Installation and Operation Manual 

DDC KIT

8 733 900 571

Revised 05-11

Содержание DDC KIT

Страница 1: ...Installation and Operation Manual DDC KIT 8 733 900 571 Revised 05 11 ...

Страница 2: ... Copyright 2011 Bosch Inc All rights reserved ...

Страница 3: ...r notice Table of Contents THE ZONE CONTROLLER 4 SPECIFICATIONS 4 INSTALLATION PROCESS 5 Mounting Holes 5 Install Sensors 5 Routing Wire Harness 6 DDC Wiring Diagrams 8 For use with TW Models 8 For use with BP CP CE and TA models 9 Table of Contents DDC KIT 3 ...

Страница 4: ...ersal Inputs 8 inputs Inputs 1 and 2 are configurable for 0 5VDC 10K ohm thermistor or dry contact inputs 3 and 4 support thermistor or dry contact only inputs 5 and 6 support thermistor dry contact or LogiStat Standard Communication Ports Comm Port 3 pin port configurable for ARC156 BACnet over ARC156 or EIA 485communications BACnet MS TP Modbus RTU orN2 Rnet Port 4 pin port for interface with re...

Страница 5: ...rature DAT location Installation Process Mounting Holes Controller shall be installed on the right side of unit mounting holes are available on DDC panel behind the electrical box as shown in Figure 2 The DDC kit includes all components required for the installation Follow these steps to mount controller on the side of the unit Align controller with pilot holes as shown in Figure 2 Secure controll...

Страница 6: ...he DIP switch to pulse 6 DDC KIT Routing Wire Harness Figure 4 Leaving Water Temperature Location Figure 5 Leaving Water Sensor with wire ties n Avoid sharp edges on unit cabinet during installation n Sensor must be on a clean surface of the metal portion of coil Figure 6 Sensor with insulating tape Sensor Insulating tape Figure 7 Final Sensor installation Pipe Insulating tape C C O C G R Y CONNEC...

Страница 7: ...and unit wiring diagrams as the ultimate guide for electrical reference This installation shall be performed by a trained and or certified HVAC Electrical technician Data plate included in package to be placed to the right of the data plate of the unit DDC Termination CE TA Models DDC KIT 7 T1 T2 L2 L1 TRANSFORMER ECM MOTOR INTERFACE BOARD CONTACTOR COMPRESSOR RED OR ORG ORG OR RED BLK ECM MOTOR P...

Страница 8: ... LINE UNIT FHP PART SW VERSION 2 17 2011 OPTIONAL COMPONENTS IN1 CONTROLLER INPUT 1 DIGITAL ENABLE SWITCH NO IN5 CONTROLLER INPUT 5 CTS CHANGEOVER TEMPERATURE SENSOR IN6 CONTROLLER INPUT 6 CMS CONTROL MODE SWITCH OFF HEAT ON COOL IN5 IN1 IN6 STANDARD COMPONENTS ELTS ENTERING LOAD WATER TEMPERATURE SENSOR LSTS LEAVING SOURCE WATER TEMPERATURE SENSOR LSTS ELTS DRY HOT TO BE TERMINATED ON PUMP RELAY ...

Страница 9: ...HARGE AIR TEMPERATURE SENSOR LWTS LEAVING WATER TEMPERATURE SENSOR LWTS DATS OPTIONAL COMPONENTS IN1 CONTROLLER INPUT 1 DE DIGITAL ENABLE NO RHS RELATIVE HUMIDITY SENSOR IN5 CONTROLLER INPUT5 DFS DIRTY FILTER SWITCH IN6 CONTROLLER INPUT6 RTS REMOTE TEMPERATURE SENSOR IN1 IN6 IN5 IN1 2 17 2011 DRY HOT IN1 Gnd IN2 Gnd H TERMINAL IS USED ON REHEAT APPLICATIONS ONLY DENOTES FIELD TERMINATED COMPONENTS...

Страница 10: ...Subject to change without prior notice Revised 05 11 8 733 900 571 10 DDC KIT Notes ...

Страница 11: ...8 733 900 571 Revised 05 11 Subject to change without prior notice Notes DDC KIT 11 ...

Страница 12: ...601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www boschtaxcredit com www bosch climate us ...