High pressure protection 

 
If the HP1 or HP2 switches are open upon a 
Y1 or Y2 call the UPM will not energize the 
respective  CC1  or  CC2  outputs  and 
therefore the correspondent compressor will 
remain  off,  the  fault  LED  will  flash  one  (1) 
time  for  the  HP1  and  3  times  for  HP2  and 
the alarm contact will remain off. 
 
If  a  compressor  is  running  in  normal  mode 
on a Y call (Could be Y1 or Y2 or both) and 
the  high  pressure  switch  opens,  the  UPM 
will  shut  down  the  compressor  output  and 
will keep it off until the switch closes and the 
anti  short  cycle  has  expired.  The  controller 
will  keep  track  of  the  number  of  times  the 
switch  opens,  if  within  one  (1)  hour  period 
the  switch  opens  the  number  of  times  set  
via the DIP switch the controller will shut the 
compressor  down  and  perform  a  hard 
lockout  condition  under  this  condition  the 
alarm contact will be energized. 
 
The  UPM  allows  the  user  to  configure  the 
counts  that  the  HP  will  be  allowed  to  open 
within one hour before the UPM performs a 
hard  lockout  on  the  compressor.  The  user 
can  select  either  two  or  four  times  by 
changing  switch  four  (4)  on  the  DIP  switch 
SW1 (shown on table 3) on the UPM board. 

 

 

Low pressure protection 
 

If the LP1 or LP2 switches are open upon a 
Y1  or  Y2  call  (Could  be  Y1  or  Y2  or  both) 
the  UPM  will  not  energize  the  CC1  or  CC2 
outputs  and  therefore  the  correspondent 
compressor will remain off, the fault LED will 
flash two (2) times for the LP1 and 4 times 
for the LP2 and the alarm contact will remain 
off. 
 
If the compressor is running in normal mode 
on a Y call (Could be Y1 or Y2 or both) and 
the low pressure switch opens, the UPM will 
keep  the  compressor  running  for  two  (2) 
minutes  if  the  condition  remains  after  this 
period of time the compressor will shut down 
and  the  UPM  will  start  a  soft  lockout.  The 
UPM will flash two (2) times for the LP1, four 
(4) times for the LP2 and the alarm contact 
will remain off.  
 
If the switches close, the UPM will start the 
compressor  after  the  anti  short  cycle  has 
expired  UPM  will  energize  the  compressor 
output. 
 
 
 
 

 

IMPORTANT: 
To exit the hard lockout the controller must be reset 
from the Y or R terminal by removing the power from 
the selected terminal. The user can choose which will 
be the reset point via the DIP switch SW1.

 

Содержание FHP UPM II

Страница 1: ...I O ZONE 560 583 UPM II INSTALLATION AND OPERATION MANUAL 1 ...

Страница 2: ...rect part number TABLE OF CONTENTS Specifications 3 Unit Protection Module UPM 4 Power Random Start Up 5 Anti short cycle delay 5 Y Call 5 High and Low pressure protection 5 Ground 7 DIP Switch Settings 7 Selectable Alarm Mode 7 Freeze protection 7 Brownout protection 8 Condensation overflow 8 Sequence of Operation 8 UPM Sequence of Operation SOO Flow Chart 9 2 ...

Страница 3: ...y contact Normally Open NO Inputs Four 9 inputs Dedicated inputs for 2 High Pressure Switches HPC 2 Low Pressure Switches LPC 2 Freeze Sensors FREEZE 10 K 77F Thermistor 1 Condensate Overflow Sensor CON 230 K 15 2 Compressor Call Y Signals Status Indication Visual LED status of power and alarms status indication Protection Surge and transient protection circuitry Weight 0 25 lbs 0 12 Kg Overall Di...

Страница 4: ...sors of each refrigerant circuit this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed Figure 1 UPM Two Stage Alarm output is Normally Open NO dry contact If 24 VAC output is needed R must be wired to the ALR COM terminal 24VAC will be available on the ALR OUT te...

Страница 5: ...ved The anti short cycle delay is 300sec delay on break during normal operation Y Call The UPM will energize the compressor s output CC in an event of a Y call from a thermostat or controller after the random start up and or the anti short cycle delays have elapsed Y input terminal must be energized with a 24 VAC signal High and Low pressure protection The UPM monitors the state of the High and Lo...

Страница 6: ...or The user can select either two or four times by changing switch four 4 on the DIP switch SW1 shown on table 3 on the UPM board Low pressure protection If the LP1 or LP2 switches are open upon a Y1 or Y2 call Could be Y1 or Y2 or both the UPM will not energize the CC1 or CC2 outputs and therefore the correspondent compressor will remain off the fault LED will flash two 2 times for the LP1 and 4 ...

Страница 7: ...associated functionality Selectable Alarm Mode The UPM controller can be configured to have either a constant signal or a pulse If constant CONT is selected the UPM will provide a closed contact until the alarm is cleared If pulsed PULSE is selected the UPM will sequence the alarm contact with the fault LED flashes Freeze protection The default setting for the freeze limit trip is 30 F however thi...

Страница 8: ...espondent code via its status LED 6 flashes Figure 4 Freeze sensor location To exit the hard lockout water has to return to its normal level and UPM has to be reset by removing the power from the Y terminal R if set on the DIP switch the compressors will be turned on after anti short cycle expires Brownout protection The UPM controller will constantly monitor the power supply if the nominal voltag...

Страница 9: ...UPM Sequence of Operation SOO Flow Chart 9 ...

Страница 10: ...10 601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www fhp mfg com 6 720 220 322 REV 6 11 ...

Отзывы: