DS7461i Installation Guide
© Bosch Security Systems
B.V., 2020
Page 3
5.1 DS7430 Multiplex Expansion Module Wiring
Note: Do not loop wires around the terminals.
DS7461i
Ground
Zone 1+
Multiplex Bus -
Multiplex Bus +
DS7430
Power Bus
N/C
N/O
Use 47K ohm EOL P/N:26069
for non-fire applications.
Use 47K ohm EOL P/N:28010
for fire applications.
Alarm Contact
(Normally Open or
Normally Closed)
Figure 3: Wiring to a DS7430 Multiplex Expansion Module
5.2 DS7436 Multiplex Expansion Module Wiring
DS7461i
Ground
Zone 1+
Multiplex Bus -
Multiplex Bus +
DS7436
N/C
N/O
Use 47K ohm EOL P/N:26069
for non-fire applications.
Use 47K ohm EOL P/N:28010
for fire applications.
Either Bus A or Bus B,
or both, may be used. Refer
to the panel’s reference guide.
PWR+ PWR- BUS+ BUS-
PWR+ PWR- BUS+ BUS-
Figure 4: Wiring to a DS7436 Multiplex Expansion Module
5.2 D8125MUX Multiplex Expansion Module Wiring
D8125 Multiplex Module
POWER A
MUX BUS A
POWER B
MUX BUS B
+
-
+
-
+
-
+
-
Either Bus A or Bus B,
or both, may be used. Refer
to the panel’s reference guide.
DS7461i
Ground
Zone 1+
Multiplex Bus -
Multiplex Bus +
N/C
N/O
Use 47K ohm EOL P/N:26069
for non-fire applications.
Use 47K ohm EOL P/N:28010
for fire applications.
Alarm Contact
(Normally Open or
Normally Closed)
Figure 5: Wiring to a D8125MUX Multiplex Expansion Module
6.0 Switch Settings
Set the address switch settings before connecting the DS7461i to the multiplex bus.
No two DS7461i Single Zone modules may be set to the same address. Having
two or more units set to the same address may prevent fault detection or cause
multiplex bus failure.
You can find the Address Switch Settings using the chart on the last page,
or by calculating the decimal number of the address.
Binary Switch Values (Point 17 shown)
O
N
1
2
3
4
5
6
7
8
128 64 32 16
8
4
2
1
The DS7400 Series control panels cannot be programmed for zone (point) addresses 001-008.
In the switch
settings chart
= ON
Address
Switches
1 2 3 4 5 6 7 8
O
N
1 2 3 4 5 6 7 8
O
N