FMR-7033 

|

 

Installation Instructions | 4.0 

Wiring the FMR-7033 

 

 

Bosch Security Systems, Inc. | 9/08 | F01U010583-01

Figure 2: 

Location of the FMR-7033 Base 
Mounting Holes 

Inside of FMR-7033 Keypad

DO NOT USE THIS PIN!!

Back of FMR-7033 Keypad

1

2

3

4

5

6

7

1- Address 

Pins 

2- Terminal 

Strip 

3-   Double Gang Mounting Slots 

4-   Terminal Strip Opening 

DO NOT USE AS A WIRE ENTRANCE. 

5-   Sounder Opening 

6-   Wire Entrance 

7-   Single Gang Mounting Slots 

 

 

4.0  Wiring the FMR-7033 

 

Ensure that power is removed from all 
wiring before routing. Keypad wiring cannot 
be shared with multiplex, option bus, 
telephone or siren wiring. 

 

 

 

Up to three keypads can be used on any 
single 1,000 ft (305 m) run of #18 AWG 
(1.2 mm) wire. Refer to the FACP’s 
installation guide for more detailed 
instructions. 

 

Table 1: 

FMR-7033 Wiring Guidelines 

 

 

Wiring Specifications 

Value 

Wire Gauge 

#18 AWG (1.2 mm) 

Wire Type 

Non-shielded; 4-wire 

Maximum number of keypad 
allowed per system 

Distance allowed between FACP 
and Keypad 

2000 ft (610 m) 

Maximum distance of keypad 
wiring and bus 

4000 ft (1219 m) 

To wire the FMR-7033 Fire System Controller: 

1. 

Route the wiring from the FACP to the keypads. 
Refer to the FACP’s installation guide for details. 

2. 

Bring the base wiring through the wire entrance 
in the keypad’s base. Refer to 

Item 6

 in

 Figure

 2 

for wire entrance location. 

3. 

Connect the wiring to the FMR-7033’s terminal 
strip. Refer to 

Figure 3

4. 

Place the keypad onto the base. 

5. 

While feeding the excess wiring out of the rear 
of the base, press the cover straight in until it 
latches. 

Figure 3: 

Wiring the FMR-7033’s Terminal Strip 

R

+12V

B

Com

G

Data In

Y

Data Out

1

2

1 -  FMR-7033 Terminal Strip 

2 -  FPD-7024 Option Bus 

5.0  Powering the FMR-7033 

The power supplied to the FMR-7033 from the R and 
B terminals on the FACP is 12 VDC with a maximum 
draw of 100 mA per FMR-7033 keypad. This power is 
supplied from a 24 VDC battery when AC power fails. 

Содержание FMR-7033

Страница 1: ...FMR 7033 EN Installation Instructions Addressable Fire System Controller ...

Страница 2: ... Label and Slide 5 7 0 Setting the FMR 7033 s Address 5 8 0 Programming the FMR 7033 5 9 0 Troubleshooting the FMR 7033 5 10 0 Specifications 6 11 0 Operating the FMR 7033 7 Figures Figure 1 Removing the FMR 7033 Cover 3 Figure 2 Location of the FMR 7033 Base Mounting Holes 4 Figure 3 Wiring the FMR 7033 s Terminal Strip 4 Figure 4 Installing the Instruction Label and Slide 5 Figure 5 FMR 7033 Key...

Страница 3: ...er functions It operates identically to the built in user interface on the FACP Up to four FMR 7033 controllers might be connected to an FPD 7024 The FMR 7033 can be surface mounted mounted to a single or double gang box or to a four inch square box 3 0 Device Mounting The FMR 7033 should be mounted no higher than shoulder height of the shortest person using the system Remove the keypad s cover by...

Страница 4: ...1 2 mm Wire Type Non shielded 4 wire Maximum number of keypad allowed per system 4 Distance allowed between FACP and Keypad 2000 ft 610 m Maximum distance of keypad wiring and bus 4000 ft 1219 m To wire the FMR 7033 Fire System Controller 1 Route the wiring from the FACP to the keypads Refer to the FACP s installation guide for details 2 Bring the base wiring through the wire entrance in the keypa...

Страница 5: ... must not conflict with the addresses of other keypads or other option bus devices Each keypad address can support only one device All keypads must also be programmed at the FACP Select the keypad address 1 15 by placing the shorting jumpers over the address pins as shown in Figure 5 Figure 5 FMR 7033 Keypad Addresses 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 1 2 4 8 Address 1 Address 4 Address 7 Address 10...

Страница 6: ...FACP does not respond to keypad input The keypad s address was not set Three beep error tone at all keypads Invalid key input 10 0 Specifications Table 3 FMR 7033 Specifications Nominal Supply Voltage 12 VDC from Option Bus Standby Current 100 mA 75 mA for battery calculation Alarm Current 100 mA 75 mA for battery calculation Environment Use Indoor Dry Operating Temperature 32 F to 120 F 0 C to 49...

Страница 7: ...ets the bell or sirens for an alarm or trouble condition only if the system is so configured 1 The two line character display can show all messages normally displayed on an FPD 7024 or an FMR 7036 keypad 2 The red Alarm LED lights whenever the system registers an alarm and was not reset 3 The yellow Silenced LED lights when the user manually silences an alarm or trouble condition It turns off when...

Страница 8: ... 2008 Bosch Security Systems Inc F01U010583 01 Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 9199 800 289 0096 www boschsecurity com ...

Отзывы: