FMC-420RW-HSRRD
en
13
Bosch Sicherheitssysteme GmbH
F.01U.099.400 | 1.0 | 2010.02
Notice
Product Description
Manual Call Point LSN improved resettable for outdoor use, surface
mounting. For installation refer to Page
.
Connection
Address Setting
Look up the address in the tables (Pages
) and set the 8 DIP switches
accordingly (see Pages
X
Use always the same operating mode within one loop, stub or T-tap!
Functional Test
1.
Press firmly onto the pane (6.1,
). As soon as the alarm has been
triggered, the LED is illuminated and the color display of the pane turns
from white to red.
2.
To reset the manual call point, unlock the maintenance flap with the
test key and pull it forwards (6.2 and 6.3,
3.
Insert the test key into the top openings and push it down (6.4,
The color display turns white again.
4.
Close the maintenance flap (6.5,
).
Technical Specifications
WARNING!
Risk of injury from electric shock. The system must be current-
free during connection work.
Pos. Description
Function
1
LSN1: a, b / LSN2: a, b
LSN incoming/LSN outgoing
2
E
Shielding
Address (A)
Operating mode
0
Loop/stub in LSN improved version mode with automatic
addressing
1 ... 254
Loop/stub/T-taps in LSN improved version mode with
manual addressing
255 = CL
Loop/stub in LSN classic mode (address range: max. 127)
LSN operating voltage
15 V DC to 33 V DC
LSN current consumption
0.4 mA
Permissible operating temperature
-25° C to +70° C
Protection class (EN 60529)
IP 67
Dimensions (H x W x D)
108 x 108 x 66 mm