background image

Bosch Security Systems | 12/03 | 74-07491-000-B

EN | 

4

D223TD 

| Installation Instructions | 2.0 Installation

7.

Connect the keypad wire to the control panel.

The maximum length for all wires connected to
D2212 Terminal 8 combined is 152 m (500 ft).
Route the data wire runs away from electrical,
telephone, and other data wiring.

Figure 3 shows a typical installation using one
D223TD Keypad. Use parallel connections for
additional keypads or expanders.

For more information, refer to the D2212 Installation
Guide 
(P/N: 74-07361-000).

8. Assign the D223TD to a device address.

Before you begin, make sure the control
panel’s standby pin is locked down to
prevent sending missing point reports.

To set the D223TD address:

a.

Set DIP Switch 1 to the 

ON

 position.

b. The display shows:

SET ADDRESS MODE

ADDRESS IS ##

c.

Enter the address (1 to 8) with a leading zero.
For example, 01 for Address 1.

Only use address numbers 1 to 8.

d. Return DIP Switch 1 to the 

OFF

 position.

When using more than one D223TD Keypad,
set one of the keypads to Address 1.

The control panel’s program affects the keypad’s
address. Choose the keypad address in the control
panel’s program. Then select 

Text Keypad

 for the

device type’s address.

For more information, see Address Configuration in
the D2212 Program Entry Guide (P/N: 74-07386-000).

When replacing a D223TD at Address 1, if the
system has custom text, preserve the custom text by:

a.

Copying the control panel’s program using a
D5200.

b. Attaching a new D223TD at Address 1.
c.

Reprogramming the control panel using the
copied program.

9. Disable the sounder.

Turn DIP Switch 3 to the 

OFF

 position

(see Figure 2).

The fire points need the trouble sounder. Disabling
the sounder with DIP Switch 3 stops the D223TD
from annunciating fire point trouble.

If this system has fire points installed,
contact the local authority having jurisdiction
(AHJ) to verify the code requirements for fire
trouble sounders before disabling the
D223TD sounder.

Enable the sounder for Underwriters
Laboratories, Inc. (UL) systems. For UL
installations, the sounder on at least one
keypad in the system must remain
connected.

10. Adjust the D223TD display.

After the D223TD is mounted, view the display
from the user’s perspective. If the display requires
adjustment for clarity, use the display adjustment
potentiometer (R50) in the lower right-hand corner
of the D223TD circuit board.

11. Replace the front cover.

a.

Align the top two tabs of the enclosure cover
with the top two tab slots in the enclosure
base.

b. Slide the top of the cover into the base.
c.

Gently push the bottom of the cover down on
the base until it snaps into place.

12. Adjust the keys.

Push each key on the keypad towards the top of the
enclosure making sure it fits

 wi

th the opening in the

top cover.

Figure 3:

Wiring the D223TD to the D2212

1 -   D223TD Keypad

4 -   Red wire

2 -   D2212 Control Panel

5 -   Green wire

3 -   Black wire

1

2

3

4

5

6

7

8

9

0

A

B

C

*

1

CLEAR

11

12

6

7

8

9

10

On

AL L  O N
SY S TE M   O K

3

4

5

2

Содержание D223TD

Страница 1: ...D223TD EN Installation Instructions Keypad ...

Страница 2: ... the D5300 Remote Control Account Manager II RAM II or Remote Programming Software RPS 1 1 Display The D223TD continuously displays the latest status conditions of the security system Once the program is received it takes 15 seconds for the new text to replace the old text When a series of events affecting the system occurs the D223TD displays each event by priority For example alarms display befo...

Страница 3: ...ne and other data wiring 3 Splice the connectors to the wires Connect the three wire cable to the control panel Use solder to splice the connectors to the wires Insulate all exposed splices with tape so they do not short to one another 4 Remove the front cover from the enclosure base Using a small flat bladed screwdriver gently push back the two bottom cover tabs As you push back the tabs lift the...

Страница 4: ...custom text by a Copying the control panel s program using a D5200 b Attaching a new D223TD at Address 1 c Reprogramming the control panel using the copied program 9 Disable the sounder Turn DIP Switch 3 to the OFF position see Figure 2 The fire points need the trouble sounder Disabling the sounder with DIP Switch 3 stops the D223TD from annunciating fire point trouble If this system has fire poin...

Страница 5: ...ry power supply Current Requirements Maximum 140 mA Normal 85 mA LCD on Standby 30 mA no keypad backlighting Enclosure Dimensions H x L x D 12 cm x 21 cm x 2 cm 4 56 in x 8 15 in x 816 in Color Off white Operating Temperature 0 C to 50 C 32 F to 122 F Non condensing Relative Humidity 5 to 85 at 30 C 86 F Keypad Wiring Three wire cable supplies data in common and positive voltage Display ON indicat...

Страница 6: ...Bosch Security Systems 12 03 74 07491 000 B EN 6 D223TD Installation Instructions Notes ...

Страница 7: ...EN 7 D223TD Installation Instructions Bosch Security Systems 12 03 74 07491 000 B Notes ...

Страница 8: ...Bosch Security Systems 130 Perinton Parkway Fairport NY 14450 9199 USA www boschsecurity us Customer Service 800 289 0096 Technical Support 888 886 6189 2003 Bosch Security Systems 74 07491 000 B ...