Bosch AMC2 Series Скачать руководство пользователя страница 2

3 = Card reader
4 = Communication and power supply
5 = AMC2 xxx-EXT
In the default configuration, the connection to the
AMC2 is established via the RS485 interface.

Installation/configuration notes

Up to three extension boards can be connected to one
AMC2 controller; this provides a maximum of 56 input
and output signals for configuration with the AMC2
signals.
For a system configuration the AMC2 16I-16O-EXT,
AMC2 16I-EXT, and AMC2 8I-8O-EXT can also be used
in combination, e.g. two AMC2 16I-16O-EXTs and one
AMC2 8I-8O-EXT – but the maximum number of
modules that can be connected is also restricted to
three per AMC2 controller.

Notice
Systems with Access Personal Edition Software
can only connect one I/O-Extension to an AMC2
Controller.

An AMC2 16I-16O-EXT can only provide signals for the
entrances of the AMC2 controller to which it is
connected. It is not possible to transmit to another
AMC2.
Configuration examples:

Solid lines: Power supply
Dotted lines: Data lines

1. AMC2 with power supply.
2. Power and data are supplied to the AMC2 xxx-EXT via

the AMC2.

3. The AMC2 xxx-EXT with its own power supply

receives data from the AMC2.

4. The first AMC2 xxx-EXT is supplied by the AMC2 - the

second has its own power supply and a connection to
the third. All AMC2 xxx-EXTs receive their data from
the AMC2.

Power supply

An external power supply (10 to 30 V DC) for the
AMC2 is connected to the first (positive) and third pin
(negative).
When using an uninterruptible power supply (UPS),
the relevant UPS output relay is connected to the pins

• 4 and 7 for alternating current (AC)
• 5 and 7 for the battery
• 6 and 7 for direct current (DC)

Otherwise, these pins will short-circuit.

Voltage equalization - grounding

• Different grounds can be balanced via jumpers with

protective ground.

• A line (shielding, potential equalization) with

protective ground must only be connected in one
place.

• For further instructions, please see the operating

manual.

2 | AMC2 - Input/Output Extension Boards

Содержание AMC2 Series

Страница 1: ...gnals The relay outputs can be used to activate locking mechanisms for example If there are not enough contacts available on the AMC2 to transfer the necessary signals up to three AMC2 xI xO EXT units can be connected to provide additional inputs and outputs Notice Systems with Access Personal Edition Software can only connect one I O Extension to an AMC2 Controller The electronics are located in ...

Страница 2: ...nsmit to another AMC2 Configuration examples Solid lines Power supply Dotted lines Data lines 1 AMC2 with power supply 2 Power and data are supplied to the AMC2 xxx EXT via the AMC2 3 The AMC2 xxx EXT with its own power supply receives data from the AMC2 4 The first AMC2 xxx EXT is supplied by the AMC2 the second has its own power supply and a connection to the third All AMC2 xxx EXTs receive thei...

Страница 3: ...Hardware 16 or 8 or null relay outputs with ohm load max switching voltage 30 V DC max switching current 1 25 A 16 or 8 analog inputs Tamper switch Temperature 0 C to 45 C 32 F to 113 F Power supply 10 or 30 V DC max 60 VA Available for external devices 55 VA or via the AMC2 Protection class IP 30 Housing Base PPO UL 94 V 0 Upper Polycarbonate UL 94 V 0 Color White Dimensions WxHxD 232 x 90 x 46 m...

Страница 4: ... com Robert Bosch SEA Pte Ltd Security Systems 11 Bishan Street 21 Singapore 573943 Phone 65 6571 2808 Fax 65 6571 2699 apr securitysystems bosch com www boschsecurity asia Bosch Shanghai Security Systems Ltd 201 Building No 333 Fuquan Road North IBP Changning District Shanghai 200335 China Phone 86 21 22181111 Fax 86 21 22182398 www boschsecurity com cn Robert Bosch Ltda Security Systems Division...