Notice!
Planning should take the anticipated total current and line resistance into account to ensure
each detector has an operating voltage of at least 15
V
DC.
As soon as an LSN classic device is in a loop or stub, only loop or stub structures can be
used. In this case, T-tapping is no longer possible.
FPA-5000
FPA-5000
FPA-5000
1: Loop
2: 1 or 2 stubs
3: T-tap
FPA-5000
FPA-5000
4: 1 or 2 stubs and T-taps
mixed
5: Loop and stubs mixed with
T-taps
Tab.
2.1:
Possible structures in LSN
When configuring the detectors, it is essential to ensure that no mesh structures are created.
FPA-5000
FPA-5000
Mesh structures within a
stub structure
Mesh structures within a
loop structure
Tab.
2.2:
Unusable network structures