Troubleshooting
The LED on the module is used to indicate the operational status of the Battery Charger. The
following table describes the different states of the LED.
Symptom
Diagnosis
Remedy/description
LED color
LED status
Green
ON
AC transformer power present No action
OFF
AC transformer power
not
present
–
Check if the Transformer
is plugged into a non-
switched outlet.
–
Check 120 VAC supply to
outlet.
–
Check if transformer has a
faulty secondary; fuse may
be blown.
Tab.
5.2:
LED status troubleshooting
To insure the module is not faulty, meter the battery leads of the module. A reading of
13.80
VDC or higher indicates the unit is functioning normally.
6
Specifications
Electrical
Float Voltage
1
13.9
VDC maximum
Supplied Voltage
16.5
VAC, 40
VA supplied by D1640 plug‑in transformer
Supplied Current
1.2
A
Ampere-hours
27
Ah maximum
1
measured with batteries in circuit
Mechanical
Dimensions (HxWxD)
0.75
in. x 3.0
in. x 5.0
in. (1.9
cm x 7.6
cm x 12
cm)