DS160/161

Request To Exit PIR sensors

Installation Instructions

1.0

Description

The DS160/161 is a passive-infrared (PIR) detector designed for request to exit (REX) interior applications. It is UL Listed as an access
control device under the UL 294 Standard.

The technology designed into the DS160/161 is based on the principal that all objects emit infrared energy. The warmer an object is, the more
infrared energy emitted. Its PIR technology allows the DS160/161 to detect the change in infrared energy that occurs when a person passes
through its field of view.

 The DS160/161 has features such as Sequential Logic Input (SLI) to eliminate unauthorized entry. SLI allows you to arm the detector using
any dry contact device, such as a second detector, card reader, or the access control system. This provides better control for this type of
application.

A built-in sounder can be automatically activated if the door is propped open. The sounder can be controlled from any dry contact device. The
DS160/161 detection pattern provides dense C-shaped coverage ideal for most REX applications. In addition, complete pattern control
allows it to be adjusted to a single zone or placed over a doorknob, for example. There are fifteen possible coverage patterns to accommo-
date most applications. This, combined with the ability to monitor the door and intelligently control the lock, adds considerable security to
these types of applications.

The DS160/161 uses Motion Analyzer II signal processing to help prevent false activation due to environmental conditions.  The relay output
consists of two Form “C” contacts that can be adjusted to latch from approximately 0.5 to 64 seconds. The latch time features two modes of
operation, resettable (where the relay timer will not time out as long as someone is in the field of view) and non-resettable (where the relay
will remain latched for a fixed period of time). The relay can also be programmed to fail safe or fail secure in the event of power loss.

The DS160/161 may either be ceiling or wall mounted, and its pattern may be aimed and/or masked for more effective use based upon
installation needs. It is not designed as a primary means of exit for emergency egress applications.

The DS160/161 is available in a light grey (DS160) or a black (DS161) enclosure along with an optional trim plate (light gray TP160 or black
TP161) that can cover a single gang box. Panic hardware must be used with this or any other egress device.

2.0

Specifications

• Input Power:

12 VDC to 30 VDC or AC

• Current Draw: 39 mA at 12 VAC, 76 mA at 30 VAC Alarm 39 mA at

12 VDC, 60 mA at 30 VDC Alarm 8 mA nominal
standby current

• Relay:

Two Form “C” contact sets rated for 1 A  each at
30 VDC or AC max  for resistive loads.

• Sounder:

85 dB with adjustable volume

• Temperature:

-20°F to +120°F (-29°X to +49°C). For UL
Listed installations, the temperature range
is +32°F to +120°F (0°F to +49°C)

.

• Humidity:

0% to 95% non-condensing. 0% to 85%
non-condensing for UL Listed
installations

.

• Dimensions ( xWxD):

1.8 in. x 7 in. x 1.75 in.
(4.5 cm x 17.8 cm x 4.4 cm)

• Trim plate (HxW):

Optional. TP160 (light gray); TP161 (black)
3 in. x 8.25 in. (7.6 cm x 21 cm)

3.0

Installation

3.1

Remove the cover using a small flat blade screwdriver.

Insert screwdriver

here

Bottom

of

unit

3.2

Rotate the detector clockwise to remove it from the
base.

3.3

Select a mounting location

     

Push to Exit

Alarm will Sound

Push to Exit

Alarm will Sound

Push to Exit

Alarm will Sound

Push to Exit

Alarm will Sound

Above the

Door

On the Ceiling

Above

Double Doors

Содержание DS161

Страница 1: ...mately 0 5 to 64 seconds The latch time features two modes of operation resettable where the relay timer will not time out as long as someone is in the field of view and non resettable where the relay will remain latched for a fixed period of time The relay can also be programmed to fail safe or fail secure in the event of power loss The DS160 161 may either be ceiling or wall mounted and its patt...

Страница 2: ... NO NC C NO D R T T 4 3 2 Spike Protection Many magnetic locks and electric door strikes have built in spike protection also be called diode protected If your lock is not spike protected install a bridge rectifier such as a KBL005 between the relay contacts and the magnetic lock door strike as shown below 12 30 Volt DC or AC Power Supply Maglock NC C NO NC C NO D R T T Bridge Rectifier Relay conta...

Страница 3: ...S160 161 does when the contact attached to Terminal R is closed Keycard Input An input to the Terminal R activates the detector Normally this is used with a keycard reader outside of the door building The internal sounder does not activate when the keycard input is selected The keycard inputs are affected by Resettable Non resettable Mode Switch 2 The relay remains activated for as long as the key...

Страница 4: ...witch 10 is OFF Monitor External Device Mode Input Devices Normally Closed contacts NC C NO NC C NO D R T T Photoelectric Beams PIRs Floor Switches Keycard Readers 5 7 4 Wiring Example Monitor Door Contacts First Option In the Monitor Door Contacts Mode a person entering the field of view of the detector activates the relay and timer Door contacts connected to Terminal D monitor if the door is ope...

Страница 5: ...as described in Section 5 7 3 after the contact closes 12 30 Volt DC or AC Power Supply Maglock Relay contacts shown with Switch 3 ON Failsafe Mode Switch 9 is ON and Switch 10 is OFF Monitor External Device Mode NC C NO NC C NO D R T T Access Control System Contacts Controlthispal Inc The NFPA 101 Life Safety Code requires secured doors to have a manual release device that shall result in direct ...

Страница 6: ...ounted on a wall above the door or on the ceiling The unit can also be masked to allow only some parts of the coverage pattern to be active 7 1 Examples When the unit is mounted on the wall and the lens is pointed straight down some detection zones point toward the wall and do not detect movement Views of coverage pattern with the unit mounted at 7 5 ft 2 3 m above the floor with the eye pointed s...

Страница 7: ...uch as around a doorknob or crash bar ALARM WILL SOUND WHEN DOOR IS OPENED Masking wedges The coverage pattern depends on how high the DS160 161 is mounted location of the unit and the position of the detector lens If you want a setup as shown above mount the DS160 161 just above the door on the hinge side with the lens pointed down and slightly out IMPORTANT ...

Страница 8: ...y Systems 130 Perinton Parkway Fairport New York USA 14450 9199 Customer Service 800 289 0096 Technical Support 888 886 6189 2004 Bosch Security Systems DS160 DS161 Installation Instructions P N 37365M 02 04 Page 8 ...

Отзывы: