5.0
Setup and Testing
1.
Apply power to the unit.
2.
Wait at least 3 min for the detector to settle.
3.
Test the unit by walking directly through the coverage area, toward
the door.
4.
Aim the detector up or down if necessary to obtain the proper
coverage. Tighten the screws after aiming the detector.
5.
Check that the relay latch time is sufficient. Adjust if necessary.
6.
After confirming proper operation, replace the cover and walk test
one more time to ensure the coverage has not changed.
6.0 Other
Information
Single Door Use:
The pattern can be masked to remove the outer
zones using the supplied masking kit. Snap the masking wedges into
place on the outer surface of the lens (refer to
Figure 7
). The
masking wedges eliminate zones A, B, K, and L.
Figure 7: Pattern Masking
Testing:
Test the detector a minimum of once each year to ensure
continued operation.
7.0 Coverage
Figure 8 and Figure 9 show the standard patterns for a wall-mounted unit.
Figure 8: Standard Patterns for a Wall-mounted Unit
3.0
1.5
0
3.0
1.5
Meters
0
5
Feet
10
5
0
5
10
Feet
Meters
0
1.5
Pointed
-14°
D
F
H
J
I
C
E
G
Mounted at 7 ft
Mounted at 15 ft
Top View
Pattern on the Floor
4.5
3.0
1.5
0
4.5
3.0
1.5
Meters
0
5
10
15
Feet
15
10
5
0
5
10
15
Meters
0
1.5
3.0
4.5
Pointed
+14°
D
F
H
J
I
C
E
G
B
L
K
A
Figure 9: Standard Patterns for a Wall-mounted Unit
Front View
4.5
3.0
1.5
0
4.5
3.0
1.5
Meters
0
5
10
15
Feet
15
10
5
0
5
10
15
Feet
Meters
0
1.5
3.0
4.5
Side View
0
1.5
Meters
0
5
7
0
5
Feet
0
1.5
Meters
4.5
3.0
Meters
0
1.5
3.0
4.5
0
5
Feet
10
15
10
15
Feet
Pointed at
-14°
Pointed at
+14°