Bosch FPA-1000 Series Скачать руководство пользователя страница 13

Analog Addressable Fire Panels

 Release Notes for Version 1.03 | en

13

Bosch Security Systems, Inc.

Release Notes

F.01U.075.638 | 08 | 2012.08

Communication loss counters for Supervised Output Modules

: If there are more than 

100 FLM-325-N4 devices on an SLC, the loss counter values for the FLM-325-N4 devices 
on the SLC diagnostics menu are not always zero.

Indication of remaining time during Walk Test on Web: 

Not available yet.

Forbidden characters for label text on Web page:

 

The following characters must not be used on Web pages: < > & “ ‘ . 
The following characters are not displayed correctly on the panel’s LCD: % \ ~

New SLC devices:

 The following SLC devices are in the literature but not available yet: 

FAP-325-T Analog Multisensor Detector Analog Multisensor Detector

FLM-325-I4-A Contact Monitor 4-inch Class A

FLM-325-I4-AI Contact Monitor 4-inch Class A w/Isolator

FLM-325-2R4-2A Dual Relay Module 2 A

FLM-325-2R4-2AI Dual Relay Module 2 A w/Isolator

FLM-325-2R4-8A Dual Relay Module 8 A

FLM-325-2R4-8AI Dual Relay Module 8 A w/Isolator

Installation and Operation Guide (IOG) Version 3.0:

Page 85: It says, “ If the panel is already silenced, pressing [SILENCE] causes an 
unsilence command in the panel”. This feature was removed and the statement will 
be removed from the IOG accordingly in the next revision.

Silenceable options: The silenceable options for the Mainboard and Option Bus 
relays are not shown on the product MMI, but replaced by [EXT SIGNALING].

Page 133: The Web login screenshot on the page below shows a RESET button. Such 
button is not available on the product Web page.

Page 136: The description about the item "Compare Configuration" does not exactly 
match the software functionality. In fact, it should say, "You can compare either two 
different FPA-1000-UL configuration? files or preview saved/unimplemented 
changes".?

Real-time event printing features including programmable delay

: This feature is 

described in the IOG and Online Help, but is not yet available on MMI and Web page. 

Compare Configuration:

 With the IE Web browser, the “Compare Configuration” page 

cannot be saved as a file. (It works with the Mozilla Firefox browser.)

Web access:

 After having confirmed, the user needs to reconfirm the Web access on the 

panel if no activities have been performed for 25 minutes. Sometimes after confirmation, 
reconfirmation is required before the time out of 25 minutes.

Menu 3.2.4:

 When having selected from menu 3.2.4, sometimes the panel prints the SLC 

diag pages multiple times until the user exits the menu.

8

Release Notes for Version 1.03

8.1

New Features in Version 1.03

No new features

8.2

Issues Fixed in Version 1.03

Off hook time

: When accessing the panel remotely through the phone line the off hook 

time of a dropped call is reduced.
This fixes an issue that the panel didn’t hang off in time after a remote call was dropped.

Powered IN terminals in Class B mode

: This fixes an issue when the CZM which is wired 

in Class B mode provided voltage to the IN terminals when there is an open trouble.

Содержание FPA-1000 Series

Страница 1: ...Analog Addressable Fire Panels FPA 1000 en Release Notes ...

Страница 2: ......

Страница 3: ...ues Fixed in Version 1 13 10 4 3 Known Issues in Version 1 13 10 5 Release Notes for Version 1 12 10 5 1 New Features in Version 1 12 10 5 2 Issues Fixed in Version 1 12 10 5 3 Known Issues in Version 1 12 11 6 Release Notes for Version 1 11 11 6 1 New Features in Version 1 11 11 6 2 Issues Fixed in Version 1 11 11 6 3 Known Issues in Version 1 11 11 7 Release Notes for Version 1 10 11 7 1 New Fea...

Страница 4: ...Systems Inc 10 Release Notes for Version 1 01 15 10 1 New Features in Version 1 01 15 10 2 Issues Fixed in Version 1 01 15 10 3 Known Issues in Version 1 01 15 11 Release Notes for Version 1 00 16 11 1 New Features in Version 1 00 16 11 2 Issues Fixed in Version 1 00 16 11 3 Known Issues with Version 1 00 16 ...

Страница 5: ... act as one panel The standard control panel supports one Signaling Line Circuit SLC for up to 254 detectors and modules or up to 127 analog sounder bases in combination with a suitable detector for a total of 254 addressable device capacity per SLC The control panel is easily expandable with the FPE 1000 SLC Signaling Line Circuit Plug in Module doubling the address points On the front of the pan...

Страница 6: ...imum number of history event records has been increased to 2999 Walk test timer reset In walk test mode every activation from an input point restarts the 25 minute walk test timer Silence at reset At the beginning of system reset the panel silences every silenceable output according to the silence mode audible only or audible visible programmed for the system Sandwich Alarm silence unsilence For s...

Страница 7: ...alls non modem result in a trouble message Currently a work around is to disable remote access Only one group allowed Currently although up to eight panels can be networked they must all be in the same group Panels will be assignable to different groups in the next release but in the meantime prevent access to functions silence reset etc by untrained unauthorized personnel Multi building interconn...

Страница 8: ...g Addressable Fire Panels F 01U 075 638 08 2012 08 Release Notes Bosch Security Systems Inc Shorted Option Bus Terminals issue If option bus ternimal B gnd and terminal G tx are shorted a transistor may break requiring replacement of the panel ...

Страница 9: ...n corrected SLC intermittent open issue If the SLC loop is intermittently open and closed troubles will be reported for the wrong devices 3 3 Known Issues in Version 1 14 incorrect temporal pattern FAA 325 B6S may produce an incorrect temporal pattern for the first cycle Reduced system initialization speed On large systems with many FMR 1000 annunciators tupdating annunciator status and initializi...

Страница 10: ...pairs Set the maximum co dependent zones of one zone to four different zones Hexadecimal reporting account number Regardless of which reporting format menu web browser is used the panel can be programmed with hexadecimal reporting account numbers Point restoral upon reset Upon panel reset the panel restores all existing alarms including fire waterflow alarms gas alarms and supervisory alarms This ...

Страница 11: ...isable remote access New SLC devices The FAP 325 T Analog Multisensor Detector is in the literature as SLC device but is not available yet 6 Release Notes for Version 1 11 6 1 New Features in Version 1 11 No new features introduced in this version 6 2 Issues Fixed in Version 1 11 Phone line 1 troubles In out calls on phone line 1 no longer initiate line disconnect or dialer answering trouble signa...

Страница 12: ...panel MMI and Web pages into the languages Portuguese and Spanish New features on the Web pages Off line configuration tool Online help Allows for comparing and printing the programmed configuration Allows timezone offset for time synchronization with PC 7 2 Issues Fixed in Version 1 10 Gas alarm Gas alarms are reported to the central station receiver as event type Fire Supervisory if Modem IIIa2 ...

Страница 13: ...he product MMI but replaced by EXT SIGNALING Page 133 The Web login screenshot on the page below shows a RESET button Such button is not available on the product Web page Page 136 The description about the item Compare Configuration does not exactly match the software functionality In fact it should say You can compare either two different FPA 1000 UL configuration files or preview saved unimpleme...

Страница 14: ...ass A loop and pressing reset 28 day Auto Test Interval This fixes an issue where the next auto test report is sent approximately 1 hour later than expected when setting the auto test interval to 28 days FAA 325 B6S menu for the detector The menu item Edit Sounder Base for detectors is removed The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programm...

Страница 15: ...mming is disabled 25 minutes later FAA 325 B6S menu for the detector The menu Edit Sounder Base for detectors is not working The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programming SLC devices 10 Release Notes for Version 1 01 10 1 New Features in Version 1 01 With Version 1 01 the panel s display supports Spanish and Portuguese 10 2 Issues Fixe...

Страница 16: ...ctor The menu Edit Sounder Base for detectors is not working The menu was intended as a shortcut from Add A Device or Edit A Device to Edit Sounder Base when programming SLC devices 11 Release Notes for Version 1 00 11 1 New Features in Version 1 00 New product release 11 2 Issues Fixed in Version 1 00 New product release 11 3 Known Issues with Version 1 00 None ...

Страница 17: ......

Страница 18: ......

Страница 19: ......

Страница 20: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity us Bosch Security Systems Inc 2012 ...

Отзывы: