Product Description FLM−420−RHV−S / FLM−420−RHV−D
19 / 36
ST
−
FIR / PRM1 / zab
610
−
F.01U.003.282 / A2
Functional Description
The interfaces have two change−over contact relays (Form C) for the controlled activation of external ele-
ments (e.g. ·smoke flaps, extinguishing systems, or fans) at LSN fire panels.
Wiring
Description
Connection
NC / COM / NO
Relay 1
NC / COM / NO
Relay 2
b1+ / a− / b2+
LSN
FB2 +
Relay 2, Fe
FB1/FB2 −
Relay 1 und 2, Feedback −
FB1 +
Relais 1, Fe
Address Setting
Mode/
X
XX
X
X
X
XX
X
FAN
RLHV
CL 0 0
n
0 0 0
1...254
FPA−
5000
BZ 500 LSN
UEZ 2000 LSN
UGM 2020
n
n
255...299
n
_
_
_
_
Technical Specification
Operating/displa y elements
2 LEDs (1x red, 1x green)
Function selection
FAN or RLHV function via rotary switch
Address setting 0 0 0
Loop/stub in LSNi mode with automatic addressing
(T−tap system not possible)
Address setting 1...254
Loop/stub/T−tap system in LSNi mode with manual
addressing
Address setting CL 0 0
Loop/stub in classicˆ LSN mode
Input voltage (min − max)
15 V DC − 33 V DC
Maximum current consumption
15,5 mA
Max. relay contact rating
10 A bei 120 V AC / 230 V AC / 24 V DC,
6 A bei 30 V DC
Fuses
F1 = 10 A, F2 = 10 A
Feedback current
max. 1 mA (EOL resistance R=3.9 k
)
Feedback voltage
max. 30 V DC
Safety class as per IEC 60950
II
Protection class as per IEC 60529
FLM−420−RHV−S: IP 54 / FLM−420−RHV−D: IP 30
Permitted operating/storage temperature
−20
_
C . . . 50
_
C / −25
_
C . . . 85
_
C
Permitted relative humidity
< 96%
Material interface module housing
Material surface−mount housing
PPO (Noryl)
ABS + PC−Blend
INFO
It is not permitted
−
to operate the relay with different voltages (high voltage and low voltage)
−
to place two different AC line voltage phases on the relay contacts
−
to use
different adressing modes together.
DANGER
RISK OF ELECTRIC SHOCK !
Danger of life with contact of live parts and wires.
"
Disconnect power before connecting equipment!
"
Before connecting the power supply make sure that the contact protection is fixed and
locked in place (see page 5 resp. 7).
Содержание FLM-420-RHV-D
Страница 2: ...FLM 420 RHV S 2 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 2 1 2 FLM 420 RHV S FLM 420 RHV D 7 5 ...
Страница 4: ...FLM 420 RHV S 4 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 4 5 10 35 36 INFO 126 4 96 126 4 96 Ø21 0 83 ...
Страница 5: ...FLM 420 RHV S 5 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 6 7 8 9 1 2 CAUTION ...
Страница 6: ...FLM 420 RHV D 6 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 4 1 3 2 1 3 2 ...
Страница 7: ...FLM 420 RHV D 7 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 10 35 36 INFO 1 2 5 CAUTION ...
Страница 8: ...FLM 420 RHV D 8 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 4 3 2 1 3 2 1 ...
Страница 9: ...FLM 420 RHV D S 9 36 ST FIR PRM1 zab 610 F 01U 003 282 A2 4x 1 2 ...