Power Up
4
Bosch Security Systems, Inc. | 8/06 | F01U002307C
3.0 Power
Up
The power supplied to the FMR-DACT-KEYPAD
from the DACT is 12 VDC with a maximum draw
of 100 mA.
4.0 Installing the Instruction
Label and Slide
1.
Place the instruction label (Item 2 in Figure 3) on
the pullout slide (Item 3 in Figure 3), positioning
it as close to the pull tab as possible.
2.
Install the slide so you can pull from the left or
right from the back of the base.
Figure 3:
Installing the Instruction Label and
Slide
1
2
3
2
1 - Back of the FMR-DACT-KEYPAD
2 - Label
3 - Slide
Note: The label on the slide has writing on the
reverse side.
5.0 Setting the Address
The FMR-DACT-KEYPAD must have an address
set within its address pins.
Select the address, 1 to 15, by placing the shorting
jumpers over the address pins as shown in Figure 4.
Figure 4:
Setting the Address
1 | 2 | 4 | 8
Address 9
1 | 2 | 4 | 8
Address 8
Address 7
1 | 2 | 4 | 8
Address 4
1 | 2 | 4 | 8
1 | 2 | 4 | 8
Address 6
1 | 2 | 4 | 8
Address 5
Address 1
1 | 2 | 4 | 8
1 | 2 | 4 | 8
Address 2
1 | 2 | 4 | 8
Address 3
1 | 2 | 4 | 8
Address 12
1 | 2 | 4 | 8
Address 11
Address 10
1 | 2 | 4 | 8
Address 13
1 | 2 | 4 | 8
1 | 2 | 4 | 8
Address 14
1 | 2 | 4 | 8
Address 15