Shutdown
45
Condens 7000 WP – 6721842519 (2022/03)
Table 23 Faults that are not shown on the display
Fault display: System pressure too low
If the system pressure in the heating system falls below the minimum
pressure that has been set, the display shows the message
LoPr => L0.X
bar
. The system pressure is too low.
▶ Fill the heating system.
If the system pressure in the heating system drops below 0.3 bar, the
display shows the message
LoPr
alternating with the operating
pressure. The heating system is then blocked.
▶ Fill the heating system.
12
Shutdown
12.1
Standard decommissioning
▶ Switch off the boiler via the on/off switch (
▶ Close gas isolator.
▶ Close the service valves.
12.2
Decommissioning when there is a risk of frost
If the boiler remains switched off.
▶ Set the pump overrun time to 24 hours (
▶ Make sure that a sufficient flow rate is possible at all radiators.
If the boiler is switched off:
▶ Switch off the boiler via the on/off switch (
▶ Drain the entire heating system.
▶ If installed, drain the entire potable water system.
13
Environmental protection and disposal
Environmental protection is a fundamental corporate strategy of the
Bosch Group.
The quality of our products, their economy and environmental safety are
all of equal importance to us and all environmental protection legislation
and regulations are strictly observed.
We use the best possible technology and materials for protecting the
environment taking account of economic considerations.
Packaging
Where packaging is concerned, we participate in country-specific
recycling processes that ensure optimum recycling.
All of our packaging materials are environmentally compatible and can be
recycled.
Used appliances
Used appliances contain valuable materials that can be recycled.
The various assemblies can be easily dismantled. Synthetic materials are
marked accordingly. Assemblies can therefore be sorted by composition
and passed on for recycling or disposal.
Old electrical and electronic appliances
This symbol means that the product must not be disposed
of with other waste, and instead must be taken to the waste
collection points for treatment, collection, recycling and
disposal.
The symbol is valid in countries where waste electrical and
electronic equipment regulations apply, e.g. "European Directive 2012/
19/EC on old electronic and electrical appliances". These regulations
define the framework for the return and recycling of old electronic
appliances that apply in each country.
As electronic devices may contain hazardous substances, it needs to be
recycled responsibly in order to minimize any potential harm to the
environment and human health. Furthermore, recycling of electronic
scrap helps preserve natural resources.
For additional information on the environmentally compatible disposal
of old electrical and electronic appliances, please contact the relevant
local authorities, your household waste disposal service or the retailer
where you purchased the product.
You can find more information here:
www.weee.bosch-thermotechnology.com/
14
Data Protection Notice
We,
Bosch Thermotechnology Ltd., Cotswold Way,
Warndon, Worcester WR4 9SW, United Kingdom
process product and installation information,
technical and connection data, communication data,
product registration and client history data to provide
Heat-up takes too long.
▶ Set the pump rate or pump characteristic map correctly and match to the maximum
output.
Flue gas values incorrect, CO content too high.
▶ Check the gas type.
▶ Check the gas supply pressure.
▶ Check the flue system, clean or repair as necessary.
▶ Check the gas/air ratio.
▶ Check the air/gas ratio control valve, replace if required.
Violent ignition, poor ignition.
▶ Check the ignition transformer with service function t01 for misfiring, replace if
required.
▶ Check the gas type.
▶ Check the gas supply pressure.
▶ Check the power supply.
▶ Check the electrodes with cable, replace if required.
▶ Check the flue system, clean or repair as necessary.
▶ Check the gas/air ratio.
▶ For natural gas: check the external gas flow monitor, replace if required.
▶ Check the burner, replace if required.
▶ Check the air/gas ratio control valve, replace if required.
No function, the display remains dark.
▶ Check the electrical wiring for damage.
▶ Replace defective cables.
▶ Check the fuse, replace if required.
Device faults
Remedy