5
FCP-500
Series
Mounting
the
Base
(FCA-500
and
FCA-500-E)
1.
Insert
the
base
in
the
back
box
so
that
it
fits
over
the
four
screws.
2.
Turn
the
base
clockwise
until
it
stops
to
lock
it
in
place.
3.
Repeat
steps
1
and
2
if
you
install
multiple
detectors
in
a
line.
4.
Slightly
turn
each
base
until
the
mark
on
the
base
aligns
with
the
other
detectors’
marks
(see
Fig.
8.).
5.
Tighten
the
screws
with
the
supplied
wrench.
Inserting
the
Detector
Head
1.
Remove
the
protective
film
from
the
detector
head.
2.
Snap
the
trim
ring
into
place
on
the
base.
3.
Place
the
detector
head
in
the
base
and
turn
it
until
the
detector
head
drops
into
the
alignment
grooves.
4.
Push
the
center
of
the
detector
until
it
locks
into
place.
It
clicks
and
springs
up.
Start-up
1.
Check
the
wiring
from
the
control
panel
to
the
last
head
on
the
run
for
proper
polarity
and
continuity.
2.
Make
sure
each
run
terminates
with
an
EOL
resistor
as
specified
by
the
control
panel
manufacturer.
3.
Apply
power
to
the
system.
Check
for
alarm
and
troubles.
4.
If
single
detectors
alarmed
or
went
in
trouble,
check
if
there
is
a
free
space
of
at
least
19
in.
(50
cm)
around
these
detectors.
If
the
problem
persists,
replace
these
detectors
or
swap
them
with
known
good
units.
If
also
the
good
units
alarm
or
go
in
trouble,
the
sensitivity
may
have
been
affected
by
the
surrounding
environment.
Recheck
if
there
are
any
obstructions
around
the
detector
which
may
reflect
the
light
emitted
by
the
detector.
5.
Activate
the
dry
reed
contact
of
each
detector
for
10
sec
with
a
magnet
until
the
detector
alarms
(see
Section
5.,
Dry
Reed
Contact
and
Section
6.,
Electronical
Function
Test
).
Then
reset
the
detector
by
removing
the
power
for
at
least
2
seconds.
After
the
reset,
the
detector
will
calibrate
itself
to
the
surrounding
environment..
Make
sure
that
no
objects
or
obstructions
(like
the
test
tool
SOLO330
itself)
are
in
front
of
the
detector
during
calibration
for
15
sec.
Alignment
mark
Fig.
8.
i
After
installation
each
detector
must
be
calibrated.
If
there
are
any
obstruction
in
front
of
the
detector
after
the
reset
during
its
calibration
(Electronic
Function
Test,
Section
6.),
the
sensitivity
of
the
detector
may
be
affected.
6.
Perform
the
sensitivity
test
described
in
Section
7.
at
every
detector.