Technical information
23
Compress 7001i AW – 6721835318 (2021/09)
9.2
Specifications – heat pump (three-phase current)
Table 19 Specifications – heat pump (three-phase current)
Unit
13 OR-T
17 OR-T
Air/water operation
Power output with A -10/W35
, 100% compressor speed
KW
9.97
12.30
Power output with A -7/W35
, rated output
KW
10.73
13.02
COP with A -7/W35
2.74
2.55
Modulation range with A -7/W35
4.0-10.7
4.0-13.0
Power output with A +2/W35
1)
, 100% compressor speed
1) Performance data in accordance with EN 14511
KW
11.71
14.37
Modulation range with A +2/W35
5-12
5.5-14
Power output with A +7/W35
KW
5.18
5.63
COP with A +7/W35
, partial load
5.00
4.87
Power output with A +2/W35
KW
7.00
7.86
COP with A +2/W35
, partial load
3.64
4.04
Cooling capacity with A 35/W7
KW
8.86
9.69
EER with A 35/W7
2.72
2.68
Cooling capacity with A 35/W18
KW
11.12
11.45
EER with A 35/W18
3.23
3.77
Electrical details
Power supply
400V 3N AC, 50Hz
400V 3N AC, 50Hz
Protection index
IP X4
IP X4
Fuse rating for supplying the heat pump directly via the building
connection
2)
2) Fuse class gL/C
A
13
13
Maximum power consumption
KW
7.2
7.2
Performance factor cos phi with maximum output
>0.97
>0.97
Rated power input of compressor with A -7/W35 rated output
KW
3.92
5.11
Performance factor cos phi with A7/W35
>0.97
>0.97
Heat pump soft start
Yes
Yes
Soft start type
Inverter
Inverter
Max. number of compressor starts
1/h
10
10
Starting current
<5
<5
Heat transfer medium
Minimum flow
l/s
0.62
0.81
Internal pressure reduction
kPa
15.8
22.9
Air and noise generation
Max. fan motor output (DC transformer)
W
280
280
Maximum air current
m³/h
7300
7300
Sound pressure level at a distance of 1 m, 35% compressor speed
dB(A)
45
45
Sound power
3)
3) Sound power level in accordance with EN 12102
dB(A)
53
53
Max. sound power
dB(A)
64
64
Max. sound power "quiet operation"
dB(A)
57
58
General details
Refrigerant
4)
4) GWP100 = 2088
R410A
R410A
Refrigerant charge
kg
3.3
4.0
CO
2
(e)
Tonne
6.89
8.35
Maximum temperature of flow, heat pump only
°C
62
62
Installation altitude above sea level
Up to 2000 m above sea level
Dimensions (W x H x D)
mm
1122x1695x545
1122x1695x545
Weight without walls and top cover
kg
154
165
Weight with walls and top cover
kg
182
193
Содержание Compress 7001i AW
Страница 1: ...6721835318 2021 09 GB Installation Manual Air to Water Heat Pump Compress 7001i AW 5 17 OR S T ...
Страница 30: ......
Страница 31: ......