Bosch DRA Series Скачать руководство пользователя страница 8

Figure 2.8: Wiring a DRA Annunciator to a D340 duct smoke housing

D341/D342 duct smoke housings
The D341 or D342 duct smoke housings used for the D285DH photoelectric smoke detection
head or the D286 ionization smoke detection head requires use of the DRA-5 Annunciator.
Connect the positive (RED) lead to terminal 3 (RED LED) and the negative lead (WHITE) to
terminal 8 (GROUND).

Figure 2.9: Wiring a DRA Annunciator to a D34 or-D342 duct smoke housing

D343 MUX duct smoke housing
The D343 MUX duct smoke housing used for the D7050DH photoelectric smoke detection
head requires use of the DRA-5 Annunciator. Connect the positive (RED) lead to terminal 8
(RED LED) and the negative lead (WHITE) to terminal 5 (GROUND).

8

en | Connection

DRA Remote Annunciators

09/2012 | 01 | F.01U.275.209

Installation Guide

Bosch Security Systems, Inc.

Содержание DRA Series

Страница 1: ...DRA Remote Annunciators DRA 5 and DRA 12 24 en Installation Guide ...

Страница 2: ......

Страница 3: ...Table of contents 1 Introduction 4 2 Connection 5 3 Technical data 10 DRA Remote Annunciators Table of Contents en 3 Bosch Security Systems Inc Installation Guide 09 2012 01 F 01U 275 209 ...

Страница 4: ...ion of alarms for a number of Bosch Security Systems fire alarm detectors It is designed to be mounted to a single gang box but it can also be surface mounted 1 4 en Introduction DRA Remote Annunciators 09 2012 01 F 01U 275 209 Installation Guide Bosch Security Systems Inc ...

Страница 5: ...al 2 wire base Four wire bases The D292 D293A D293E or D293S base used for two wire conventional detectors requires use of the DRA 5 Annunciator Connect the positive RED lead to terminal 3 and the negative lead WHITE to terminal 4 Figure 2 2 Wiring a DRA Annunciator to a 4 wire base Multiplex bases The D7050 B6 base used for multiplex detectors requires use of the DRA 12 24 Annunciator Connect the...

Страница 6: ...terminal c Figure 2 4 Wiring a DRA Annunciator to F220_Bases FAA 440 standard bases The FAA 440 B4 or FAA 440 B6 base used for FAP 440 and FAH 440 detectors requires use of the DRA 5 Annunciator or the DRA 12 24 Annunciator Connect the positive RED lead to terminal S and the negative lead WHITE to terminal C Figure 2 5 Wiring a DRA Annunciator to FAA 440 standard bases 6 en Connection DRA Remote A...

Страница 7: ...E base used for F220 detectors requires use of the DRA 5 Annunciator Connect the positive RED lead to terminal V and the negative lead WHITE to terminal C Figure 2 7 Wiring a DRA Annunciator to FCA 500 bases D340 duct smoke housing The D340 duct smoke housing used for D285DH photoelectric smoke detection head requires use of the DRA 5 Annunciator Connect the positive RED lead to terminal 12 RMT LE...

Страница 8: ...erminal 3 RED LED and the negative lead WHITE to terminal 8 GROUND Figure 2 9 Wiring a DRA Annunciator to a D34 or D342 duct smoke housing D343 MUX duct smoke housing The D343 MUX duct smoke housing used for the D7050DH photoelectric smoke detection head requires use of the DRA 5 Annunciator Connect the positive RED lead to terminal 8 RED LED and the negative lead WHITE to terminal 5 GROUND 8 en C...

Страница 9: ...Figure 2 10 Wiring a DRA Annunciator to a D343 duct smoke housing DRA Remote Annunciators Connection en 9 Bosch Security Systems Inc Installation Guide 09 2012 01 F 01U 275 209 ...

Страница 10: ...raw DRA 5 10 mA at 5 V DRA 12 24 10 mA at 24 V Mechanical Dimensions HxWxD Standard single gang wall plate 4 85 in x 3 1 in x 0 25 in 123 2 mm x 78 7 mm x 6 35 mm 3 10 en Technical data DRA Remote Annunciators 09 2012 01 F 01U 275 209 Installation Guide Bosch Security Systems Inc ...

Страница 11: ......

Страница 12: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2012 ...

Отзывы: