P/N: CM710BIRG Rev 1.3 

Page  

  3

Copyright © 2012 

 

E&OE

Module Address Switches and Output Numbering

Table 2: and Table 3: list the module address settings and corresponding output numbers that apply when adding 
output expanders to the listed panels.  Each output expander module added to the Solution 16i will provide a maxi-
mum of 4 additional outputs.  

 

i

Note

  Only one CM710B can be assigned to each address.  All mod-

ules are supplied from the factory set to address 1.  You must 
power cycle the panel or perform a LAN scan whenever you 
change the module address.  The LAN must be in the unlocked 
state or the LAN scan will not find new modules.

 

Panel Output Assignments

The following tables list the output numbers which become available when adding output expander modules to the 
system.  

Solution 16i Panel

Module 

Number

Address Setting

Output  

Numbers

SW1 SW2 SW3 SW4

Control Panel

1 to 4

1 =

OFF OFF OFF OFF

5 to 8

1 x CM710B can be fitted to the Solution 16i panel. 

Table 2: CM710B  Address Configuration On Solution 16i Panel

Solution 144 and Solution E Panels

Module 

Number

Address Setting

Output  

Numbers

SW1 SW2 SW3 SW4

S

olution 144 P

anel

S

olution E P

anel

Control Panel

1 to 5

Virtual Outputs

6 to 8

1 =

OFF OFF OFF OFF

9 to 12

2 =

ON

OFF OFF OFF

13 to 16

3 =

OFF

ON

OFF OFF

17 to 20

4 =

ON

ON

OFF OFF

21 to 24

5 =

OFF OFF

ON

OFF

25 to 28

6 =

ON

OFF

ON

OFF

29 to 32

7 =

OFF

ON

ON

OFF

33 to 36

8 =

ON

ON

ON

OFF

37 to 40

9 =

OFF OFF OFF

ON

41 to 44

10 =

ON

OFF OFF

ON

45 to 48

11 =

OFF

ON

OFF

ON

49 to 52

12 =

ON

ON

OFF

ON

53 to 56

13 =

OFF OFF

ON

ON

57 to 60

14 =

ON

OFF

ON

ON

61 to 64

15 =

OFF

ON

ON

ON

65 to 68

16 =

ON

ON

ON

ON

69 to 72

Up to 16 x CM710B can be fitted to the Solution E panel. 

Up to 8 x CM710B can be fitted to the Solution 144 panel.

Table 3: CM710B  Address Configuration On Solution E and Solution 144 Panels

ON

Position

Figure 1: Address Switch Activation

Содержание CM710B

Страница 1: ...CM710B 4 Way Output Expander Module Security System Installer Reference Guide EN Security Systems ...

Страница 2: ...up A dedicated service keypad and tamper input are provided If the tamper input is not required you should fit the supplied shunt to the tamper input pins To assist with installation the module includes indicators to show module and individual output status at all times A four way dip switch is used to select the output expanders address The address setting determines the output numbers for each e...

Страница 3: ...s Setting Output Numbers SW1 SW2 SW3 SW4 Control Panel 1 to 4 1 OFF OFF OFF OFF 5 to 8 1 x CM710B can be fitted to the Solution 16i panel Table 2 CM710B Address Configuration On Solution 16i Panel Solution 144 and Solution E Panels Module Number Address Setting Output Numbers SW1 SW2 SW3 SW4 Solution 144 Panel Solution E Panel Control Panel 1 to 5 Virtual Outputs 6 to 8 1 OFF OFF OFF OFF 9 to 12 2...

Страница 4: ...00 002 000 N Of 1 10 Seconds 000 000 000 000 000 000 Output Options Off On Low Battery Y Y N Y N N Guest Control N N N N N N Reserved N N N N N N Monitor Overload Y Y Y Y N N Monitor Device Fail Y Y N Y N N Alarm On Device Fail N N N N N N Block If All On N N N N N N Show Status On Keypad N N N N N N Show Status On Keypad N N N N N N Table 4 Solution 144 and Solution E Output Defaults Zone Allocat...

Страница 5: ... 2 Ur 36 External Audible A 71 CLI Trigger CLI 11 Dialler Disabled P 37 Internal Audible A 72 GSM Signal Lost P 12 Output Device Missing P 38 Any Zone Alarm A 73 GPRS Failure P 13 Output Trouble Op 39 Fire Alarm A 74 Ethernet Fail P 14 Panel On Line P 40 Burglary Alarm A 75 Macro Ma 15 Incoming Call P 41 Silent Alarm A 16 System Trouble P 42 Duress Alarm A 17 Box Tamper Zn 43 Keypad Medical A 18 Z...

Страница 6: ...o a unique address via this switch Tamper Connection Fit shunt if tamper not required i Note When controlling inductive loads such as Door Strikes always install protection diodes as shown Note the Cathode or marked end of the diode connects to the positive voltage When using the outputs to switch power from an external power supply you must only connect the negative of the power supply to the neg...

Страница 7: ...he table below list the default values for all output parameters in the Solution 16i panel Outputs 1 to 4 are high current digital outputs Outputs 5 to 8 are only available if the optional output expander board CM710B is fitted Options marked N A Not Applicable Solution 16i Default Output Programming Programming Option Output 1 Output 2 Output 3 Output 4 Output 5 8 Output Name External Siren Strob...

Страница 8: ...Bosch Security Systems 25 Huntingwood Drive Huntingwood NSW 2148 Australia Phone 612 9672 1777 Facsimile 612 9672 1717 2012 Bosch Security Systems CM710BIRG Issue FTR1 3 ...

Отзывы: