2 | D323A Analog Photoelectric Smoke Detector Head
USA
NFPA
Complies with National Fire Protection
Association NFPA 72
Installation/Configuration Notes
Compatible Products
The following products are compatible with the D323A
Analog Smoke Detector Head:
Category
Product ID
Product Description
Control Panels
D8024
Analog FACP
D10024A
Analog FACP
Detector Bases
D321A
Analog detector base
D336A
Analog detector base
Modules
D9067
Polling circuit module
Programming
Products
D5070
Analog device programmer
Modular Construction
The D323A is part of a two‑piece modular design
photoelectric smoke detector assembly. Attach the D323A
to a D321A Analog Detector Base (6 in. [15 cm]) or a D336A
Analog Detector Base (4 in. [10 cm]) by inserting the
detector head into a groove on the base and turning the
head clockwise.
The base’s security locking tab prevents any unauthorized
head removal from the base.
Mounting
Smoke detectors are typically mounted on the ceiling.
However, if smoke detectors are mounted on a wall, they
must be at least 4 in. (10 cm), but no more than 12 in.
(30.5 cm), below the ceiling.
For UL Listing requirements, the spacing between detectors
should be no more than 30 ft (9 m).
Programming
The D323A’s address is set by programming an EEPROM
microchip located in the detector head. The D5070 Analog
Device Programmer is required for address setting.
Parts Included
Quant.
Component
1
Detector head
1
Dust cover
Technical Specifications
Environmental Considerations
Relative Humidity:
95% maximum, non‑condensing at +104°F
(+40°C)
Temperature (Operating):
+32°F to +120°F (0°C to +49°C)
Mechanical Properties
Color:
Ivory
Dimensions (diameter x D):
4 in. x 1.5 in. (10 cm x 3.8 cm)
Material:
Acrylonitrile‑chlorinated polyethy-
lene‑styrene terpolymer (ACS) plastic
Weight:
3.2 oz (91 g)
Power Requirements
Current (Alarm):
8 mA
Current (Polling):
0.022 mA ± 20%
Current (Standby):
0.39 mA
Voltage (Operating):
24 VDC nominal;
17 VDC to 41 VDC range
Ordering Information
D323A Analog Photoelectric Smoke
Detector Head
An addressable device used in the analog poll-
ing circuit of the Bosch Security Systems'
D8024 and D10024A Fire Alarm Control Pan-
els
D323A
Americas:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
www.boschsecurity.us
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
www.boschsecurity.com
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6258 5511
Fax: +65 6571 2698
www.boschsecurity.com
Represented by
© Bosch Security Systems Inc. 2010 | Data subject to change without notice
T1119598347 | Cur: en-US, V5, 4 Jul 2010