56
INSTALLER SETTINGS menu settings (for installers only)
6 720 617 763 (2008/09)
8.2 Configuring the heating system
Installer settings: System configuration
Use this menu if you want to configure the system
automatically or manually, e.g. when commis-
sioning or making changes to the system.
•
Start automatic system configuration
for
starting automatic configuration.
•
Domestic hot water configuration
for config-
uring the domestic hot water system manu-
ally.
•
CH system configuration
for configuring the
heating system manually.
•
DHW circulation pump
: This menu option is
only active if the domestic hot water system
has a domestic hot water circulation pump.
When first commissioning a heating system, pro-
ceed as follows:
B
Start automatic configuration.
B
Check the other menu options under
System
configuration
and, if necessary, adjust to suit
the present system.
For menu structure and adjustment ranges
Æ
page 53.
8.3 Parameters for heating
Installer settings: Heating parameters
Use this menu if you want to set the parameters
for the heating circuit controlled by the FW 100
controller. For example, the heating curves can
be calculated with these parameters.
Installer settings: Heating parameters
•
Heating circuit type
: Use this menu item to
set the heating type:
–
Foot point/End point
: Default settings for
a level heating curve are used according to
the classic foot point/end point method.
–
Underfloor heating
: Default settings for an
uneven heating curve as in an underfloor
heating circuit are used.
–
Radiators
: Default settings for an uneven
heating curve as in a radiator heating cir-
cuit are used.
–
Convectors
: Default settings for an uneven
heating curve as in a convector heating cir-
cuit are used.
For menu structure and adjustment ranges
Æ
page 53.
An example system configuration is
shown in Section 2.6 on page 11.
The heating system’s solar thermal
system must be configured manu-
ally (
Æ
tomatic configuration of the
heating system does not configure
the solar system.
Set the flow temperature control on
the boiler to the maximum required
flow temperature.
Parameters not used in a particular
type of heating are not shown.