2 | D323A Analog Photoelectric Smoke Detector Head

USA

NFPA

Complies with National Fire Protection

Association NFPA 72

Installation/Configuration Notes

Compatible Products
The following products are compatible with the D323A
Analog Smoke Detector Head:

Category

Product ID

Product Description

Control Panels

D8024

Analog FACP

D10024A

Analog FACP

Detector Bases

D321A

Analog detector base

D336A

Analog detector base

Modules

D9067

Polling circuit module

Programming

Products

D5070

Analog device programmer

Modular Construction
The D323A is part of a two‑piece modular design
photoelectric smoke detector assembly. Attach the D323A
to a D321A Analog Detector Base (6 in. [15 cm]) or a D336A
Analog Detector Base (4 in. [10 cm]) by inserting the
detector head into a groove on the base and turning the
head clockwise.
The base’s security locking tab prevents any unauthorized
head removal from the base.
Mounting
Smoke detectors are typically mounted on the ceiling.
However, if smoke detectors are mounted on a wall, they
must be at least 4 in. (10 cm), but no more than 12 in.
(30.5 cm), below the ceiling.
For UL Listing requirements, the spacing between detectors
should be no more than 30 ft (9 m).
Programming
The D323A’s address is set by programming an EEPROM
microchip located in the detector head. The D5070 Analog
Device Programmer is required for address setting.

Parts Included

Quant.

Component

1

Detector head

1

Dust cover

Technical Specifications

Environmental Considerations

Relative Humidity:

95% maximum, non‑condensing at +104°F

(+40°C)

Temperature (Operating):

+32°F to +120°F (0°C to +49°C)

Mechanical Properties

Color:

Ivory

Dimensions (diameter x D):

4 in. x 1.5 in. (10 cm x 3.8 cm)

Material:

Acrylonitrile‑chlorinated polyethy-

lene‑styrene terpolymer (ACS) plastic

Weight:

3.2 oz (91 g)

Power Requirements

Current (Alarm):

8 mA

Current (Polling):

0.022 mA ± 20%

Current (Standby):

0.39 mA

Voltage (Operating):

24 VDC nominal;

17 VDC to 41 VDC range

Ordering Information

D323A Analog Photoelectric Smoke
Detector Head

An addressable device used in the analog poll-

ing circuit of the Bosch Security Systems'

D8024 and D10024A Fire Alarm Control Pan-

els

D323A

Americas:

Bosch Security Systems, Inc.

130 Perinton Parkway

Fairport, New York, 14450, USA

Phone: +1 800 289 0096

Fax: +1 585 223 9180

[email protected]

www.boschsecurity.us

Europe, Middle East, Africa:

Bosch Security Systems B.V.

P.O. Box 80002

5600 JB Eindhoven, The Netherlands

Phone: + 31 40 2577 284

Fax: +31 40 2577 330

[email protected]

www.boschsecurity.com

Asia-Pacific:

Robert Bosch (SEA) Pte Ltd, Security Systems

11 Bishan Street 21

Singapore 573943

Phone: +65 6258 5511

Fax: +65 6571 2698

[email protected]

www.boschsecurity.com

Represented by

© Bosch Security Systems Inc. 2010 | Data subject to change without notice

T1119598347 | Cur: en-US, V5, 4 Jul 2010

Отзывы: