Installation and Maintenance
●Indoor unit:
9.2 Troubleshooting for Main Malfunction
1. Malfunction of Temperature Sensor F1, F2
Main detection points:
● Is the wiring terminal between the temperature sensor and the controller loosened or poorly contacted?
● Is there short circuit due to trip-over of the parts?
● Is the temperature sensor broken?
● Is mainboard broken?
Malfunction diagnosis process:
Is the wiring terminal between the
temperature sensor and the controller
loosened or poorly contacted?
Start
Insert the temperature
sensor tightly
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Is malfunction
eliminated
Is malfunction
eliminated
Is malfunction
eliminated
Replace it with a
temperature sensor with
the same model
Make the parts upright
Is there short circuit due to trip-
over of the parts
Is the temperature sensor normal
according to the resistance table?
Replace the mainboard with
the same model.
End
Содержание brisa BRS09HPJ1IA
Страница 4: ...1 1 Summary Part Technical Information Indoor Unit B2 BRS09 24HPJ1IA...
Страница 5: ...2 Technical Information BRS09HPJ1OA BRS12HPJ1OA BRS18HPJ1OA BRS24HPJ1OA Outdoor Unit...
Страница 29: ...26 6 1 Remote Controller Introduction of...
Страница 30: ...27 Technical Information...
Страница 31: ...28...
Страница 32: ...29 Technical Information...
Страница 89: ...86 Installation and Maintenance...
Страница 94: ...91 Installation and Maintenance BRS18HPJ1OA BRS24HPJ1OA Note Take heat pump for example...
Страница 95: ...92 Installation and Maintenance...
Страница 96: ...93 Installation and Maintenance...
Страница 97: ...94 Installation and Maintenance...
Страница 98: ...95 Installation and Maintenance...
Страница 99: ...96 Installation and Maintenance...