Conettix ITS-D6686-UL | Installation Guide | 2.0 Installation
4
Bosch Security Systems, Inc. | 10/12 | F01U274796-02
2.0
Installation
2.1
All Installations
Install the Conettix D6600 Communications
Receiver/Gateway according to NFPA 70, NFPA
72, and the local authority having jurisdiction
(AHJ).
The ITS-D6686-UL is suitable for Central Station
Protective Signaling when it is installed and used
in compliance with NFPA 72 and ANSI/NFPA 70.
Installation limits for digital alarm communicator
receivers (DACR) are under the jurisdiction of the
local AHJ.
The equipment between Ethernet Interface
Modules and the ITS-D6686-UL must be UL
Listed Information Technology Equipment (ITE).
To comply with UL, ensure the following
requirements are met:
•
Mount the ITS-D6686-UL, the ITE network
interface equipment, and the D6600 that it is
connected to, in a standard 19-in rack.
•
Connect the ITS-D6686-UL to an electrical
outlet located inside the same rack with the
D6686 and D6600.
•
Install the ITS-D6686-UL in the same rack as
the D6600 and within 6 m (20 ft) of the
D6600.
•
The Ethernet and RS-232 serial cables cannot
exceed 6 m (20 ft) in length.
•
Use an uninterrupted power supply (UPS) is
when the ITS-D6686-UL is used for UL Fire
(UL1481) Protective Signaling Systems.
•
Use the supplied transformer (Group
West/Part number - 48D-12-900).
2.2
Mounting the D6686
Mount the D6686 on a rail or other user-supplied
spot behind the D6600 that it will be connected
to. Refer to
Figure 3
.
2.3
Connecting the D6686
Connect the D6686 as follows:
•
Power cable to an available electrical outlet
•
Ethernet cable to network switch
•
RS-232 serial cable to Serial 1 port
Refer to the
D6600/D6100IPv6 Installation and
Operation Guide – Network Communication
section,
(P/N: 4998122704) for applications
using both serial ports.
Refer to
Figure 3
.
Figure 3: D6686 Connections
1– Power cable
2– Ethernet cable
3– RS-232 serial cable (Serial 1 port)
4– Serial 2 port (empty)
5 – Standard 19-in. mounting rack