16
|
Commissioning
AGS10-2, AGS10E-2, AGS20-2, AGS50-2
6 720 811 270 (2015/04)
6.3.2
Checking the flow rate
▶ Refer to Tab. 13 for the required flow rate (at 30-40 °C in the return).
▶ Check the flow rate in the sight glass of the flow limiter (
Fig. 27[3]).
6.3.3
Setting the flow rate
It may be necessary to reduce the flow rate for solar systems with up to
4 flat plate collectors (or 3 evacuated tube collectors).
▶ Set the speed to 100 % on the solar controller (
controller
instructions: "Function test").
If the
maximum flow rate
(
▶ Reduce the flow rate at the flow limiter [2] until the flow rate drops
below the maximum.
After commissioning
The viscosity of the heat transfer fluid makes air bubbles substantially
more resilient than those in pure water.
▶ After several hours of solar pump operation, vent the solar system via
the air separator in the solar pump station [4] and (if installed) the air
vent on the roof.
Fig. 27
[1]
Gravity brake ready for operation
[2]
Adjusting screw on the flow limiter, depending on the type
[3]
Read-off edge for the flow rate, depending on the type
[4]
Ventilation at the air separator
If the pre-set flow rate is not reached at the pump's
highest speed stage:
▶ Check maximum permitted pipe lengths and sizing
(
Chapter 4.1).
▶ If necessary, install a more powerful solar pump.
Quantity Flat plate l/min
1)
1) Nominal flow rate per collector: 50 l/h
Evacuated tube l/min
2)
2) Nominal flow rate per collector: 30 l/h
1
1
0.5-0.6
2
1.5-2
1-1.2
3
2.5-3
1.4-1.8
4
3-4
1.9-2.4
5
4-5
2.4-3.0
6
5-6
2.9-3.6
7
5.5-7
3.3-4.2
8
6.5-8
3.8-4.8
9
7.5-9
4.3-5.4
10
8-10
4.8-6.0
11
9-11
5.2-6.6
12
10-12
5.7-7.2
13
10.5-13
6.2-7.8
14
11.5-14
6.7-8.4
15
12.5-15
7.1-9.0
16
13-16
7.6-9.6
17
14-17
8.1-10.2
18
15-18
8.6-10.8
19
15.5-19
9.0-11.4
20
16.5-20
9.5-12.0
Table 13 Maximum flow rate at 30 - 40 °C in the return depending on
collector version and number of collectors
Low energy pumps do not require a step switch as they
are modulated using a control signal.
Quantity
Flat plate l/min
Evacuated tube l/min
1 2.5
--
2 5
5
3 7.5
7.5
4 10
10
Table 14 Flow rate (maximum flow rate) at 30 - 40 °C in the return
depending on collector version and number of collectors
0,5
7 6 5 4 3 2
1
L/min
7 6 5 4
1
0,5
3
2
6720801165.19-2.ST
1
20
0
40
60
°C 80
100
120
20
0
40
60
°C 80
100
120
S
E
3
2
4
Содержание AGS10-2
Страница 20: ...20 Commissioning inspection and maintenance reports AGS10 2 AGS10E 2 AGS20 2 AGS50 2 6 720 811 270 2015 04 ...
Страница 25: ... 25 6 720 811 270 2015 04 AGS10 2 AGS10E 2 AGS20 2 AGS50 2 Notes ...
Страница 26: ...26 AGS10 2 AGS10E 2 AGS20 2 AGS50 2 6 720 811 270 2015 04 Notes ...
Страница 27: ... 27 6 720 811 270 2015 04 AGS10 2 AGS10E 2 AGS20 2 AGS50 2 Notes ...
Страница 28: ......