26
en | AVENAR panel series
AVENAR panel
2022-07 | 5.0 | F.01U.378.910
System manual
Bosch Sicherheitssysteme GmbH
BIS
Figure 2.6:
Connection to BIS
For a multiple-building network, it is essential to clarify with the network administrator:
–
whether the network is designed for multiple-building connections (e.g. there must be no
technical interference due to differences in grounding potential)
–
whether the bus users are designed for this kind of network (e.g. sufficient bandwidth).
i
Notice!
For detaiIed information about the installation und configuration of the OPC server refer to
the FSM-5000-OPC server manual.
i
Notice!
EN 54
The connection of a building management system (e.g. BIS) via an Ethernet interface using an
OPC server or an FSI server is EN54 compliant if the EN54 relevant functions are performed
by the fire panel solely. Any EN54 relevant control or administration (e.g. control of
notification appliances or administration of switch-off) by the building management system
requires an individual EN54 certification of the overall system by a certification body.
2.9
Connection to a voice alarm system
The PRAESENSA, Praesideo, PAVIRO or Plena voice alarm system can be connected via a data
transmission line to the panel. This enables the panel to control voice alarm zones. The control
can be defined down to the individual detector level.
–
For connection to the PRAESENSA, Praesideo or PAVIRO systems the Ethernet interface
and IP protocols are used. The voice alarm system can be configured for up to 244 virtual
VAS triggers. You will find detailed information in the Networking Guide which is available
for download at www.boschsecurity.com.
–
For connection to a Plena system the RS232 interface on the IOS 0020 A or IOS 0232 A is
used. The Plena system can be configured for up to 120 virtual VAS triggers. You will find
detailed information in the Wiring Guide which can be found on the extranet.
The virtual VAS triggers are programmed using the FSP-5000-RPS programming software.