background image

CP156B Specifications

Part Number:

CP156B -  External 6x2 Metal Keypad With Smart Card Reader (IP67).

Operating Voltage:

10.0V D.C. - 14.5V D.C. @ 100mA Max.

Module Connection: 

(RS485 LAN)

Max total LAN length using multi strand security cable = 500m.  

Max total LAN length using 2 pair twisted shielded data cable (Belden 8723) = 1200m.   

See the control panel manual for complete wiring instructions.

Lock Output:

Relay 2Amp DC

Egress Input:

Low to trigger.  Can be disabled via software control.

Dimensions:

45mm(W), 23mm(D), 162mm(H). CM444B = 46mm(W), 12.5mm(D), 12mm H)

Environment:

-30˚ to 55˚C  RH 5 to 85% at 30˚C non-condensing.

Fixing Method:

The CP156B should be mounted on a sturdy vertical wall using fixtures appropriate for the wall 

construction type.

Warranty:

3 years from date of manufacture (return to base).

N12138

RoHS

In the interest of ongoing product development this 

document is subject to change without notice. 

CP156B

Installer Reference Guide

8

Bosch Security Systems    01/19    CP156BIRG  FTR1.1

1

ON

K E

2 3 4 5

Not Used

EGRESS

INPUT

N/O

BK - Black
RD - Red

WH - White

BL - Blue

YL  - Yellow & GY - Grey

GN - Green

RD - RED

BK - BLACK

WH - WHITE

BL - BLUE

= LAN +

= LAN -

= LAN A

= LAN B

BRN - BROWN

ORG - ORANGE

PPL - PURPLE

GN - GREEN

= RELAY NO

= RELAY COM

= RELAY NC

= EGRESS

YL - YELLOW

GY - GREY

= NOT USED

= NOT USED

Control Panel

Wiring Legend

CM720 or CM723 

Power Supply

(Battery backed up)

+    -

DOOR

LOCK

Egress 

Input

BACK EMF

DIODE

+

Exte

rna

l K

eyp

ad

ORG - Orange - COM

BRN - Prown - NO

LOCK RELAY 2Amp
PPL - Purple - NC

Door Control

Not Used

M

O

DUL

E  

LA

N

CONT

ROL  

PANEL

-

A

B

+

Keypad connection point. 

Only use the supplied cable to 

connect to this keypad.

Address Select Switch.  Keypads must be 

set to a unique address as per “Table 2: 

Keypad Address” on page 2.

All CP156B keypads are supplied from 

the factory set to Address 1.

You must power circle the panel or 

preform a LAN scan after connecting the 

CP156B for the system to initialise the 

keypad.

Figure 8: CP156B Connection Diagram

N12138

Connection Diagram

Содержание CP156B

Страница 1: ...CP156B External Metal Keypad with Smart Card Reader Security System Installer Reference Guide EN Security Systems ...

Страница 2: ...ach keypad fitted to the system must be assigned a unique address on the LAN The CP156B includes a DIP switch for quick address selection The following table shows the address setting for each keypad as well as the number of keypad devices each panels can support CP156B Keypad Compatibility Panels Supported Version Keypads Supported Solution 6000 2 25 Up to 16 Table 1 CP156B Compatibility CP156B E...

Страница 3: ...sing table 2 Note Each keypad on the system must have a unique address Step 4 Attach the connection cable to the keypad by plugging in the con nector Note the connector is polarised and will only plug in when correctly aligned Do not use excessive force Step 5 Make sure the cable grommet is fitted correctly to insure a correct water resistant seal Step 6 Carefully hook the keypad to the back plate...

Страница 4: ...ystem operation The Red Green indicators will show alarm or area sta tus The Blue indicator will show door status Figure 7 LED Indicators Keypad Operation The CP156B keypad can be configured to provide sys tem area control door access control or both depending on the installation requirements As there is no LCD display on the keypad feedback is provided via the red green and blue LED s and the key...

Страница 5: ... be assigned to the same door as the keypad If both alarm area and door control is required then you will need to assign a home area and a door to the keypad i Note The CP156B LED indicators will only display the status of the programmed home area You can not move between areas from this keypad If you require multiple area status visibility you should use a display keypad like the CP700B Keypad Al...

Страница 6: ...C door strikes the back EMF energy generated when the lock is released should be shunted with a reverse diode and is not always provided by the door strike manufacturer The Egress input Green Wire on the CP156B keypad al lows you to simplify the wiring required to implement an egress button on the inside of the door The egress input triggers the lock output on the keypad by operating the associate...

Страница 7: ...t incorporates both the EM and Smart Card formats with identical 40bit credential allowing the one token to be used across different technologies You may have a site that is running the dated EM for mat but now installing a new site with the high security Smart Card Format and want to use the same tokens across both sites PR301 Smart Card Token PR350 Smart Card PR370 Dual Smart Card Token PR365 Ad...

Страница 8: ...ct to change without notice CP156B Installer Reference Guide 8 Bosch Security Systems 01 19 CP156BIRG FTR1 1 1 ON K E 2 3 4 5 Not Used EGRESS INPUT N O BK Black RD Red WH White BL Blue YL Yellow GY Grey GN Green RD RED BK BLACK WH WHITE BL BLUE LAN LAN LAN A LAN B BRN BROWN ORG ORANGE PPL PURPLE GN GREEN RELAY NO RELAY COM RELAY NC EGRESS YL YELLOW GY GREY NOT USED NOT USED Control Panel Wiring Le...

Страница 9: ...CP156B Installer Reference Guide 9 Bosch Security Systems 01 19 CP156BIRG FTR1 1 This page left intentionally blank ...

Страница 10: ...CP156B Installer Reference Guide 10 Bosch Security Systems 01 19 CP156BIRG FTR1 1 This page left intentionally blank ...

Страница 11: ...CP156B Installer Reference Guide 11 Bosch Security Systems 01 19 CP156BIRG FTR1 1 This page left intentionally blank ...

Страница 12: ...Bosch Security Systems Level 2 21 Solent Circuit Baulkham Hills NSW 2153 Australia Phone 1300 026 724 www boshsecurity com au 2019 Bosch Security Systems CP156BIRG Issue FTR1 1 ...

Отзывы: