background image

D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide

Page 18

© 2004 Bosch Security Systems, Inc.

43700F

D9412G/D7412G/D7212G

Troubleshooting

• With the overload removed, the panel returns power to Terminals 3, 6, 7, 8, 24, and 32, and the Programming

Connector.  The panel sends 

PT BUS RESTORAL

 and 

SDI RESTORAL

 reports.

• If a D928 Module is connected, it stops sounding.

• If the battery voltage is below 8.4 V, the panel does not reconnect it. The battery must be replaced.

• When the battery reaches 13.7 V, the panel sends a 

BATTERY RESTORE

 report and turns off the red Low

Battery LED.

• When the battery reaches 13.9 V, the panel turns off the yellow Charging Status LED.

3.15

Service Walk Test

The Service Walk Test differs from the standard Walk Test in that POPITs whose switches are set for a point number not
programmed in the panel appear in the test.

The Service Walk Test allows a user to walk test all 246 points from a panel-wide command center, regardless of the point
index type. 

246 PTS TO TEST

 will appear in the D7412G and D7212G Control Panels even though there is a maximum

of only 75 and 40 points available, respectively. Service Walk Tests may also be initiated by account-wide or area-wide
command centers but will only test those points that fall within the scope of the command center that initiated the function.
The Service Walk Test will not test points in areas that are currently armed.

WARNING

Fire and other 24-hour points do not transmit reports during Service Walk Test!

The steps below outline a simple Service Walk Test procedure. The flow chart (Figure 1 on page 19) shows all the Service Walk
Test options.

1.

Choose a command center to conduct the test. Be certain the display shows the idle disarmed text.

2.

Press the [MENU] key to enter the Function List. Press[NEXT] repeatedly until reaching the

SERVICE WALK ?

 prompt. Press [ENT]. Or press [9][9] followed by [ENT] to reach the Service Menu to

access the Service Walk Test.

Note:

The D7412G and D7212G do NOT include the Service Walk Test in the Service Menu. Therefore, the D7412G and
D7212G must have the Service Walk Test function enabled in the Function List in order for the Service Walk Test to
be accessed.

3.

The display shows 

### PTS TO TEST

 

. Test the first detection device.

4.

As the detection devices are faulted, the command center emits a brief tone and displays the point text of the
point tested for 60 seconds. After 60 seconds, the display returns to the points to test message.

Extra Points display default text:  

If the switches on a POPIT are set  incorrectly to a point number that is not in

the program for the panel, the default text for that point number (

PT ###

) displays when the point is

faulted. The panel’s Program Record Sheet shows the default text for all points.

Faulting the point a second time produces the tone and displays the point text, but does not reduce the 

PTS TO

TEST

 count.

5.

During the Service Walk Test, to see the points that remain untested, press [ESC]

 

when point text is displayed.

The display shows 

## PTS TO TEST

. Press the [ESC] key. 

VIEW UNTESTED ?

  is displayed. Press

[ENT].

 

## PTS UNTESTED

 is displayed. Press [NEXT] to see a list of the points that have not yet been

tested. Move through this list by pressing the [NEXT] key. To resume the Service Walk Test, press [ESC]. 

##

PTS UNTESTED

 

 is displayed. Press [ESC]. 

 

## PTS TO TEST

 

is displayed. Resume testing points. To end

the Service Walk Test, press [ESC] twice.

6.

After testing the last point, 

0 PTS TO TEST

 displays. Press [ESC]. The display momentarily shows 

ALL

PTS TESTED

 before returning to idle text.

Note:

The Service Walk Test, when performed on a D7412G and D7212G, cannot display “0 points to test” as it is physically
unable to connect to the second POPEX Module (used for Points 129-247).

Automatic time-out returns the system to idle text: If there is no point or command center activity for 20 min., the
walk test ends automatically. The command center returns to idle text.

Содержание D7212G

Страница 1: ...Control Panels D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Страница 2: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 2 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Страница 3: ... 8 Problems with the D8125 POPEX Data Expansion Loops 15 3 8 1 Metering the Loops 15 3 9 EMI on Long Wire Runs 16 3 10 Checking Shielded Cable 16 3 11 Battery and Power Reports 16 3 12 Watchdog Reset Reports 17 3 13 Runaway Reports to the Receiver 17 3 14 Overloaded Power Supply 17 3 15 Service Walk Test 18 3 16 Ground Fault 20 3 16 1 Procedure for Isolating Earth Ground Faults 20 3 17 Panel Buzze...

Страница 4: ...gure 8 D7212G System Wiring Diagram 29 Figure 9 D7212G System Wiring Diagram 30 Figure 10 D7212G System Wiring Diagram 31 Tables Table 1 Chapter Summary 5 Table 2 Referenced Literature 5 Table 3 Quick Reference Terminal Description 7 Table 4 Troubleshooting Problems Found During Self Diagnostics 9 Table 5 Troubleshooting Problems Programming the Panel 10 Table 6 Troubleshooting Command Center Prob...

Страница 5: ...are summarized in Table 1 Section No Description 1 Introduction information about organization of the manual and additional literature that may be ordered 2 Quick Reference Terminal Description description of panel terminals presented in a quick reference table 2 Basic Troubleshooting basic troubleshooting solutions and procedures to resolve common problems during programming and installation of t...

Страница 6: ...138544 D7212G Program Entry Guide 4998138538 D7212G Program Record Sheet 4998138542 D7212G Release Notes 4998138543 D7412G Release Notes 43856 D8125MUX Operation and Installation Guide 36796 D9210B Operation and Installation Guide 32206 D9412G Release Notes 43821 D9412G D7412G Approved Applications Compliance Guide 43494 D9412G D7412G D7212G Installation and Troubleshooting Quick Reference Guide 4...

Страница 7: ... output interrupted by RESET SENSORS or alarm verification Shares PTC with Terminals 6 and 7 D136 Plug in Relay required Install a D136 in the SW AUX socket for output at Terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power Steady or Pulsed Alarm Power Alternate Alarm Power and Switched Aux Power Terminals 3 6 7 and 8 10 EARTH GROUND Connect to earth ground A cold water pipe or grounding r...

Страница 8: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 8 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Quick Reference Terminal Description Notes ...

Страница 9: ...C silences the buzzer The display clears when communication restores i e the receiver acknowledges a report PANEL BROKEN appears in the displays of all command centers the command center buzzer sounds and the green operation monitor LED stops flickering or is off A hardware or software problem has occurred Pressing ESC does not silence the buzzer The panel must be returned to Bosch Security System...

Страница 10: ...e P N 43488 for a complete description SERVC PRINTER appears in command center displays The panel has lost contact with a supervised printer Pressing ESC silences the buzzer The displays clear when contact with the missing printer restores Table 4 cont d Troubleshooting Problems Found During Self Diagnostics 3 3 Problems Programming the Panel Before attempting to program the panel become familiar ...

Страница 11: ...turned on Table 6 Troubleshooting Command Center Problems 3 5 Phone Line Trouble Phone line problems that are not corrected can result in the panel going into Communications Failure The D9412G D7412G can be programmed to monitor one or two phone lines See the D9412G D7412G Program Entry Guide P N 47775 for programming instructions If the phone line monitor is enabled SERVC PHONE LINE 1 or SERVC PH...

Страница 12: ... shorted between the phone company s equipment and the receiver by placing a call to the number for the receiver If you hear the line ring but the ring detector doesn t light or if you hear a busy signal and the green on line OL indicator is not lit call the phone company for service The panel reaches a busy signal for all ten attempts to reach the receiver The receiver s call load is too great Ad...

Страница 13: ...k Test to search for extra points may help diagnose the problem Problem with data expansion loop See Section 3 8 Problems with the D8125 POPEX Data Expansion Loops on page 15 Points intermittently appear as missing Points are erratic Debounce Count parameter set at 1 If an off board point is in transition between normal and faulted conditions as the panel scans it it appears as missing It is recom...

Страница 14: ...the panel or Data Expansion Loop may be disconnected from POPEX module Check POPEX module for correct connections to the panel and the Data Expansion Loop If you find missing points the service walk test may help you diagnose the problem see Section 3 7 1 Extra Points Keyswitch points P Type is programmed as 4 5 6 7 or 9 report as missing If area is armed the point reports a MISSING ALARM If the a...

Страница 15: ...7320 2231 14 11650 3551 Table 10 Data Expansion Loop Wire Specifications When metering the loop monitor it long enough to observe an intermittent problem To meter the data expansion loop without POPITs connected to it 1 Disconnect the loop from the POPEX Module 2 Twist the positive and then the negative wires together at each POPIT location so that the positive and negative wires are continuous to...

Страница 16: ...nd source 3 10 Checking Shielded Cable If improperly installed shielded cable can create problems rather than solve them Follow the procedure below to check shielded cable for proper installation 1 Remove the drain wire for the shield from Terminal 10 2 Meter the drain wire for continuity to Terminal 10 earth ground If there is continuity find and remove the foreign ground on the drain wire 3 Reco...

Страница 17: ...use runaway reports to the receiver on AC failure Be sure to replace all D8128 or D8128A OctoPOPITS with the D8128D Module 3 14 Overloaded Power Supply If the load on the panel s power supply exceeds its capacity the panel follows a routine to protect itself and the battery It sends reports to the Central Station at several points during this routine Keep in mind that AC power remains at Terminals...

Страница 18: ... SERVICE WALK prompt Press ENT Or press 9 9 followed by ENT to reach the Service Menu to access the ServiceWalk Test Note TheD7412GandD7212GdoNOTincludetheServiceWalkTestintheServiceMenu Therefore theD7412Gand D7212G must have the Service Walk Test function enabled in the Function List in order for the Service Walk Test to beaccessed 3 The display shows PTS TO TEST Test the first detection device ...

Страница 19: ...T ENT ESC ESC ESC ESC NEXT Test a device Test a device Test a device Test a device Text displays for 60 seconds Text displays for 60 seconds IDLE TEXT SERVICE WALK 246 PTS TO TEST POINT TEXT 245 PTS TO TEST POINT TEXT 244 PTS TO TEST POINT TEXT 1 PTS TO TEST VIEW UNTESTED 0 PTS TO TEST PTS UNTESTED POINT TEXT ESC ESC ESC Figure 1 Service Walk Test Flow Chart ...

Страница 20: ... and 13 88 VDC STOP This voltage reading means that the Ground Fault may be in one of the Panel power circuits such as the Battery or AUX Remove both battery wires from terminal 4 and terminal 5 at the same time If the voltage across terminals 9 and 10 changes to 6 5 to 6 8 VDC which indicates a normal reading then the ground fault is on the battery wire or wires Locate and remove the ground fault...

Страница 21: ... known earth ground is needed for the test Once the earth ground fault is isolated remove the ground repair the wire or replace the wire 6 If the voltage being read represents a ground fault on terminals 25 26 or 28 the ground fault condition may physically be on either the Zonex Bus Popit Bus or an input point on an OctoPopit or Popit To isolate the ground fault in this scenario follow these step...

Страница 22: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 22 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Troubleshooting Notes ...

Страница 23: ...GRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED ON WHEN COMMUNICATING OFF WHEN IDLE GRN PROG CONN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket GND START RED 1...

Страница 24: ...EN IDLE VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket GND START D130 1 2 5 3 4 Figure 3 D9412G System Wiring Diagram 2 of 3 1 Op...

Страница 25: ... CONN Point 8 GND FAULT Detect E N A B L E D I S A B L E ZONEX OUT 2 26 25 ZONEX IN 2 ZONEX POWER 24 ZONEX COMMON 23 D8125 D8125 D8128D D8128D D8129 D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 5 6 7 7 8 9 10 11 3 3 3 3 3 3 3 3 3 4 Figure 4 D9412G System Wiring Diagram 3 of 3 1 Up to eight supervised D9210Bs 2 Up to three supervised D9131As 3 Power limited supervised 4 Power limite...

Страница 26: ...T GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket D1640 16 5 V 40 VA 60 Hzr C900 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 1 2 3 4 5 8 D126 D1218 D126 D1218 D126 D1218 D126 D1218 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 14 10 7 13 10 10 10 16 11 12 6 15 9 10 7 10 RJ31X Figure 5 D7412G Syst...

Страница 27: ...2 0 3 0 VDC Short 0 0 1 3 VDC LOOP START GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket P105BL D125B D129 P105F 2 5 3 4 D130 1 Figure 6 D7412G System Wiring Diagram 2 of 3 1 Optional For 24 V applications use a UL Listed 24 VDC Power Supply with a D130 Relay Mod...

Страница 28: ...ONE LED RED ON WHEN COMMUNICATING OFF WHEN IDLE PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits LOOP START GND START GROUND START GROUND START Requires Relay Model D136 in Ground Start Socket D8125 D8128D D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 4 5 6 7 3 3 3 3 3 3 Figure 7 ...

Страница 29: ... local AHJ connect D113 Battery Lead Supervision Module D113 BAT 2 BAT 1 BAT 2 BAT 1 SUPV CHGR CHGR VAUX D126 or D1218 D126 or D1218 To Point Input To Battery Negative To Battery Positive To AUX P PROG CONN All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY ...

Страница 30: ...All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY A RELAY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminal...

Страница 31: ...AY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED RED ON WHEN COMMUNICATIN G OFF WHEN IDLE GRN PERIPHERAL DEVICE CONNECTIONS RED POWER YELLO...

Страница 32: ...urity Systems Inc 43700F 09 04 130 Perinton Parkway Fairport NY 14450 9199 USA Installation and D9412G D7412G D7212G Customer Service 800 538 5807 Technical Support 888 886 6189 Troubleshooting Ref Guide Page 32 of 32 ...

Отзывы: