en | Technical Data
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
Material
PA6 plastic, Grilon BS V0 (UL94 V‑0)
Color
satin finish, anthracite, RAL 7016
7.3.6
UPS 2416 A Universal Power Supply 24 V/6 A
Input voltage range
100 V AC to 240 V AC
Input frequency
50 Hz to 60 Hz
Input current
max. 1.95 A
Efficiency
> 85 %
Back-up time
>16 ms at 115 V AC
Output voltage
26 V DC to 29 V DC
Maximum output current
6 A
Maximum power
160 W (permanent)
Cooling
Ventilation without ventilator
Safety standards
IEC 60950/EN 60950
Permissible operating temperature
-5 °C to 50 °C
Permissible storage temperature
-20 °C to 60 °C
Housing material and color
Aluminum, anodized, black satin finish
Space required (H x W x D)
approx. 200 x 100 x 40 mm
Weight
approx. 780 g
7.4
Panel Controller and Remote Keypad
7.4.1
MPC
Display element
TFT touch screen, 320 x 240 pixels, 127.5 mm x 170 mm
active area
Operating elements
22 buttons, 1 key switch, 12 LEDs, 1 reboot button
Interfaces
CAN1, CAN2, ETH1, ETH2, USB, RS232
Signal inputs
IN1/IN2
Max. length of CAN cable for
system networking
L
max
= 1000 m, depending on configuration, cable type
and topology
Input voltage
20 V DC to 30 V DC
Maximum current consumption
–
Standby mode: 136 mA at 24 V DC
–
In case of alarm: 226 mA at 24 V DC
Permissible operating temp.
-5 °C to 50 °C
Permissible storage temperature -20 °C to 70 °C
Space required (H x W x D)
190 x 404 x 60 mm
Weight
Approx. 2 kg