x GC 7000 WP 85kW 492 0 993 4 97 1 x GC 7000 WP 100kW 96 5 0 374 1 87 2 x GC 7000 WP 100kW 193 0 567 2 84 3 x GC 7000 WP 100kW 289 5 0 723 3 62 4 x GC 7000 WP 100kW 386 0 859 4 30 5 x ...