If temperature drops below or remains at the 
freeze limit trip for 30 seconds, the controller 
will shut the compressor down and enter into 
a soft lockout condition. Both the status LED 
and  the  Alarm  contact  will  be  active.  The 
LED  will  flash  (five  (5)  times)  the  code 
associated with this alarm condition. 

Once the UPM detects a brownout condition 
its  fault  LED  will  flash  seven  (7)  times  as 
error code indication. 

Condensation overflow 

 

The  UPM  controller  continuously  monitors 
the  drain  pan  for  high  condensate  water 
level,  and  to  do  so  it  utilizes  a  sensor  and 
identifies  an  alarm  condition  when  the 
sensor’s impedance drops below 230KΩ +/- 
15  %.  (ONLY  when  condensate  sensor 
option is present) Once the UPM senses this 
resistance value it enters into a hard lockout 
and  reports  the  correspondent  code  via  its 
status LED (6 flashes). 

 

 

 

Figure 4 - Freeze sensor location 

 

To exit the hard lockout water has to return 
to its normal level and UPM has to be reset 
by  removing  the  power  from the  Y  terminal 
(R if set on the DIP switch) the compressors 
will  be  turned  on  after  anti  short  cycle 
expires. 

 
 
 

Brownout protection 

The  UPM  controller  will  constantly  monitor 
the  power  supply,  if  the  nominal  voltage 
drops  below  25%  of  its  value.    (18  VAC 
approximately),  the  unit  will  enter  brownout 
protection  mode.  The  compressor  CC 
outputs will be de-energized and the unit will 
enter the soft lockout mode. 

Sequence of Operation

   

 

The  UPM  sequence  of  operation  illustrated 
in the flow chart applies for both refrigerant 
circuits.  The  second  compressor  is 
energized  10  seconds  after  the  first  if  both 
Y1  and  Y2  signals  are  applied  at  the 
simultaneously. 

 
The  controller  will  not  monitor  the  power 
supply  during  the  first  500  milliseconds  of 
compressor start up to avoid noise and false 
alarms. 

 

Содержание FHP UPM II

Страница 1: ...I O ZONE 560 583 UPM II INSTALLATION AND OPERATION MANUAL 1 ...

Страница 2: ...rect part number TABLE OF CONTENTS Specifications 3 Unit Protection Module UPM 4 Power Random Start Up 5 Anti short cycle delay 5 Y Call 5 High and Low pressure protection 5 Ground 7 DIP Switch Settings 7 Selectable Alarm Mode 7 Freeze protection 7 Brownout protection 8 Condensation overflow 8 Sequence of Operation 8 UPM Sequence of Operation SOO Flow Chart 9 2 ...

Страница 3: ...y contact Normally Open NO Inputs Four 9 inputs Dedicated inputs for 2 High Pressure Switches HPC 2 Low Pressure Switches LPC 2 Freeze Sensors FREEZE 10 K 77F Thermistor 1 Condensate Overflow Sensor CON 230 K 15 2 Compressor Call Y Signals Status Indication Visual LED status of power and alarms status indication Protection Surge and transient protection circuitry Weight 0 25 lbs 0 12 Kg Overall Di...

Страница 4: ...sors of each refrigerant circuit this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed Figure 1 UPM Two Stage Alarm output is Normally Open NO dry contact If 24 VAC output is needed R must be wired to the ALR COM terminal 24VAC will be available on the ALR OUT te...

Страница 5: ...ved The anti short cycle delay is 300sec delay on break during normal operation Y Call The UPM will energize the compressor s output CC in an event of a Y call from a thermostat or controller after the random start up and or the anti short cycle delays have elapsed Y input terminal must be energized with a 24 VAC signal High and Low pressure protection The UPM monitors the state of the High and Lo...

Страница 6: ...or The user can select either two or four times by changing switch four 4 on the DIP switch SW1 shown on table 3 on the UPM board Low pressure protection If the LP1 or LP2 switches are open upon a Y1 or Y2 call Could be Y1 or Y2 or both the UPM will not energize the CC1 or CC2 outputs and therefore the correspondent compressor will remain off the fault LED will flash two 2 times for the LP1 and 4 ...

Страница 7: ...associated functionality Selectable Alarm Mode The UPM controller can be configured to have either a constant signal or a pulse If constant CONT is selected the UPM will provide a closed contact until the alarm is cleared If pulsed PULSE is selected the UPM will sequence the alarm contact with the fault LED flashes Freeze protection The default setting for the freeze limit trip is 30 F however thi...

Страница 8: ...espondent code via its status LED 6 flashes Figure 4 Freeze sensor location To exit the hard lockout water has to return to its normal level and UPM has to be reset by removing the power from the Y terminal R if set on the DIP switch the compressors will be turned on after anti short cycle expires Brownout protection The UPM controller will constantly monitor the power supply if the nominal voltag...

Страница 9: ...UPM Sequence of Operation SOO Flow Chart 9 ...

Страница 10: ...10 601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www fhp mfg com 6 720 220 322 REV 6 11 ...

Отзывы: