DS6R2
|
Installation and Operation Guide | 3.0 Programming
.
Bosch Security Systems, Inc. | 4/08 | F01U081960-01
13
Table 3: Programming Values (continued)
Program
Address Description
Factory
Default Value
Program Value
56
RF Key fob 2 ID Number
000000000
000000000 = Disabled
Allows 000000001 to 999999999 ID numbers
57
RF Key fob 3 ID Number
000000000
000000000 = Disabled
Allows 000000001 to 999999999 ID numbers
58
RF Key fob 4 ID Number
000000000
000000000 = Disabled
Allows 000000001 to 999999999 ID numbers
59
RF Key fob 5 ID Number
000000000
000000000 = Disabled
Allows 000000001 to 999999999 ID numbers
60
RF Key fob 6 ID Number
000000000
000000000 = Disabled
Allows 000000001 to 999999999 ID numbers
99
Return to factory default values
0
18
Enter this value to return all values except the Master Code to
the factory default values. Use this function for installation and
maintenance. Refer to
Section 3.5 Resetting Default Values
on
page 14 to return the Master Code to its default value.
Table 4: Zone Types
Type Description
Instant
When the system is armed, faulting an Instant zone causes an alarm.
Delay
When the system is armed, faulting this zone causes an alarm after the Entry or Exit Delay time setting
expires.
24-hour
This zone is always active. Faulting this zone always causes an alarm.
Follower
When the system is armed and a Delay zone is not faulted, faulting this zone causes an alarm. If a Delay
zone is faulted, an alarm occurs after the delay time.
Silent Zone
When the system is armed, faulting a Silent zone causes a Silent alarm. The keypad is silent and shows
no alarm output, but the DS6R2 sends an alarm event to the central station.
Perimeter Zone
When the perimeter is armed, faulting a Perimeter zone causes an alarm.
Perimeter Delay
Zone
When the perimeter is armed, faulting this zone causes an alarm after the Entry or Exit Delay time setting
expires.
Bypass
If a zone is programmed to bypass when arming the system:
1.
Enter your PIN.
2.
Press the [Bypass] key.
3.
Enter the zone number.
4.
Press [ON] to bypass this zone.
The bypass condition clears when the system is disarmed. A 24-hour zone type cannot be bypassed. All
other zone types can be bypassed.
Shunt
If a zone is programmed for Zone Shunt, only the first zone faulted causes an alarm. All other faults during
this armed period are ignored. The Zone Shunt clears when the system is disarmed.
Request-to-exit
(REX)
When this zone is disarmed, activating this input activates the output programmed to follow the Door
Unlock Time setting.
If Zone 6 is programmed to 8=REX, Door Unlock activates after Zone 6 is activated.