background image

5

 

FCP-500

 

Series

 

Mounting

 

the

 

Base

 

(FCA-500

 

and

 

FCA-500-E)

 

1.

  

Insert

 

the

 

base

 

in

 

the

 

back

 

box

 

so

 

that

 

it

 

fits

 

over

 

the

 

four

 

screws.

 

2.

  

Turn

 

the

 

base

 

clockwise

 

until

 

it

 

stops

 

to

 

lock

 

it

 

in

 

place.

 

3.

  

Repeat

 

steps

 

1

 

and

 

2

 

if

 

you

 

install

 

multiple

 

detectors

 

in

 

a

 

line.

 

4.

  

Slightly

 

turn

 

each

 

base

 

until

 

the

 

mark

 

on

 

the

 

base

 

aligns

 

with

 

the

 

other

 

detectors’

 

marks

 

(see

 

Fig.

 

8.).

 

5.

  

Tighten

 

the

 

screws

 

with

 

the

 

supplied

 

wrench.

 

Inserting

 

the

 

Detector

 

Head

 

1.

  

Remove

 

the

 

protective

 

film

 

from

 

the

 

detector

 

head.

 

2.

  

Snap

 

the

 

trim

 

ring

 

into

 

place

 

on

 

the

 

base.

 

3.

  

Place

 

the

 

detector

 

head

 

in

 

the

 

base

 

and

 

turn

 

it

 

until

 

the

 

detector

 

head

 

drops

 

into

 

the

 

alignment

 

grooves.

 

4.

  

Push

 

the

 

center

 

of

 

the

 

detector

 

until

 

it

 

locks

 

into

 

place.

 

It

 

clicks

 

and

 

springs

 

up.

 

Start-up

 

1.

  

Check

 

the

 

wiring

 

from

 

the

 

control

 

panel

 

to

 

the

 

last

 

head

 

on

 

the

 

run

 

for

 

proper

 

polarity

 

and

 

continuity.

 

2.

  

Make

 

sure

 

each

 

run

 

terminates

 

with

 

an

 

EOL

 

resistor

 

as

 

specified

 

by

 

the

 

control

 

panel

 

manufacturer.

 

3.

  

Apply

 

power

 

to

 

the

 

system.

 

Check

 

for

 

alarm

 

and

 

troubles.

 

4.

  

If

 

single

 

detectors

 

alarmed

 

or

 

went

 

in

 

trouble,

 

check

 

if

 

there

 

is

 

a

 

free

 

space

 

of

 

at

 

least

 

19

 

in.

 

(50

 

cm)

 

around

 

these

 

detectors.

 

If

 

the

 

problem

 

persists,

 

replace

 

these

 

detectors

 

or

 

swap

 

them

 

with

 

known

 

good

 

units.

 

If

 

also

 

the

 

good

 

units

 

alarm

 

or

 

go

 

in

 

trouble,

 

the

 

sensitivity

 

may

 

have

 

been

 

affected

 

by

 

the

 

surrounding

 

environment.

 

Recheck

 

if

 

there

 

are

 

any

 

obstructions

 

around

 

the

 

detector

 

which

 

may

 

reflect

 

the

 

light

 

emitted

 

by

 

the

 

detector.

 

5.

  

Activate

 

the

 

dry

 

reed

 

contact

 

of

 

each

 

detector

 

for

 

10

 

sec

 

with

 

a

 

magnet

 

until

 

the

 

detector

 

alarms

 

(see

 

Section

 

5.,

 

Dry

 

Reed

 

Contact

 

and

 

Section

 

6.,

 

Electronical

 

Function

 

Test

 

).

 

Then

 

reset

 

the

 

detector

 

by

 

removing

 

the

 

power

 

for

 

at

 

least

 

2

 

seconds.

 

After

 

the

 

reset,

 

the

 

detector

 

will

 

calibrate

 

itself

 

to

 

the

 

surrounding

 

environment..

 

Make

 

sure

 

that

 

no

 

objects

 

or

 

obstructions

 

(like

 

the

 

test

 

tool

 

SOLO330

 

itself)

 

are

 

in

 

front

 

of

 

the

 

detector

 

during

 

calibration

 

for

 

15

 

sec.

 

Alignment

 

mark

 

Fig.

 

8.

 

i

 

After

 

installation

 

each

 

detector

 

must

 

be

 

calibrated.

 

If

 

there

 

are

 

any

 

obstruction

 

in

 

front

 

of

 

the

 

detector

 

after

 

the

 

reset

 

during

 

its

 

calibration

 

(Electronic

 

Function

 

Test,

 

Section

 

6.),

 

the

 

sensitivity

 

of

 

the

 

detector

 

may

 

be

 

affected.

 

6.

 

Perform

 

the

 

sensitivity

 

test

 

described

 

in

 

Section

 

7.

 

at

 

every

 

detector.

 

Bosch

 

Security

 

Systems

  

BDL-F01U000626

 

|

 

A7

 

|

 

2007.07

 

                 Available from A1 Security Cameras 

    www.a1securitycameras.com email: [email protected]

Содержание FCP-500

Страница 1: ...500 Series Photoelectric Detectors FCP 500 FCP 500 P FCP 500 C FCP 500 C P en Installation Guide Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Страница 2: ...Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Страница 3: ...tors 4 998 151 301 FAA 500 TR W Trim Ring White 4 998 151 295 FAA 500 TR P Trim Ring Transparent with Color Inserts 4 998 151 296 Table 3 Options optional Type Description Material No DRA 5 Remote LED Annunciator FAA 500 TTL Test Adapter with Magnet F 01U 508 725 FAA 500 RTL Removal Tool F 01U 508 720 Table 4 Technical Data Operating Voltage 9 7 V DC to 30 V DC Current Consumption Standby Alarm Tr...

Страница 4: ...mpliance with NFPA 72 In low air flow applications with smooth ceilings space sensors with a maximum distance of 30 ft For specific information regarding sensor spacing placement and special application refer to NFPA 72 D Not suitable for outdoor use D Do not install in areas where the detector is pointed at direct or indirect sunlight D Do not mount detector in a cone of light from a lamp D Maint...

Страница 5: ...r openings in the detector head are clearly exposed Ceiling Mount Back Box FAA 500 BB UL D For installation refer to the FAA 500 BB UL Installation Guide P N 601 F 01U 003 008 Wiring the Base FCA 500 and FCA 500 E i In applications which require UL listed units the power of all connections detector power trouble and alarm relay must be taken from power limited supplies when the cable is carried th...

Страница 6: ...anel yellow Multiple Detector Wring to Power Supply FCA 500 black red FCA 500 to Control green Panel yellow blue yellow white white white Fig 6 black red FCA 500 E DRA 5 red white green blue white yellow Fig 7 BDL F01U000626 A7 2007 07 Bosch Security Systems Table 5 Wiring Connections Inner Ring for Conventional Connection Alar l Alarm m r re ela ay y normally open Shielding Indicator output Volta...

Страница 7: ...t least 19 in 50 cm around these detectors If the problem persists replace these detectors or swap them with known good units If also the good units alarm or go in trouble the sensitivity may have been affected by the surrounding environment Recheck if there are any obstructions around the detector which may reflect the light emitted by the detector 5 Activate the dry reed contact of each detector...

Страница 8: ... s performance X X 5 Perform Electronic Functional Test see Section 6 X X 6 Perform Sensitivity Test see Section 7 X X 7 Test the optical sensor see Section 8 X X 8 Test the optical sensor and the CO sensor see Section 9 X Table 7 LED Operation Status LED Normal green flashes every 8 sec Alarm red steady Trouble green double flash every 8 to12 sec Test mode green flashes once every second 5 Dry Re...

Страница 9: ...r the detector might come loose 4 By covering the scattered light areas both optical sensors are triggered simultaneously no smoke aerosol is required 5 This can take up to 20 sec An alarm activates and the red LED lights If the panel is in test mode the alarm resets automatically 9 CO and Smoke Test for the FCP 500 C FCP 500 C P i The CO sensor has not been evaluated to the requirements of UL 207...

Страница 10: ...Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 www boschsecurity us Customer Service 800 289 0096 Technical Support 888 886 6189 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com ...

Отзывы: