background image

6 720 608 030

Troubleshooting

19

6

Troubleshooting

6.1

Introduction

Many  of  the  questions  customers  ask  regarding
operation of this unit can be answered by following the
troubleshooting steps as outlined below. Visit our web
site  at  www.boschhotwater.com  for  more  detailed
troubleshooting.  For  best  results,  perform  each  step
before proceeding to the next. The suggested solutions
may require that the cover be taken off. (See chapter

3.4).

6.2

Pilot does not light

1.  Verify  gas  supply  is  on  at  Natural  Gas  meter  or
Propane Tank.  Make sure all manual gas shut off valves
are in the open position. Have licensed gas technician
confirm  adequate  gas  pressure  at  the  inlet  tap
(chapter 3.9). If gas is not present, verify manufacturer
supplied Maxitrol regulator is in the upright position. The
arrow on the back of the regulator should point in the
same direction as gas flow.
2. If the unit was just installed or the gas lines have been
worked on, there may be air in the gas line. Centered in
the sparking position, hold down the gas control slide
button  while  hitting  the  pilot  igniter  button  every  few
seconds. It may take several minutes to bleed air out of
the gas line.
3. Verify a spark is being thrown at pilot area while gas
control  slide  button,  centered  in  the  single  flame
position, is being firmly depressed. Repeatedly push in
pilot  igniter  button  to  light  the  pilot.  If  no  spark  is
present, verify proper wire connection to the electrode.
4. Pilot assembly may be blocked. Clean or replace the
pilot orifice (chapter 5.3).

6.3

Pilot lights, but goes out when 

button released

1.  When  lighting  pilot  ensure  the  gas  control  slide
button is fully depressed and held down for at least 20
seconds after pilot is lit.
2. Verify gas type indicated in rating sticker located on
right hand side of cover, coincides with the gas type you
are using. NG is a natural gas unit and LP is for liquid
propane.
3. If using a power vent, check the safety spillage switch
reset button (the safety spillage switch is wired through
the  water  heater's  thermocouple  circuit).  The  spill
switch should be located at top of water heater close to
draft  diverter  (Consult  manual  that  came  with
powervent).
4. Check all connections of the pilot safety circuit.  The
pilot safety circuit consists of a thermocouple, overheat
sensor  (ECO),  flue  gas  sensor,  safety  spillage
switch(models  with  Powervents  only)  and  the

electromagnet (See parts diagram for locations). Clean
sensor connections with light sandpaper if corrosion is
evident. The electromagnet connection is 5mm nut from
the thermocouple which screws into a larger 17mm nut.
Tighten both nuts snugly but do not over tighten.
5.  Pilot  flame  should  be  blue in  color  and  completely
engulfing  the  tip  of  the  thermocouple.  If  not,  have  a
licensed  gas  technician  verify  gas  pressure  is  in
accordance 

with 

manufacturer's 

specifications

(chapter 3.9)  and  clean  or  replace  the  pilot  orifice
(chapter 5.3).
6.  Have  a  licensed  gas  technician  verify  the  proper
operation  of  the  thermocouple  by  measuring  the
millivoltage from the thermocouple lead to ground. The
proper  reading  should  be  24mVDC  or  greater.  If  the
reading  is  lower,  the  thermocouple  may  be  defective.
Call Bosch Water Heating for further instruction.

6.4

Pilot goes out during or after hot 

water use

1.  Pilot  outage  during  use  typically  results  from  the
unit's safety overheat/high limit sensors interrupting the
pilot  circuit.  The  GWH  1600  P  does  not  have  a
thermostat.  If  inlet  water  is  preheated,  the  unit  will
overheat, stopping the flow of gas. Plumb inlet with a
cold water line only.
2. Failure to vent properly by reducing pipe diameter,
improper  use  of  elbows  or  not  meeting  required  vent
length  are  common  causes  that  deactivate  the  pilot
safety  circuit.  Confirm  venting  is  in  accordance  with
manufacturer's specifications (see chapter 3.7).
3. Confirm the combustion air requirements are being
met  in  accordance  with  manufacturer's  specifications
(see  chapter 3.6).  Proper  venting  and  combustion  air
will ensure a proper draft.
4. Confirm that the burners in the water heater go off
immediately  when  the  hot  water  is  turned  off.  If  they
remain  on  or  shut  down  slowly,  then  the  overheat
sensor (ECO) will interrupt the pilot circuit and shut off
all gas to the heater. The water valve assembly, which
actuates the burners, may be dirty and require periodic
maintenance  (every  2  -  5  years  depending  on  water
quality and use) (see chapter 5.2).
5. Check all connections of the pilot safety circuit. The
pilot safety circuit consists of a thermocouple, overheat
sensor  (ECO),  flue  gas  sensor,  safety  spillage
switch(models  with  Powervents  only)  and  the
electromagnet (See parts diagram for locations). Clean
sensor connections with light sandpaper if corrosion is
evident. The electromagnet connection is 5mm nut from
the thermocouple which screws into a larger 17mm nut.
Tighten both nuts snugly but do not over tighten.

Содержание AquaStar GWH 1600 P LP

Страница 1: ... For assistance or additional information consult a qualified installer service agency or the gas supplier In the Commonwealth of Massachusettes the installation must be performed by a licensed plumber or gas fitter Upon completion of the installation these instructions should be handed to the user of the appliance for future reference What to do if you smell gas Open windows Close gas valve Do no...

Страница 2: ...n burners 18 5 5 Vent assembly 18 5 6 Mineral scale build up 18 6 Troubleshooting 19 6 1 Introduction 19 6 2 Pilot does not light 19 6 3 Pilot lights but goes out when button released 19 6 4 Pilot goes out during or after hot water use 19 6 5 Burners do not light with water flow 20 6 6 Hot water temperature fluctuates at tap 20 6 7 Water is too hot 21 6 8 Water is not hot enough 21 6 9 Burners ign...

Страница 3: ...ter 3 8 Venting Natural Draft Vent diameter inches 5 Minimum height feet 6 with no elbows Vertical termination Sidewall termination only with AQ4 power vent kit Water Hot water connection inches NPT Cold water connection inches NPT Water valve material Polymer PPS Polypropylene Sulfid Minimum water flow 0 5 gallon minute 1 9 l m Minimum recommended water pressure 30 PSI 2 07 bar Connections Bottom...

Страница 4: ...SI Z223 1 NFPA 54 In Canada The Installation should conform with CGA B149 1 2 INSTALLATION CODES and or local installation codes 2 Carefully plan where you install the heater Proper clearances must be followed 3 The appliance must be isolated from the gas supply piping system by closing its individual manual gas shutoff valve not supplied with heater during any pressure testing at pressures in exc...

Страница 5: ...le for fixing to wall 38 Exhaust pipe to connector 39 Draft diverter with flue gas monitor 40 Gas valve 49 Observation window 102 Piezo Fig 4 Minimum clearances Model GWH 1600 TOP A 12 inches 306 mm FRONT B 4 inches 100 mm BACK 0 inches SIDES 4 inches 100 mm BOTTOM C 12 inches 306 mm Dimensions inches mm GWH 1600 P A 16 73 425 B 25 75 655 C 13 15 334 D 5 11 130 E 21 25 540 F 2 55 65 G 1 18 30 H 3 ...

Страница 6: ...r is noncombustible For installations in an alcove or closet maintain the minimum clearances to combustible and non combustible materials listed below See also Fig 4 A Top 12 inches 306 mm B Front 4 inches 100 mm C Back 0 inches D Sides 4 inches 100 mm E Bottom 12 inches 306 mm Warning The water in this water heater is cold and always remains cold except for the times that hot water is being used ...

Страница 7: ...ecommended that support board s either 1x4 s or 1 2 minimum plywood first be attached across a pair of studs and then the heater should be attached to the support boards see Fig 7 B Secure the two included L shaped hooks to wall studs or support board 13 1 4 apart See Fig 7 B Hang heater on two L shaped hooks See Fig 8 Fig 6 Remove front cover Fig 7 Support board Fig 8 Secure heater to wall Warnin...

Страница 8: ... rating of all appliances installed in the space That would be 5850 cubic feet for the AquaStar GWH 1600 P alone b Installations in structures that have been tightly constructed air infiltration rate of 0 40 ACH or less must be provided for combustion air per the National Fuel Gas Code Consult a HVAC specialist if your air infiltration rate is questionable Appliances located in confined spaces The...

Страница 9: ... must be secured to each other with sheet metal screws and be properly supported Horizontal runs Any gas vent section that is greater than 45 degrees from the vertical is considered horizontal Horizontal sections must slope upwards at least inch for every foot of its horizontal length and be properly supported Keep the horizontal section short and avoid too many elbows The maximum horizontal run a...

Страница 10: ...ipe check local codes for clarification The lining material must be listed for use only with naturally drafting draft hood equipped gas appliances Follow manufactures instructions for installation of listed lining material You may not vent any other fuel burning appliances into any free space remaining in the chimney The minimum vertical gas vent length within the masonry chimney should be no less...

Страница 11: ...IGH ALTITUDE INSTALLATION The pressure regulator provided with the heater is adjusted to deliver the proper gas pressure as indicated on the rating plate and in the manual for altitude up to 2000 feet 660 meters above sea level On appliances being installed above 2000 ft 660 meters elevation the inlet gas pressure should be set at installation to the value shown below Note The gas pressures specif...

Страница 12: ...ure Drop of 0 5 Inch Water Column EHD Equivalent Hydraulic Diameter The greater the value of EHD the greater the gas capacity of the tubing Tube size inches EHD 10 20 30 40 50 60 1 2 18 EHD 82 58 47 41 37 34 3 4 23 EHD 161 116 96 83 75 68 1 30 EHD 330 231 188 162 144 131 1 1 4 37 EHD 639 456 374 325 292 267 Length of Flexible Corrugated Stainless Steel Tubing CSST Feet Tube size inches EHD 10 20 3...

Страница 13: ...y to or beneath the water connections or damage can occur to the internal water valve from heating of the pipe Plastics or other PEX type plumbing line materials are not recommended for connecting directly to the water heater Keep water inlet and outlet pipes to no less than 12 7mm diameter to allow the full flow capacity It is recommended that all water piping below the heater be properly insulat...

Страница 14: ...uctions exactly B What to do if you smell gas WHAT TO DO IF YOU SMELL GAS B Close gas valve Open windows B Do not try to light any appliance B Do not touch any electric switch do not use any phone in your building B Immediately call your gas supplier from a neighbors phone Follow the gas supplier s instructions B If you cannot reach your gas supplier call the fire department C Use only your hand t...

Страница 15: ...n the gas valve button is released the pilot should continue to burn If the gas valve button does not pop out when released stop and immediately call your service technician or gas supplier If pilot does not stay lit repeat all steps If pilot will not stay lit after several tries slide the gas valve button all the way to the left and call service technician or gas supplier B The heater will now fi...

Страница 16: ...ctivation rate Gas control slide button The gas control slide button adjusts temperature by adjusting how much gas is allowed to flow to the burners As the slide is adjusted to the left the output temperature will lower with the lowest setting being the small flame position Fig 24 The hottest position is the highest flame position all the way to the right Fig 25 4 5 Draining water from heater If t...

Страница 17: ...ter valve Loosen the two set screws at the bottom of the water valve where it connects to the gas valve If the set screws are seized STOP and call Bosch tech support before proceeding Forcing and snapping seized set screws may cause irrevocable damage to the water valve and gas valve assemblies Remove the water valve by pulling it to the right Separate the two halves of the water valve by removing...

Страница 18: ...ain water from the unit s heat exchanger by disconnecting inlet and outlet water connections 5 Connect the line A from the outlet of the circulating pump installer supplied to the inlet water fitting on the water heater 6 Using another line B connect to the water outlet fitting on the water heater Route the other end of this line into a descaling reservoir 7 Using a 3rd line C from the descaling r...

Страница 19: ...itch models with Powervents only and the electromagnet See parts diagram for locations Clean sensor connections with light sandpaper if corrosion is evident The electromagnet connection is 5mm nut from the thermocouple which screws into a larger 17mm nut Tighten both nuts snugly but do not over tighten 5 Pilot flame should be blue in color and completely engulfing the tip of the thermocouple If no...

Страница 20: ...be added with it in order to attain a useable hot water temperature The addition of too much cold will overpower and slow the flow within the tankless water heater decreasing it below activation point which shuts off the burners The end result is nothing but cold water coming out of the outlet Reduce the need for cold water mix by setting the gas slide control button towards the single flame posit...

Страница 21: ... service person for help in correcting a plumbing crossover 5 Inspect the water path outside of the heater for obstructions Make sure all outlets i e showerheads faucet aerators and whole house filters are clear of debris Also the water heater s inlet filter screen should be inspected and cleaned see chapter 5 2 6 The water valve may be dirty prohibiting it from fully opening the gas valve This pa...

Страница 22: ...ressure may be inadequate resulting in improper combustion Ensure gas pressure is in accordance with manufacturer s specifications see chapter 3 6 A gas pressure reading is needed to proceed further Contact your original installer or a licensed gas technician to obtain this reading 3 For proper combustion at high elevations the inlet gas pressure should be set at installation to the value shown in...

Страница 23: ...you want This way you have the precise water temperature needed mixing cold water to regulate temperature will increase the water temperature with consequent waste of water For increased safety shut off the appliance from the main water supply if your are staying away from home for a considerable time At below freezing temperatures disconnect the plumbing connections to the heater and allow the he...

Страница 24: ...8 Interior components and diagram parts list 8 1 Interior components Fig 28 Functional scheme 4 Heat exchanger 5 Burner 10 Temperature adjustment selector 11 Water valve 20 Gas connection 22 Flexible hot outlet 26 Gas control slide 30 Pilot gas tubing 102 Piezo ...

Страница 25: ...diagram parts list 25 8 2 Components diagram Fig 29 Components Diagram 50 49 32 48 46 45 43 28 29 30 31 25 17 18 19 20 21 23 26 24 27 33 34 35 13 36 37 22 38 39 40 41 42 44 47 8 9 11 12 13 14 15 16 10 6 4 5 51 52 1 2 3 7 6720608124 10 1 JF ...

Страница 26: ...00 245 0 22 Poppet valve head 2 NG 8 708 500 358 0 23 Electromagnet 8 707 201 028 0 24 Sealing screw 8 703 305 283 0 25 Valve operation housing 8 708 008 069 0 26 Guide plate 8 701 000 387 0 27 Gas pressure regulator LP 8 707 406 083 0 27 Gas pressure regulator NG 8 707 406 084 0 28 Water valve 8 707 006 344 0 29 Watervalve pushrod 10x 8 703 204 051 0 30 Diaphragm L 8 700 503 084 0 31 Inlet water ...

Страница 27: ...lying the replacement part s BBTNA will provide ground service delivery for these parts Expedited or upgraded shipping will be charged to the customer Service Labor Costs This warranty does not cover any labor costs associated with service removal or re installation of part s All such costs must be borne by the Purchaser Additionally this warranty does not cover any labor costs associated with ser...

Страница 28: ...re __________ Installing Company _____________________________________________ Installer name _____________________________________________ Address _____________________________________________ Phone _____________________________________________ See Chapter 3 8 and gas pressure table to be filled out by installer Installation manual should be left with the owner after the installation is tested an...

Отзывы: