background image

8  |

  

Bosch 2H/2C/Hum Touch-Technology Thermostat

                                                                

Installation, Operation & Application Manual

09.2016 

|

 Bosch Thermotechnology Corp.

Data subject to change

5     System setup and con

fi

 guration

5.1     Connection to the UPM

The UPM’s ALARM COM terminal should be connected to R on the UPM board 
(refer to unit manual for more information), and the ALARM OUT terminal should 
be connected to the A terminal on the thermostat. The UPM must be confi gured as 
described in Section 5.2.

5.2     Con

fi

 guration of the UPM

The ALARM DIP switch on the UPM has to be set to the ON position (“PULSE”). 
Simply push the right side of this switch, so it is down on the right side and up on the 
left side.

OUTCOM

ALR

DISPLAY

4
3
2
1

LOCKOUT

RESET

ALARM

TEST

4
R

CONT

YES

2
Y

PULSE

NO

UPM

A

RH

RC

C

Y1
W/O/B
G
W2
Y2
AUX

Thermostat Back Plate

Figure 3

5.3     Output chart

The thermostat is confi gurable for all systems. The confi guration directly aff ects the 
outputs. Use the output chart to correctly confi gure and wire the thermostat to your 
system.

Description

1st Cool

2nd

 

Cool

1st  Heat

2nd

 

 Heat

Heat/Cool

Y1, G

YI, Y2, G

W1, G*

W1, W2, G*

Heat Pump 
(one compressor)

Y1, G, O

Y1, G, O

Y1, G, B

Y1, W2, 

G, B

Heat Pump
(two compressors)

Y1, G, O

Y1, Y2, 

G, O

Y1, G, B

Y1, Y2, 

G, B

Emergency Heat 
(heat pump only)

N/A

N/A

W2, G

N/A

Table 2 

*  G not on for gas/oil systems

5.4     Humidity output chart

(De)humidifi cation Setting

With Humidity Control Demand

No

N/A

Humidifi cation
Only

Heat

W

Heat-Fan

W and/or G

Dehumidifi cation
Only

Cool-No

G only

Cool-Fan

Y and/or G

Table 3 

 

  When in dehumidifi cation mode and EAC is set to Cool-2, Y2 will energize 

to extend cooling cycle. See Confi guration menu section

5.5     Con

fi

 guration and thermostat lock

During Confi guration Mode, certain settings are protected by a numeric code access 
screen to prevent unintentional changes that could potentially damage the system or 
create a dangerous condition. 

Whenever changes are attempted to one of the critical settings, the unlock code 
screen will appear: 

The unlock code for these critical settings can be found during the power-up 
sequence. 

The large number (indicated by “98” in the diagram) is the code that will unlock 
the desired confi guration setting. The smaller numbers (indicated by “93” and 
“82” in the diagram) are codes used to lock and unlock your thermostat to prevent 
tampering. 

To view the default codes for your thermostat, remove the thermostat from the 
sub base and, if using batteries, remove one battery for 10 seconds. Replacing the 
batteries or reinstalling thermostat will cause the codes to display for approximately 
5 seconds.

 

 

 

 

 

Write your 

codes here

Thermostat lock code

Figure 4 

Содержание 8-733-944-325

Страница 1: ...Bosch Programmable Thermostat 2H 2C Hum Touch Technology Thermostat Installation Operation Application Manual ...

Страница 2: ...2 Bosch 2H 2C Hum Touch Technology Thermostat Installation Operation Application Manual 09 2016 Bosch Thermotechnology Corp Data subject to change ...

Страница 3: ...ermostat 6 4 Wiring diagram 7 4 1 Terminal designator descriptions 7 5 System setup and configuration 8 5 1 Connection to the UPM 8 5 2 Configuration of the UPM 8 5 3 Output chart 8 5 4 Humidity output chart 8 5 5 Locking unlocking thermostat 9 5 6 Changing the lock code 9 5 7 Configuration mode 9 5 8 Configuration mode settings 9 6 Mode of operation 14 6 1 Icon functions 14 6 2 Operating modes 15...

Страница 4: ...where there is no risk to people or property 1 2 Safety Please read before proceeding WARNING Always turn off power at the main power supply before installing cleaning or removing thermostat Read this manual carefully before installing or operating your new thermostat Make sure to save this manual for future reference WARNING This thermostat is for 24 VAC applications only do not use on voltages o...

Страница 5: ...tat Remote Sensor Compatible Ideally Suited for Residential New Construction Replacement Light Commercial Service Alarm Fault Detection and History 2 3 Package contents tools required Package includes Thermostat base Wiring labels Screws and wall anchors 2 AA Alkaline batteries Installation Operation and Application Manual Tools required for installation Drill with 3 16 bit Hammer Screwdriver 2 4 ...

Страница 6: ...ling 3 3 Installing thermostat DANGER ELECTRICAL SHOCK HAZARD Turn off power at the main service panel by removing the fuse or switching the appropriate circuit breaker to OFF position before removing the existing thermostat CAUTION Thermostat installation must conform to local and national building and electrical codes and ordinances Mount the thermostat about five feet above the floor Do not mount...

Страница 7: ... jumper between RH and RC is required Thermostat is powered between RH C 4 1 Terminal designator descriptions A Alarm display 24 VACinput switched from RH RC RH 24 VAC hot C 24 VAC common Y1 1st stage cool 1st stage heat for heat pumps Y2 2nd stage cool for 2 stage or 2 compressor systems 2nd stage heat for 2 stage or 2 compressor heat pump systems G Fan W1 O B Configurable W1 1st stage heat for n...

Страница 8: ...B Y1 Y2 G B Emergency Heat heat pump only N A N A W2 G N A Table 2 G not on for gas oil systems 5 4 Humidity output chart De humidificationSetting With Humidity Control Demand No N A Humidification Only Heat W Heat Fan W and or G Dehumidification Only Cool No G only Cool Fan Y and or G Table 3 When in dehumidification mode and EAC is set to Cool 2 Y2 will energize to extend cooling cycle See Configurat...

Страница 9: ...o configure the thermostat perform the following steps 1 Press then press repeatedly until is selected 2 Press to advance from one screen to the next Pressing will return you to the previous screen 3 Press the or to change settings within each screen Changes are saved automatically 4 To exit configuration mode press Auto exit occurs after two minutes with no icons touched 5 8 Configuration mode sett...

Страница 10: ... F 1 C to 5 C Set the minimum separation between heat setpoint and cool setpoint in Auto Changeover Mode Press the or to set deadband value Press to advance to the next screen CONFIG Figure 9 Heat Source There are six heat source settings WARNING Incorrect settings can damage system and or cause potentially dangerous conditions Use the code described in Configuration and Thermostat Lock Non Heat P...

Страница 11: ...thermostat is locked Press the or to select Press to advance to the next screen CONFIG Figure 13 Maximum Heat Setpoint 45 F to 90 F 7 C to 32 C Adjust to control the maximum heat set temperature allowed Press the or to select Press to advance to the next screen CONFIG HEAT Figure 14 Minimum Cool Setpoint 45 F to 90 F 7 C to 32 C Adjust to control the minimum cool set temperature allowed Press the ...

Страница 12: ...oner or dehumidifier to de humidify home Press the or to select Press to advance to the next screen CONFIG HUMIDITY Figure 20 Humidity Differential 1 to10 Set the percent difference between the setpoint humidity and when the humidifier or dehumidifier system turns on Press the or to select Press to advance to the next screen CONFIG HUMIDITY RH Figure 21 Condition to Turn On Set the condition for syste...

Страница 13: ... SLEEP The fan will run continuously during this scheduled period when the mode is not set to OFF To turn on the fan during one of the scheduled periods WAKE LEAVE RETURN SLEEP please do the following Press or to select Press to advance to the next screen CONFIG ON SCHEDULE FAN OFF Figure 25 Check Filter Timer 800 2500 hours After the number of fan running hours specified for example 1200 hours th...

Страница 14: ...de feature is configured The thermostat is controlling a dehumidifier including an air conditioner The thermostat will turn on the dehumidifier when the relative humidity is above the setpoint humidity by the differential Depending on the settings when the relative humidity reaches the differential humidity set or the room temperature is 3 F below the set cooling temperature the dehumidifier is turned o...

Страница 15: ...on the display for each stage of heat that is on For heat pumps there is a four minute delay for your compressor to restart after it has turned off To bypass the compressor time delay go to OFF mode and press HEAT HEAT MODE Figure 29 EM Heat Mode In this mode the compressor is bypassed and emergency heat is used This mode is only used with heat pumps HEAT MODE Figure 30 Cool Mode In this mode the t...

Страница 16: ... correct setting HEAT FAN Either the heating system or fan must be operating in order for the humidifier to turn on HEAT Heat must be operating in order for the humidifier to turn on no No condition other than humidity reading below setpoint and differential will turn on humidifier 1 Go to MENU HUMIDITY and press 2 Change the humidity setpoint above the relative humidity by the differential see Configu...

Страница 17: ... heat temperature and cool temperature The thermostat monitors the day and time while maintaining the specific conditions you have chosen for each period in your program Setting the program schedule 1 Press then press until EDIT is displayed 2 Press to enter Program Schedule 3 The day of the week flashes Use the or to select the day of the week You can select the days individually or if you keep goi...

Страница 18: ...ocked View fault Screen VIEW Day Month Figure 33 View month day and year VIEW Day Month Year Figure 34 View program schedule settings OFF shows when schedule is off SETTINGS show when schedule is on VIEW SCHEDULE SLEEP Mon Figure 35 View if locked or unlocked Unlocked Locked VIEW Figure 36 View filter status Accumulated fan run time displays VIEW Figure 37 Display setpoints fan and program informa...

Страница 19: ... is illuminated To view UPM s fault code go to Press multiple times to the last menu item If no fault history is recorded screen will show VIEW Er no VIEW Figure 39 If fault history is recorded screen will show VIEW E x month date time indicating the fault code date and time of the fault VIEW Day Month Figure 40 You can press or button to browse fault history The thermostat records the latest 20 f...

Страница 20: ...Schedule will be overridden until the next transition period To switch to the 1 5 hour override use the arrow This mode allows the user to override the Schedule set points for 1 5 hours Figure 41 6 10 Setting the vacation timer The vacation timer lets you set the date and time of your RETURN from vacation Until that date time the system will remain at the VACATION heating and cooling setpoints spe...

Страница 21: ...onal program schedule to record your settings MONDAY 1 WAKE LEAVE RETURN 6 00PM SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL TUESDAY 2 WAKE LEAVE RETURN 6 00PM SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL WEDNESDAY 3 WAKE LEAVE RETURN 6 00PM SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL THURSDAY 4 WAKE LEAVE RETURN 6 00PM SLEEP HEAT HEAT HEAT HEAT COOL COOL COOL COOL FRIDAY 5 WAKE LEAVE RETURN 6...

Страница 22: ...ot correct Calibrate thermostat see Configuration Mode Setting LOCK displays when any button is pressed Thermostat has the button lockout function activated see Lockout Unlock Feature and see Configuration Mode Setting Section 5 8 Heat or Cool not coming on Verify wiring is correct gently pull on each wire to verify there is a good connection at terminal block displays Check for low battery conditio...

Страница 23: ...Installation Operation Application Manual Bosch 2H 2C Hum Touch Technology Thermostat 23 Bosch Thermotechnology Corp 09 2016 Data subject to change NOTES ...

Страница 24: ...United States and Canada Bosch Thermotechnology Corp 50 Wentworth Avenue Londonderry NH 03053 Tel 866 305 9974 Fax 603 965 7581 www boschheatingandcooling com BTC 469202102 A 09 2016 ...

Отзывы: