82
en | Commissioning
FCS-320-TM Aspirating Smoke Detector
F.01U.130.928 | 1.0 | 2009.11
Operation Guide
Bosch Sicherheitssysteme GmbH
14. Open the "Settings" screen in the diagnostic software and enter the following settings for
the functional test:
15. You can use the diagnosis program to track the airflow values and the fault messages
during the functional test.
Information for installing the diagnostic software can be found in
Section 6.1 Preparation,
page 76
.
6.7.2
Conducting the Functional Test
1.
Close all the test pipe’s aspiration borings with some duct tape.
After a short run-up time, the negative pressure produced by the FCS-320-TM must be
80 Pa. This step can be omitted if a limited functional test is carried out without a digital
precision pressure gauge.
NOTICE!
On completion of the functional test, the original settings must be restored. You should
therefore record this data (e.g. using the log for the device as a saved text file).