Bosch D8132 Скачать руководство пользователя страница 1

Battery charger modules

D8132 and D8132LT

en

Installation manual

Содержание D8132

Страница 1: ...Battery charger modules D8132 and D8132LT en Installation manual ...

Страница 2: ......

Страница 3: ...ing to these instructions NFPA codes local codes and the authority having jurisdiction AHJ Failure to follow these instructions can result in failure of a detector to initiate an alarm event Bosch Security Systems Inc is not responsible for improperly installed tested or maintained devices Before installing the module become familiar with the Installation and Operation Guide for the control panel ...

Страница 4: ...teries D126 or up to two 12 V 13 5 Ah batteries can be installed with the module The module is ideal for systems requiring extended battery standby time such as UL Bank Safe and Vault applications and systems requiring additional auxiliary current output In addition to providing increased standby time and auxiliary power the batteries also filter the AC power supply The amount of ripple that appea...

Страница 5: ...acent to the control panel s enclosure Figure 3 1 Module installation 1 Enclosure 3 Mounting locations 2 Module 4 Mounting screws 3 Install the module in one of the vertical mounting locations The upper mounting location is recommended if two 12 V 13 5 Ah batteries will be installed Fasten the module in place with the three mounting screws provided The green AC power LED on the module can be viewe...

Страница 6: ...me Ampere hour and auxiliary current values are identified determine the combination of batteries required for your application using the following table 24 standby hours 60 standby hours 72 standby hours Total battery Amp hrs Ah Aux current load Recharge time hrs Aux current load Recharge time hrs Aux current load Recharge time hrs 430 mA 9 N A N A N A N A 12 550 mA 10 50 mA 7 10 mA 7 15 680 mA 1...

Страница 7: ...o the control panel s battery negative terminal 2 Connect the red wire of the four pin connector cable to the control panel s battery positive terminal Warning Do not short these wires 3 Plug the four pin connector cable into J1 on the module 4 Connect the two grey wires to a separate 16 5 V 40 VA transformer D1640 Warning Do not connect the grey wires to the control panel s transformer terminals ...

Страница 8: ...n the section Wiring for extending battery standby time and providing additional auxiliary current output page 6 These values will vary depending upon the condition of the batteries installed For standalone power supply operation install the module as shown in the following figure Figure 4 2 Wiring D8132 as standalone power supply 1 AC branch circuit unswitched 5 Devices 2 D1640 transformer 6 Gray...

Страница 9: ...control panel from the D8132 to the device loop and from the device loop ground to the control panel earth ground GV3 and GV4 panels require a D1640 transformer For legacy products refer to the control panel documentation The D8132 can support up to 27 Ah of battery backup If two batteries are used they must have the same Ampere hour Ah rating When the control panel and the module are connected to...

Страница 10: ...heck if the Transformer is plugged into a non switched outlet Check 120 VAC supply to outlet Check if transformer has a faulty secondary fuse may be blown Tab 5 2 LED status troubleshooting To insure the module is not faulty meter the battery leads of the module A reading of 13 80 VDC or higher indicates the unit is functioning normally 6 Specifications Electrical Float Voltage1 13 9 VDC maximum S...

Страница 11: ......

Страница 12: ...Bosch Security Systems Inc 130 Perinton Parkway Fairport NY 14450 USA www boschsecurity com Bosch Security Systems Inc 2018 Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany ...