8 | Specifications
Dimensions
2.9 in x 5.0 in x 0.6 in (73.5 mm x 127 mm x 15.25
mm)
Voltage (input)
12 VDC nominal
Current
Standby: 110 mA + reader current
Alarm: 110 mA + reader current
Alarm output
Form C relay (NC, COM, NO) at 12/24 V @ 2.0 A
Operating
temperature
0°C to +50°C (+32°F to +122°F)
Relative humidity
5% to 93% at +32°C (+90°F) non-condensing
Terminal wire size
18 AWG to 22 AWG (1.02 mm to 0.65 mm)
SDI2/SDI wiring
to B901 + Reader
with external power
supply
Maximum distance - wire size (unshielded wire only):
1000 ft (305 m) - 22 AWG (0.65 mm), 2500 ft (762 m)
- 18 AWG (1.02 mm)
SDI2/SDI wiring to
B901 + Reader from
control panel
175 ft (53 m) - 22 AWG (0.65 mm), 450 ft (137 m) -
18 AWG (1.02 mm)
Wiring distance from
B901 to Reader
200 ft (61 m) - 22 AWG (0.65 mm), 500 ft (152 m) -
18 AWG (1.02 mm) Reader dependant
Bosch compatible
control panels
B9512G/B9512G-E/B8512G/B8512G-E/B6512/
D9412GV4/D7412GV4/D9412GV3/D7412GV3/
D9412GV2/D7412GV2/D9412G/D7412G
(Refer to the control panel installation document for
the number of supported devices.)
Bosch compatible
readers and
accessories
ARD-AYH12 EM Prox Wall Mount
ARD-AYJ12 EM Prox Mullion
ARD-AYK12 EM Prox Mini Mullion
ARD-AYQ12 EM Prox Wall Mount Vandal Resistant
ARD-AYCE65B EM Prox or PIN Mullion
ARD-R10 HID iClass Mini Mullion
ARD-R40 HID iClass Wall Mount
D8223 HID Prox Wall Mount
D8224 HID Prox Mullion
D8224-SP HID Prox Switch Plate Mount
D8225 HID Prox Mini Mullion
D8229 PIN Reader
Bosch compatible
credentials
ACA-ATR13 EM Tokens*
ACD-ATR11ISO EM Cards*
ACD-ATR14CS EM Clamshell Cards
ACD-IC2K26-50 iClass Cards**
ACT-IC2K26-10 iClass Tokens**
D8236-10 HID Prox Cards***
D8236KF-10 HID Prox Tokens***
* EM cards work with EM readers, ** iClass cards work with iClass readers,
*** Prox cards work with Prox readers
Approved For
Level Comment
Destructive Attack
I
Line Security
IV
IP or cellular with encryption
Line Security
II
IP or cellular without encryption
Line Security
I
B430/PSTN
Endurance
IV
Send by Power
IV
7 | Certifications
Region Certification
USA
UL 294 - Access Control System Units
UL 365 - Police Station Connected Burglar Alarm Units and
Systems
UL 609 - Local Burglar Alarm Units and Systems
UL 864 - Control Units and Accessories for Fire Alarm Systems
UL 985 - Household Fire Warning System Units
UL 1023 - Household Burglar-Alarm System Units
UL 1076 - Proprietary Burglar Alarm Units and Systems
UL 1610 - Central Station Burglar Alarm Units
CSFM - California Office of The State Fire Marshal
FCC Part 15 Class B
CA
Canada CAN/ULC S303 - Local Burglar Alarm Units and Systems
CAN/ULC S304 - Signal Receiving Centre and Premise Alarm
Control Units
ULC-ORD C1023 - Household Burglar Alarm System Units
ULC-ORD C1076 - Proprietary Burglar Alarm Units and Systems
ULC 2016701-S1871E - Fire Alarm and Security Subassemblies
ICES-003 - Information Technology Equipment (ITE)
When the tamper switch is activated, the heartbeat LED stays OFF
for 3 sec before indicating the firmware version. The LED pulses the
major, minor, and micro digits of the firmware version, with a 1 sec
pause after each digit.
In the following example, the version 1.4.3 shows as LED flashes:
[3 sec pause]
*___****___***
[3 sec pause, then normal operation].
To show the firmware version using an LED flash pattern:
- If the optional tamper switch is installed:
With the enclosure door open, activate the tamper switch (push and
release the switch).
- If the optional tamper switch is NOT installed: Momentarily short
the T+ terminal.
Refer to
Figure 6.1
for an example of flash patterns.
6 | Show the firmware version
Figure 6.1: Firmware LED flash patterns
5 | LED descriptions
The module includes one blue Heartbeat LED, and one Reader
LED. The Heartbeat LED indicates that the module has power as
well as a module’s current state. The Reader LED indicates data
transmission. Refer to
Table 5.1
.
Flash Pattern
Function
Flashes once
every 1 sec
Normal state: Indicates normal operation
state. (blue)
ON Steady
LED trouble state: Module is not powered
(for OFF Steady only), or some other
trouble condition prohibits the module from
communicating with the control panel.
OFF Steady
Flashes rapidly
Card data is executing (yellow)
OFF Steady
No card data is being received
Table 5.1: LED descriptions
4 | Configuration
3.8 | Wire to door contact
ZN+ RT
E
COM REX
2
1
Callout ― Description
1 ― RTE device
2 ― B901 Access Control Module
Figure 3.7: Wiring the door contact
ZN+ R
TE
COM REX
3
1
2
Callout ― Description
1 ― Door Contact
2 ― 1k EOL
3 ― B901 Access Control Module
Figure 3.8: Wiring the RTE
NOTICE!
Firmware reprogramming on the B901 is not supported if
connected via the SDI bus. Updating the firmware is achieved
via the SDI2 connection only.
Wire the door contact
.
3.8.1 | Request to Enter (RTE)
Wire the Request to Enter (RTE) device. The strike is activated, and
the door point is shunted when RTE is momentarily shorted to COM.
The
Shunt only
option shunts the point when this input is momentarily
shorted. To activate the shunt but not the strike, program RTE Shunt
Only? as [YES].
3.8.2 | Request to Exit (REX)
After you wire the module, power up the system and configure the B901
using Remote Programming Software (RPS) to assign the module to
an assigned area. Whenever possible, be consistent when numbering
doors, areas, and keypads. For example, assign Door 1 to Area 1 and
keypad 1. Test for proper operation.
Figure 3.9: Wiring the REX
ZN+ R
TE
COM REX
1
2
Callout ― Description
1 ― REX device
2 ― B901 Access Control Module
Wire the Request to Exit (REX) device
.
The strike is activated, and the door point is shunted when REX is
momentarily shorted to COM. The
Shunt only
option shunts the point
when this input is momentarily shorted. To activate the shunt but not
the strike, program REX Shunt Only? as [YES].
NOTICE!
Do not use a Request to Exit device (REX) for emergency
exit applications. NFPA 101 requires that a UL Listed panic
device be used to provide direct power from the standby
power source. Check with your local Authority Having
Jurisdiction (AHJ) prior to installing your system.
en
Installation Guide
Access Control Interface Module
B901