Bosch D285 Скачать руководство пользователя страница 4

Bosch | 6/04 | 32029E

4

D285/D285TH 

| Installation Instructions |

4.0  Maintenance

 

Notify all concerned parties before and after 
fire alarm system maintenance or testing. 

 

At least once a year, clean the detector and base. Use a
vacuum or clean/dry compressed air, paying particular
attention to the screens. In dusty areas or areas of heavy
insect concentration, cleaning might be required more
often.

To clean the detectors:

1.

Remove the detector from the base. Clean the base
with a clean cloth and common window cleaner.

2. Remove the detector’s cover. Use a thin, flathead

screwdriver to pry the chassis from the cover.
Insert the screwdriver into the cover slots and pry
up (refer to Item 1 in Figure 2).

3. Gently pry the cover tab away from the chamber

cover and pull the chamber cover up and away from
the chamber (refer to Item 2 in Figure 3).

4. Using clean, dry compressed air or a vacuum,

remove any dust or debris from the chassis area.

5. Replace the chamber. Ensure the hole for the LED

(and thermistor) is properly aligned over the LED
(and thermistor). Place the chamber parallel to the
chassis and gently snap the locking tabs into place.

6. Replace the detector’s cover, carefully aligning the

LED holes and thermistor.

7.

Return the detector to its base.

 

After cleaning, test the detectors for proper 
calibration using one of the tests described 
in Sections 5.1 Visual Check, 5.2 Magnet 
Test, or 5.3 Voltage Measurement Test

 on 

page 5. 

 

 

Do not paint the detectors. Paint or other 
foreign matter covering the screens can 
prohibit or retard smoke from entering the 
detector. 

 

4.0   Maintenance

Figure 2:

Removing the Detector Base

1 - Cover slots (3)

2 - Detector chassis

3 - Cover

2

1

3

#1

Figure 3:

Removing the Detector’s Chamber Cover

#2

Содержание D285

Страница 1: ...D285 D285TH EN Installation Instructions Photoelectric Smoke Detectors ...

Страница 2: ... 57 C heat sensor requires base D285DH Detector only for D340 Series Duct Smoke Detectors D287 Base only two wire D292 Base only four wire D293A Base only four wire Form C auxiliary relay D293E Base only for power supervision four wire EOL relay Normally Open auxiliary relay D293S Base only four wire with sounder D275 EOL supervision module for four wire systems TP280 Trim Plate 6 in 16 2 cm diame...

Страница 3: ...its This determines if the problem is caused by the detector or the base c If a system alarm with no detector alarms is present remove all detectors and check the wiring at each base Pay close attention to the wiring of each EOL resistor and EOL module 3 When the system is free of alarms check each detector to ensure the red LED indicator is flashing approximately every 3 sec This verifies the det...

Страница 4: ...ull the chamber cover up and away from the chamber refer to Item 2 in Figure 3 4 Using clean dry compressed air or a vacuum remove any dust or debris from the chassis area 5 Replace the chamber Ensure the hole for the LED and thermistor is properly aligned over the LED and thermistor Place the chamber parallel to the chassis and gently snap the locking tabs into place 6 Replace the detector s cove...

Страница 5: ...on the head Observe the LED If the detector is within the factory marked calibration range it goes into alarm and the alarm LED latches ON If the detector is too sensitive the LED rapidly flashes six times once every 1 2 sec and the detector goes into alarm If the detector is not sensitive enough the LED flashes four times slowly once every 2 sec and the detector goes into alarm If the detector is...

Страница 6: ...Bosch 6 04 32029E 6 D285 D285TH Installation Instructions Notes ...

Страница 7: ...7 Bosch 6 04 32029E D285 D285TH Installation Instructions Notes ...

Страница 8: ...Bosch 130 Perinton Parkway Fairport NY 14450 9199 USA Customer Service 800 289 0096 Technical Support 888 886 6189 2004 Bosch 32029E ...

Отзывы: