background image

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EN 

Release Notes for Firmware V2.07 

Fire Alarm Control Panel 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DS9400 Series 

Содержание DS9400 Series

Страница 1: ...EN Release Notes for Firmware V2 07 Fire Alarm Control Panel DS9400 Series ...

Страница 2: ...grade Information If this firmware is installed in a control panel that has been running version 1 x software it is necessary to erase the old programming in the control panel and re select the control panel type when the control panel is first powered up Be careful to select 1 DS9400 an incorrect selection cannot be undone 3 0 Fixed Items in Firmware Version 2 05 Version 2 05 firmware for the DS9...

Страница 3: ... two on board relays is programmed using Zone 62 General Trouble For this output the relay will be energized when there are no troubles present in the system When there is a trouble the relay will de energize For this relay to function properly Zones B C and D must be programmed with a value of 00 The General Trouble output function can not be combined with any other output function When communica...

Страница 4: ...1 after installing firmware version 2 03 please contact Technical Support at 888 886 6189 DS9434 Four Point Expander Removal To prevent the accidental removal of the DS9434 a new message CALL FOR SERVICE is displayed If you wish to remove a previously installed DS9434 please contact Technical Support at 888 886 6189 7 0 Fixed Items Since Firmware Version 1 08 AC Failure during Automatic Battery Te...

Страница 5: ...ents on the line This issue was observed during recent lab testing of the control panel and has not been reported from actual installations but upgrading the firmware in installed control panels to version 2 02 will assure proper response time under all circumstances Programming Access Firmware version 2 02 corrects a configuration problem found in control panels with prior firmware that improperl...

Страница 6: ...emoval of DS9431 Multiplex Expansion Module Clears PINs If the DS9431 Multiplex Expansion Module is installed and then removed all Personal Identification Numbers PINs including the standard 16 PIN numbers will be erased when the DS9400 is re powered The PIN numbers can be re entered normally User ID Report for Drill and Walk Test As shown in Appendix C of the DS9400M Reference Guide P N 31499 or ...

Страница 7: ...one number or account number for phone number 2 while routing reports to line 1 backup line 2 If only one phone number is available for reporting set report steering for all events to phone 1 only Comm fault may also be caused if one of the phone lines has Telco battery voltage but will not complete a call Make test calls to the receiver s on both phone lines listening for the receiver ACK tone 6 ...

Страница 8: ... 2006 Bosch Security Systems 36925V Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 ...