DS7461i Installation Guide

© Bosch Security Systems

 B.V., 2020

Page 3

5.1 DS7430 Multiplex Expansion Module Wiring

Note: Do not loop wires around the terminals.

DS7461i

Ground

Zone 1+

Multiplex Bus -

Multiplex Bus +

    DS7430

Power       Bus

N/C

N/O

Use 47K ohm EOL P/N:26069

for non-fire applications.

Use 47K ohm EOL P/N:28010

for fire applications.

Alarm Contact

(Normally Open or

Normally Closed)

Figure 3: Wiring to a DS7430 Multiplex Expansion Module

5.2 DS7436 Multiplex Expansion Module Wiring

DS7461i

Ground

Zone 1+

Multiplex Bus -

Multiplex Bus +

DS7436

N/C

N/O

Use 47K ohm EOL P/N:26069

for non-fire applications.

Use 47K ohm EOL P/N:28010

for fire applications.

Either Bus A or Bus B,

or both, may be used. Refer

to the  panel’s reference guide.

PWR+ PWR- BUS+ BUS-

PWR+ PWR- BUS+ BUS-

Figure 4: Wiring to a DS7436 Multiplex Expansion Module

5.2 D8125MUX Multiplex Expansion Module Wiring

D8125 Multiplex Module

POWER A

MUX BUS A

POWER B

MUX BUS B

+

-

+

-

+

-

+

-

Either Bus A or Bus B,

or both, may be used. Refer

to the  panel’s reference guide.

DS7461i

Ground

Zone 1+

Multiplex Bus -

Multiplex Bus +

N/C

N/O

Use 47K ohm EOL P/N:26069

for non-fire applications.

Use 47K ohm EOL P/N:28010

for fire applications.

Alarm Contact

(Normally Open or

Normally Closed)

Figure 5: Wiring to a D8125MUX Multiplex Expansion Module

6.0 Switch Settings

Set the address switch settings before connecting the DS7461i to the multiplex bus.

No two DS7461i Single Zone modules may be set to the same address. Having
two or more units set to the same address may prevent fault detection or cause
multiplex bus failure.

You can find the Address Switch Settings using the chart on the last page,
or by calculating the decimal number of the address.

Binary Switch Values (Point 17 shown)

O
N

1

2

3

4

5

6

7

8

128 64 32 16

8

4

2

1

The DS7400 Series control panels cannot be programmed for zone (point) addresses 001-008.

In the switch

settings chart

      = ON

Address

Switches

1  2  3  4  5  6  7  8

O
N

1  2  3  4  5  6  7  8

O
N

Содержание DS7461i

Страница 1: ...AWG 76 m 0 65 mm 193 m 1 02 mm Fire applications require 18 AWG Operating Temperature Range 32 F to 122 F 0 C to 50 C Relative Humidity 0 to 93 Signaling Line Circuit Class B Initiating Circuit Class B When used in a fire system NFPA 72 prohibits this product from sharing a communications bus with non fire devices 3 0 Programming Refer to the control panel s installation guide for multiplex zone p...

Страница 2: ...461i Terminals Description Bus Positive Multiplex Input Bus Negative Multiplex Input 1 Input Zone Positive Input G Input Zone Ground Table 1 DS7461i Terminal Descriptions Connect wiring to the DS7461i as shown in Figure 3 and Figure 4 Input zones are designed to monitor Normally Open or Normally Closed dry contacts They are supervised using 47K ohm end of line resistors The protection zone can be ...

Страница 3: ... D8125 Multiplex Module POWER A MUX BUS A POWER B MUX BUS B Either Bus A or Bus B or both may be used Refer to the panel s reference guide DS7461i Ground Zone 1 Multiplex Bus Multiplex Bus N C N O Use 47K ohm EOL P N 26069 for non fire applications Use 47K ohm EOL P N 28010 for fire applications Alarm Contact Normally Open or Normally Closed Figure 5 Wiring to a D8125MUX Multiplex Expansion Module...

Страница 4: ... SWITCH NUMBER SWITCH ON CLOSED 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190 191 192 1 2 3 4 5 6 7 8 ZONE POINT ADDRESS SWITCH NUMBER SWITCH ON CLOSED 193 194 195 196 197 198 199 200 201 202 203 20...

Отзывы: