en | Maintenance and Service
Conventional Automatic Detectors
F.01U.002.707 | 8.0 | 2011.10
Operation Guide
Bosch Sicherheitssysteme GmbH
7.3
Test Procedure for Detectors without C-Sensor
1.
Position the Smoke Detector Tester on the detector.
2.
Spray aerosol (1 to 2 seconds).
Do not remove the test device from the detector; the O sensor triggers only approx.
30 seconds after the application of the test aerosol.
3.
Reset detector.
This switches the detector to revision mode.
4.
The thermal sensor of the FCP-OT320/FCP-OT320-R470 and all heat detectors is tested
with the test device for heat detectors.
7.4
Warranty
Defective detectors are exchanged free of charge in the case of a claim under the warranty.
7.5
Repair
In the event of a defect, the entire detector is exchanged.
7.6
Disposal
FCP-OC320 Packaging Film
The packaging bag used for multisensor detectors with C sensor consists of tear-resistant PE-
ALU laminated film and may be disposed of with the household refuse.
Defective detectors are exchanged and should be disposed of in accordance with statutory
regulations.
7.7
Additional Documentation
Unusable electrical and electronic devices/modules must not be disposed of
with normal household refuse. They must be disposed of in compliance with
the applicable regulations and directives (e. g. WEEE in Europe).
NOTICE!
The latest Product Information and the Installation Guide for the device are available as a
downloadable PDF file at http://www.boschsecurity.com/emea/fire.